Terminating the identification
The identification is completed as soon as the motor has come to a standstill again, no errors have been reported and xDone has been set to TRUE.
Check the moment of inertia identified in the parameter Measured moment of inertia for plausibility.
0x5051:118
0x5051:118Execute the identification of the moment of inertia several times. Vary the filter time for the speed and the torque.
Significant non-linear friction in the system adversely affects the calculation of the moment of inertia.
The results of the various identification runs for which the filter times were varied must be used to calculate a mean value. After successful identification, the results will be available in the parameter Measured moment of inertia.
0x5051:118
0x5051:118The mean value for J-const. must be used as the parameter Constant moment of inertia and for J_max as the parameter Max. moment of inertia.
Parameters for the moment of inertia:
–
Constant moment of inertia
0x5051:111
0x5051:111–
Max. moment of inertia
0x5051:112
0x5051:112Relevant parameters of other functions
|
Address
|
Name
|
Default setting
|
Setting range
|
|
Measured moment of inertia
|
- (Read only)
|
||