EtherNet/IP communication monitoring

Implicit Messaging Timeout
The inverter (adapter) monitors the I/O connection to the scanner. If no "Implicit Message" has been received within the timeout parameterized by the scanner for implicit messages, the reaction set in 0x2859:001 is triggered in the inverter.
 
Explicit Messaging Timeout
If no "Explicit Message" has been received within the timeout parameterized by the scanner for explicit messages, the reaction set in 0x2859:006 is triggered in the inverter.
 
Timeout for process controlling write accesses
The monitoring time set in 0x23A1:010 is used to monitor process-controlling write accesses to technology applications.
Write accesses within this monitoring time reset the watchdog. After the monitoring time has elapsed, the response set in 0x2859:007 is triggered in the inverter.
The following is monitored:
Acyclic write accesses (Explicit Messages) to the following attributes
–
Write accesses to the data attribute of the output object of the assembly object instance of the TA. 0x04-Assembly Object 
 
–
Write accesses to the Lenze Class Object 104/0x68, Instance 1, Attribute 3 (I/O image of consumed data). 0x68-Lenze Class Object 104 
 
–
Write accesses to the AC Drive Class Object 42/0x2A, Instance 1 0x2A-AC Drive Object 
 
–
Attribute 4 (NetRef)
 
–
Attribute 8 (SpeedRef)
 
–
Attribute 12 (TorqueRef)
 
 
–
Write accesses to the Control Supervisor Class Object 41/0x29, Instance 1 0x29-Control Supervisor Object
 
–
Attribute 3 (Run1)
 
–
Attribute 4 (Run2)
 
–
Attribute 5 (NetCtrl)
 
 
Cyclic write accesses (Implicit Messages)
–
A Exclusive Owner connection associated with the current TA is established, which exchanges valid I/O data within the parameterized timeout time.
 
The following write accesses to Lenze parameters do not reset the watchdog:
Write accesses to the Lenze Class Object 110/0x6E via Explicit Messaging. 0x6E-Lenze Class Object 110
Write accesses via EASY Starter
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x23A1:010
EtherNet/IP settings: Timeout
0 ... [10000] ... 65535
Setting of the maximum permissible time-out for the CIP communication.
When the specified monitoring time has elapsed, the response set in 0x2859:007 is triggered in the inverter.
0x2859:007
Network monitoring: Timeout communication
Selection of the response to the time-out during the CIP communication.
The monitoring time for the CIP communication is defined in 0x23A1:010.
Associated event ID:
–
822313236 | 0x31038114 - Network - Overall communication time-out
 
0
No response
1
Fault > CiA402
2
Warning
0x2859:001
Network monitoring: Watchdog elapsed
Selection of the response to a permanent interruption of the communication to the IO controller.
Associated event ID:
–
822313360 | 0x31038190 - Network - Watchdog time-out
 
0
No response
1
Fault > CiA402
2
Warning
0x2859:006
Network monitoring: Time-out explicit message
Selection of the response to timeouts during transfer of Explicit Messages.
0
No response
1
Fault > CiA402
2
Warning