SF_ESPE (Electro-Sensitive Protective Equipment)

[Tip] Tip

The version of the function block as described here corresponds to the latest version of the function block in Version list of function blocks.

Applicable safety standards

SF_ESPE is a certified PLCopen function block. For detailed information about applied standards, see "PLCopen – Technical Committee 5 – Safety Software".

[Important] Important

The requirements listed in the standards must be fulfilled by the user.

Interface description

This safety-oriented block is used to monitor electro-sensitive protective equipment.

Table 30. VAR_INPUT

Name

Data Type

Initial Value

Description, parameter values

Activate

BOOL

FALSE

General input parameters

S_ESPE_In

SAFEBOOL

FALSE

Input which requests safety.

Variable

FALSE: ESPE actuated, request for safety-oriented response.

TRUE: ESPE not actuated, no request for safety-oriented response.

The safety controller has to be able to detect a very short interruption of the sensor when the ESPE is used as a trigger in applications.

S_StartReset

SAFEBOOL

FALSE

General input parameters

S_AutoReset

SAFEBOOL

FALSE

General input parameters

Reset

BOOL

FALSE

General input parameters


Table 31. VAR_OUTPUT

Name

Data Type

Initial Value

Description, parameter values

Ready

BOOL

FALSE

General output parameters

S_ESPE_Out

SAFEBOOL

FALSE

Output for safety-oriented response

FALSE: Safety output is inactive.

Request for safety-oriented response (for example, reset required or internal error active)

TRUE: Safety output is activated. No requirement for safety-oriented response.

Error

BOOL

FALSE

General output parameters

DiagCode

WORD

16#0000

Diagnostic codes


Figure 68. Function block: SF_ESPE

Function block: SF_ESPE

Functional description: SF_ESPE

This FB is a safety-oriented function block for monitoring electrosensitive protective equipment (ESPE). Its function is identical to SF_EmergencyStop. The S_ESPE_Out output signal is set to FALSE as soon as the S_ESPE_In input signal becomes FALSE. The S_ESPE_Out output signal is set to TRUE only if the S_ESPE_In input is TRUE and a reset occurs. The active reset depends on the defined S-StartReset, S_AutoReset, and Reset.

If S_AutoReset = TRUE: Acknowledgment is automatic.

If S_AutoReset = FALSE: A rising trigger edge at the Reset input must be used to acknowledge the enable.

If S_StartReset = TRUE: Acknowledgment is automatic the fist time the S-PLC is started.

If S_StartReset = FALSE: A rising trigger edge at the Reset input must be used to acknowledge the enable.

[Caution] Caution

The S_StartReset and S_AutoReset inputs shall only be activated if it is ensured that no hazardous situation can arise when the S-PLC is started.

[Tip] Tip

The function of the SF_ESPE and SF_EmergencyStop FBs is identical. Therefore, for further details, see the SF_EmergencyStop function block (Functional description).