Diameter adjustment
The diameter is detected by ultrasonic sensors with an analog output variable of 0 ... 10 V. In the parameter Reference diameter analog input 1, the reference value for the sensor signal is defined.
0x5020:013
0x5020:013If no real diameter value is available because it is not possible for users to input data or no sensor is available, load a mean value for the diameter.
The curve function Y = f(x) can be used to compensate for potential nonlinearities of a sensor. This function affects the value that is diagnosed via the parameter Set diameter.
0x5051:075
0x5051:075With the default setting of the curve function, the value is not adapted. The start diameter is transmitted 1:1.
The curve function is configured via the parameters X value for diameter adaption and Y value for diameter adaption.
Parameters for the curve function:
–
X value for diameter adaption
0x5051:076, 078, 080, 082, 084, 086, 088, 090, 092
0x5051:076, 078, 080, 082, 084, 086, 088, 090, 092–
Y value for diameter adaption
0x5051:077, 079, 081, 083, 085, 087, 089, 091, 093
0x5051:077, 079, 081, 083, 085, 087, 089, 091, 093Fig. 1: Adaptation of the sensor signal via a curve function