Controller.USB-Interface

This functionality has been available since controller firmware version 1.13.0. Using a USB stick is a critical attack vector for hackers and cyberattacks. The USB interface is therefore deactivated by default.

As of V1.13 of the controller firmware, a plugged-in USB stick is not mounted by default so that no malicious code can be executed on the controller in this way.

For controllers in factory default, mounting a USB stick is initially active to enable initial commissioning.

This state is indicated by a flashing ready LED every second.

After installing a firmware update, mounting the USB stick is deactivated.

The mounting of the USB stick is also deactivated as soon as a boot project is loaded onto the controller.

If a boot project is already available during the initial startup of a PLC in factory default, mounting the USB stick will be deactivated.

The PLC is in factory default when the ready LED flashes blue every second.

The PLC can be parameterized in two different ways.

- Deactivated [0]

- Activated [1]

This is done by the parameter 0x5902.

A diagram of a customer service

Description automatically generated with medium confidence

USB-Interface

Activating the USB interface deactivates the security functionality, leaving the PLC vulnerable to cyberattacks.

  • The USB interface must be disabled to fulfill the CR 3.2 of the IEC 62443 which is the standard for the Cyber Resilience Act of the EU.Activating the USB interface deactivates the security functionality, leaving the PLC vulnerable to cyberattacks.

Backup & Restore

Backup and restore functions are the main features of different controllers. Deactivation of the USB interface is still present in firmware 1.13.xx.

When a user activates the PLC command to perform a backup or restore, the PLC will activate the USB interface and execute the command. Afterwards, the USB interface will return to its previous state.

Controller.USB-Stick:Security functionality verification

To verify that the USB deactivation is functioning correctly, you must use a USB stick. Copy a firmware file to the “firmware\active” folder on the USB stick. Then, plug in the USB stick and restart the PLC. After restarting, restart again and check the PLC's firmware version.

If the PLC has the same firmware as before, the deactivation is working correctly. This security feature only works on a PLC with a non-blinking RDY LED.

  • When a PLC is first started, the RDY LED flashes every second for 100 ms. If it is not flashing, then the PLC is not in factory default and has been used by someone else.