Selecting the setpoint source

–
The setpoint source is selected via the following parameter. 0x5020:002
 
–
The external setpoint configuration is only used when bit 29 has not been set in the control signals. 0x5030:010, Bit 29
 
–
The selected setpoint value is displayed in the External setpoint speed parameter. 0x5032:016
 
 
Optional slot B (application feedback)
Fig. 1: Optional slot (B)
If the Actual speed parameter is selected as the source, the speed setpoint is output from the optional slot (B) of the device (see Fig. "Optional slot (B)"). 0x500B:011
Feedback for slot B can for instance be provided by an encoder.
Fig. 2: Selection of the speed source
 
Analog input 1
The Analog input 1 (see plug connector X3) of the inverter can also serve as a speed source. The analog input supplies via the parameter Diagnostics of analog input 1: Value in percent scaled, the analog input supplies a percentage value which refers to a reference speed. 0x2DA4:005.
The reference speed is set via the parameter Reference speed for analog input 1. 0x5020:009
The parameterisation and scaling of the analog input takes place in the basic settings of the inverter.
Fig. 3: Front view of the plug connector X3 with analog input 1
Fig. 4: Analog input 1 as speed source
 
Example
The analog input supplies a percentage value of 50% via the parameter. 0x2DA4:005
The reference speed is 500 units/s. The resulting setpoint speed is therefore 250 units/s. 0x5020:009
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2DA4:005
Diagnostics of analog input 1: Scaled percent value
–
Read only: x.xx %
 
Display of the actual value at the analog input, scaled with the following parameters:
–
Minimum value for scaling. 0x2636:013
 
–
Maximum value for scaling. 0x2636:014
 
0x4001
Interface selection
Selecting the interface determines the interface that receives the signals.
0
Fieldbus network
Control of the application via the fieldbus.
1
Onboard EtherCAT
Activation of the application via the system bus.
0x500B:011
Actual velocity
–
Read only
 
The current speed value is resolved with 4 decimal positions.
0x5020:009
Reference velocity for analog input 1
0.0000 ... [500.0000] ... 214748.3647
The reference speed for the percentage value of the analog input.
0x5030:012
External velocity
-214748.3648 ... [0.0000] ... 214748.3647
Value for the external setpoint velocity.
0x5032:015
Active profile: Velocity setpoint
–
Read only
 
The profile setpoint speed is given in the unit [unit/s]. The value of the profile setpoint speed is displayed with 4 decimal positions.
0x5032:016
External velocity setpoint
–
Read only
 
0x5032:017
Active set velocity
–
Read only
 
The speed is resolved with 4 decimal positions. The speed is referred to in the unit [unit/s].