Selecting the setpoint source
–
The setpoint source is selected via the following parameter. 0x5020:002
–
The external setpoint configuration is only used when bit 29 has not been set in the control signals.
0x5030:010, Bit 29
0x5030:010, Bit 29–
The selected setpoint value is displayed in the External setpoint speed parameter.
0x5032:016
0x5032:016Optional slot B (application feedback)
Fig. 1: Optional slot (B)
If the Actual speed parameter is selected as the source, the speed setpoint is output from the optional slot (B) of the device (see Fig. "Optional slot (B)").
0x500B:011
0x500B:011Feedback for slot B can for instance be provided by an encoder.
Fig. 2: Selection of the speed source
Analog input 1
The Analog input 1 (see plug connector X3) of the inverter can also serve as a speed source. The analog input supplies via the parameter Diagnostics of analog input 1: Value in percent scaled, the analog input supplies a percentage value which refers to a reference speed.
0x2DA4:005.
0x2DA4:005.The reference speed is set via the parameter Reference speed for analog input 1.
0x5020:009
0x5020:009The parameterisation and scaling of the analog input takes place in the basic settings of the inverter.
Fig. 3: Front view of the plug connector X3 with analog input 1
Fig. 4: Analog input 1 as speed source
Example
The analog input supplies a percentage value of 50% via the parameter.
0x2DA4:005
0x2DA4:005The reference speed is 500 units/s. The resulting setpoint speed is therefore 250 units/s.
0x5020:009
0x5020:009Parameter
0x2636:013