Loading the start diameter

Loading the start diameter has the highest priority.
 
If the diameter has changed because, for example, a new reel has been inserted, a suitable start diameter must be loaded at the beginning of the following wrapping process.
Setting bit 22 = TRUE of the control word loads the start diameter. 0x5050:010 Bit 22
If bit 22 is held TRUE, the selected value is accepted cyclically. As long as the diameter is set or loaded, the status bit 22 = TRUE remains in the parameter Status signals. 0x5050:110 Bit 22
The following table describes the different use applications to specify the source of the start diameter.
Application
Source of setpoint diameter 0x5020:022
Source of start diameter 0x5051:065
Start diameter is predefined in the parameter Start diameter.
0x5020:022 = any
0x5051:065 = 0
Diameter is specified via the fieldbus Control word DW 1.
0x5020:022 = 0
0x5051:065 = 1
Diameter is detected by a sensor at AIN1 of the inverter
0x5020:022 = 1
0x5051:065 = 1
Fig. 1: Selection source of the start diameter
 
Relevant parameters of other functions
Address
Name
Default setting
Setting range
Reference diameter analog input 1
1000.0000 mm
0.0000 ... 214748.3647 mm
Set diameter source
External [0]
Selection list
Start diameter source
Parameter [0]
Selection list
Start diameter
100.0000 mm
1.0000 ... 10000.0000 mm
External start diameter
x.xxxx mm (Read only)