L_MC1P_ManJogOpenLoop
This FB can be used to implement controlled movement of the lower-level drive. Setpoints for current and frequency are increased and reduced using ramps. A maximum switch-off time and a starting angle for the motor rotary field can also be set.
The FB accesses the parameters of drive:
- Setpoints for current and frequency
- Ramp times
- Maximum switch-off time
- Starting angle of the motor rotary field
This FB enables you to switch between the two parameter sets that are available in the drive.
Supported devices:
- i750
- i950
|
|
|
|
L_MC1P_ManJogOpenLoop |
|
|
|
|
|---|---|---|---|---|---|---|---|
|
AXIS_REF |
- |
|
Axis |
xBusy |
|
- |
BOOL |
|
BOOL |
- |
|
xEnable |
xOperationEnabled |
|
- |
BOOL |
|
BOOL |
- |
|
xJogPositive |
xDone |
|
- |
BOOL |
|
BOOL |
- |
|
xJogNegative |
xActive |
|
- |
BOOL |
|
BOOL |
- |
|
xParameterSet2 |
xCommandAborted |
|
- |
BOOL |
|
|
|
|
|
xError |
|
- |
BOOL |
|
|
|
|
|
eErrorID |
|
- |
L_IE1P_Error |
|
|
|
|
|
|
|
|
|
Inputs
Outputs
Parameter
|
Name |
Info |
|
|---|---|---|
|
The parameters are described in: i950 commissioning manual |
|
Parameters:
- Can be changed when the controller is enabled.
- Are persistable.
- Cannot be mapped.
|
Note!
|
Signal characteristics
Figure 1 shows the situation when the current has reached its final value after a controller release and jogging has then been started by
xJogPositive:=TRUE
. The controller is shut down when the switch-off time is reached.
Figure 1: Situation 1, jogging starts when the current has reached its final value.
Figure 2 shows the following behaviour: if a negative edge change occurs for the jogging bit within the switch-off time (here: xJogPositive ), the frequency is reduced to 0 Hz. The frequency is increased again with the next rising edge of a jogging bit ( xJogPositive or xJogNegative ). The switch-off time is restarted for the new positive edge.
Figure 2: Situation 2, jogging starts when the current reaches its final value and jogging is stopped by
xJogPositive:=False
Figure 3 shows the situation for a parameter group changeover. In this example, the axis switches from Group 1 to Group 2. The new ramp slopes are active after the changeover. The axis rises to the new final current value 2 using the current slope 2 (final current value 2 > final current value 1 in the figure). Once the final current value 2 is reached, the axis switches to the new final frequency 2 using the frequency slope 2. The switch-off time 2 period begins when the axis switches from one group to the other.
Figure 3: Situation 3, jogging starts once the current has reached its final value and parameters are switched during jogging.
Motion axes (AXIS_REF)