L_MC1P_ManJogOpenLoop

This FB can be used to implement controlled movement of the lower-level drive. Setpoints for current and frequency are increased and reduced using ramps. A maximum switch-off time and a starting angle for the motor rotary field can also be set.

The FB accesses the parameters of drive:

  • Setpoints for current and frequency
  • Ramp times
  • Maximum switch-off time
  • Starting angle of the motor rotary field

This FB enables you to switch between the two parameter sets that are available in the drive.

Supported devices:
  • i750
  • i950

 

 

 

L_MC1P_ManJogOpenLoop

 

 

 

AXIS_REF

-

Axis

xBusy

-

BOOL

BOOL

-

xEnable

xOperationEnabled

-

BOOL

BOOL

-

xJogPositive

xDone

-

BOOL

BOOL

-

xJogNegative

xActive

-

BOOL

BOOL

-

xParameterSet2

xCommandAborted

-

BOOL

xError

-

BOOL

eErrorID

-

L_IE1P_Error

 

 

 

 

 

 

 

 

Inputs

Name

Data type

Information/possible settings

Axis

AXIS_REF

Transfer of the axis data structure

Motion axes (AXIS_REF)

xEnable

BOOL

FALSE ä TRUE

  • Enable MOL function (controlled operation). Activation is only permissible when the inverter is disabled.
  • The axis changes to the operating mode Manual open-loop (0x6060 = -13). It exits this mode again when the edge changes from TRUE æ FALSE.
  • The controller is released and the current brought to its set final value 0x2C67:1 (0x2C67:11 for parameter set 2) over the current ramp time set in parameter 0x2C67:3 (0x2C67:13 for parameter set 2).

xJogPositive

xJogNegative

BOOL

Logic of the control signal:

xJogPositive

xJogNegative

Action

FALSE

FALSE

No action

FALSE ä TRUE

FALSE

The frequency is brought to its final set value 0x2C67:2 (0x2C67:12 for parameter set 2) using the frequency ramp time set in parameter 0x2C67:4 (0x2C67:14 for parameter set 2).

The axis moves with positive direction of rotation of the rotary field frequency as long as xJogPositive = TRUE and the configured switch-off time parameter 0x2C67:6 (0x2C67:16 for parameter set 2) has not yet been reached.

Note :

If the frequency 0x2C67:2 (0x2C67:12 for parameter set 2) is configured with a negative sign, the axis moves with negative direction of rotation of the rotating field frequency. The motor's set mounting position is not taken into account.

TRUE æ FALSE

FALSE

Axis stops

The frequency is reduced from its current value to zero over the frequency ramp time set in parameter 0x2C67:4 (0x2C67:14 for parameter set 2).

FALSE

FALSE ä TRUE

The frequency is brought to its inverted final set value 0x2C67:2 (0x2C67:12 for parameter set 2) over the frequency ramp time set in parameter 0x2C67:4 (0x2C67:14 for parameter set 2).

The axis moves with negative direction of rotation of the rotary field frequency as long as xJogPositive = TRUE and the configured switch-off time parameter 0x2C67:6 (0x2C67:16 for parameter set 2) has not yet been reached.

Note :

If the frequency 0x2C67:2 (0x2C67:12 for parameter set 2) is configured with a negative sign, the axis moves with positive direction of rotation of the rotating field frequency. The motor's set mounting position is not taken into account.

FALSE

TRUE æ FALSE

Axis stops

The frequency is reduced from its current value to zero over the frequency ramp time set in parameter 0x2C67:4 (0x2C67:14 for parameter set 2).

FALSE ä TRUE

FALSE ä TRUE

Axis stops with warning, error output is set in the FB.

The frequency is reduced from its current value to zero over the frequency ramp time set in parameter 0x2C67:4 (0x2C67:14 for parameter set 2).

TRUE

FALSE ä TRUE

FALSE ä TRUE

TRUE

xParameterSet2

BOOL

TRUE

Enable 2nd parameter set for MOL.

(1st parameter set: 0x2C67, subcode 1 to 6 active)

(2nd parameter set: 0x2C67, subcode 11 to 16 active)

Note :

A changeover is also possible at any time during active jogging operation.

Outputs

Name

Data type

Value/meaning

xBusy

BOOL

TRUE

The FB has been enabled.

xOperationEnabled

BOOL

TRUE

The MOL function and controlled operation are active and the controller has been enabled via the function block.

xActive

BOOL

TRUE

Frequency setpoint generation is active.

xDone

BOOL

TRUE

Frequency setpoint generation is completed.

xCommandAborted

BOOL

TRUE

The activated function has been aborted.

xError

BOOL

TRUE

An error has occurred. For details see eErrorID .

eErrorID

If xError = TRUE: Error number for the error that has occurred.

Parameter

Name

Info

  • 0x2C67:1 ... 0x2C67:6
  • 0x2C67:11 ... 0x2C67:16

The parameters are described in:

i950 commissioning manual

Parameters:

  • Can be changed when the controller is enabled.
  • Are persistable.
  • Cannot be mapped.
Note!
  • If the frequency value and/or the current level is changed by switching over the parameter group using xParameterSet2 , the respective process variable is brought to the new final value using the currently selected ramp slope. The following applies: the frequency will only be changed when the current setpoint has reached its final value.
  • The switch-off time period begins every time xJogPositive and xJogNegative are changed. The switch-off time restarts when the parameter group is switched over during operation. When the switch-off time is reached, the frequency is reduced to 0 Hz over the currently selected ramp time. The drive stops at the end of the frequency ramp while remaining energised.
  • The following applies for motors with brakes (0x2820:1 < 2): automatic brake operation is adjusted so that the brake is only released when the current setpoint reaches its final value. The initial brake logic is then active again until the inverter is disabled. The release time for the brake is taken into account in the function block.
Signal characteristics

Figure 1 shows the situation when the current has reached its final value after a controller release and jogging has then been started by xJogPositive:=TRUE . The controller is shut down when the switch-off time is reached.

Figure 1: Situation 1, jogging starts when the current has reached its final value.

Figure 2 shows the following behaviour: if a negative edge change occurs for the jogging bit within the switch-off time (here: xJogPositive ), the frequency is reduced to 0 Hz. The frequency is increased again with the next rising edge of a jogging bit ( xJogPositive or xJogNegative ). The switch-off time is restarted for the new positive edge.

Figure 2: Situation 2, jogging starts when the current reaches its final value and jogging is stopped by xJogPositive:=False

Figure 3 shows the situation for a parameter group changeover. In this example, the axis switches from Group 1 to Group 2. The new ramp slopes are active after the changeover. The axis rises to the new final current value 2 using the current slope 2 (final current value 2 > final current value 1 in the figure). Once the final current value 2 is reached, the axis switches to the new final frequency 2 using the frequency slope 2. The switch-off time 2 period begins when the axis switches from one group to the other.

Figure 3: Situation 3, jogging starts once the current has reached its final value and parameters are switched during jogging.