Web break monitoring

Only activate web break monitoring when the calculated diameter corresponds to the real diameter!
 
In the event of a web break:
–
The calculated diameter changes in the opposite direction to that of the winding direction.
 
–
The circumferential speed no longer corresponds to the line speed signal.
 
When the parameter Web break detection window size = 0 or = 2, a diameter change in the opposite direction to that of the winding direction is only still permissible within the window configured in the parameter Web break detection window size. 0x5051:072
How to activate web break monitoring:
1.
Set bit 24 of parameter Control words = TRUE. 0x5050:010
 
The last valid diameter value is maintained as soon as a web break is identified.
Function
Parameter index
Bit
Bit status
Web break monitoring detected
0x5050:110
24
TRUE
Diagnose winding direction
0x5050:110
17
TRUE
Loading a start diameter that significantly deviates from the real diameter in the direction opposite the winding direction can unintentionally trigger the monitoring function. This can happen, for example, when a standard diameter of 50 [%] is loaded at the rewinder and the real diameter is only 45 [%]. In such a case, the activated web break monitoring function will prevent the diameter value from changing to the real 45 [%].
 
Parameter
Address
Name / setting range / [default setting]
Information
0x5051:073
Web break monitoring mode
0
Unexpected diameter change+dancer in limit position
1
Dancer in limit position
2
Unexpected diameter change