EtherNet/IP communication monitoring
Implicit Messaging Timeout
The inverter (adapter) monitors the I/O connection to the scanner. If no "Implicit Message" has been received within the timeout parameterized by the scanner for implicit messages, the reaction set in 0x2859:001 is triggered in the inverter.
Explicit Messaging Timeout
If no "Explicit Message" has been received within the timeout parameterized by the scanner for explicit messages, the reaction set in 0x2859:006 is triggered in the inverter.
Timeout for process controlling write accesses
The monitoring time set in 0x23A1:010 is used to monitor process-controlling write accesses to technology applications.
Write accesses within this monitoring time reset the watchdog. After the monitoring time has elapsed, the response set in 0x2859:007 is triggered in the inverter.
The following is monitored:
Acyclic write accesses (Explicit Messages) to the following attributes
–
Write accesses to the data attribute of the output object of the assembly object instance of the TA.
0x04-Assembly Object
0x04-Assembly Object –
Write accesses to the Lenze Class Object 104/0x68, Instance 1, Attribute 3 (I/O image of consumed data).
0x68-Lenze Class Object 104
0x68-Lenze Class Object 104 –
Write accesses to the AC Drive Class Object 42/0x2A, Instance 1
0x2A-AC Drive Object
0x2A-AC Drive Object –
Attribute 4 (NetRef)
–
Attribute 8 (SpeedRef)
–
Attribute 12 (TorqueRef)
–
Write accesses to the Control Supervisor Class Object 41/0x29, Instance 1
0x29-Control Supervisor Object
0x29-Control Supervisor Object–
Attribute 3 (Run1)
–
Attribute 4 (Run2)
–
Attribute 5 (NetCtrl)
Cyclic write accesses (Implicit Messages)
–
A Exclusive Owner connection associated with the current TA is established, which exchanges valid I/O data within the parameterized timeout time.
The following write accesses to Lenze parameters do not reset the watchdog:
Write accesses to the Lenze Class Object 110/0x6E via Explicit Messaging.
0x6E-Lenze Class Object 110
0x6E-Lenze Class Object 110Write accesses via EASY Starter
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x23A1:010
|
EtherNet/IP settings: Timeout
0 ... [10000] ... 65535
|
Setting of the maximum permissible time-out for the CIP communication.
When the specified monitoring time has elapsed, the response set in 0x2859:007 is triggered in the inverter.
|
|
|
0x2859:007
|
Network monitoring: Timeout communication
|
Selection of the response to the time-out during the CIP communication.
The monitoring time for the CIP communication is defined in 0x23A1:010.
|
|
|
0
|
No response
|
||
|
1
|
Fault > CiA402
|
||
|
2
|
Warning
|
||
|
0x2859:001
|
Network monitoring: Watchdog elapsed
|
Selection of the response to a permanent interruption of the communication to the IO controller.
|
|
|
0
|
No response
|
||
|
1
|
Fault > CiA402
|
||
|
2
|
Warning
|
||
|
0x2859:006
|
Network monitoring: Time-out explicit message
|
Selection of the response to timeouts during transfer of Explicit Messages.
|
|
|
0
|
No response
|
||
|
1
|
Fault > CiA402
|
||
|
2
|
Warning
|
||
Severity