UL 508-compliant motor overload monitoring
If the operation of the motor requires the compliance with the UL Standard 508, and the UL 508-compliant
motor overload monitoring is realised by the mathematical model of the I²xt monitoring,
the following conditions must be observed.
UL 508 condition 1:
In case of a motor load of 600 %, the I²xt warning must be output within 20 seconds.
–
A motor load of 600 % exists if the r.m.s. value of the total motor current displayed in parameter 0x2DD1:005 corresponds to 600% of the rated motor current
0x6075.
This condition can be fulfilled by setting the following parameters:
–
Motor utilisation (I²xt): thermal time constant - laminated core
0x2D4C:002
0x2D4C:002–
Motor utilisation (I²xt): influence winding
0x2D4C:003
0x2D4C:003–
Motor utilisation (I²xt): motor overload warning threshold
0x2D4E
0x2D4E–
Motor utilisation (I²xt): response
0x2D50:001
0x2D50:001–
Motor utilisation (I²xt): error threshold
0x2D50:002
0x2D50:002UL 508 condition 2:
In case of a motor load of 110 %, the I²xt warning at a motor rotating field frequency of
10 Hz must be output faster than at a motor rotating field frequency of 20 Hz.
–
The current motor rotating field frequency is displayed in parameter 0x2DDD.
–
A motor load of 110 % exists if the r.m.s. value of the total motor current displayed in parameter 0x2DD1:005 corresponds to 110 % of the rated motor current
0x6075.
This condition can be fulfilled by setting the following parameters:
–
I²xt: x1 = n01/nN (n01 ~ 0)
0x2D4D:001
0x2D4D:001–
I²xt: y1 = i01/iN (x = n01 ~ 0)
0x2D4D:002
0x2D4D:002–
I²xt: x2 = n02/nN (n02 = reduced cooling limit)
0x2D4D:003
0x2D4D:003–
I²xt: y2 = i02/iN (x = n02 = reduced cooling limit
0x2D4D:004
0x2D4D:004UL 508 condition 3:
After mains switching and a motor load > 100 %, the I²xt warning must be output faster than
in the same overload case before mains switching.
–
A motor load > 100 % exists if the r.m.s. value of the total motor current displayed in parameter 0x2DD1:005 is higher than the rated motor current
0x6075.
This condition can be fulfilled by setting the following parameters: