Saving control parameters persistently
After a successful optimization run, the optimized control parameters are active and available in the following objects:
-
0x2900:001 (speed controller gain)
-
0x2900:002 (Speed controller reset time)
-
0x2980:000 (Position Controller Gain)
-
Subnidex :093 (position controller gain)
After optimization, these values must still be saved manually in the storage medium in a way that is safe from power failure ("save parameter set").
The parameter set must not be saved while optimisation is active.
Save parameter set with PLCDesigner
-
The PLCDesigner project must be available as a boot application on the Lenze controller (“Online”-> “Create boot application for Lenze devices”).)
-
Now the parameter set can be saved (“Online”-> “Save parameter sets”).
-
If the values are also to be available offline in the PLCDesigner project, the parameters must be uploaded in the parameter dialog during login to the controller.
Save parameter sets with EasyStarter for i950-devices
For i950 devices, the parameters can be saved via EasyStarter (“Save” (F6)).