Homing: TP-Configuration (subindex 80 )
|
|
|||||||||||||
|
Homing: TP-Configuration
|
|||||||||||||
|
Selection list (Lenze setting printed in bold) |
Info |
||||||||||||
|
0 |
ExternalSource |
ExternalSource |
|||||||||||
|
1 |
DigIn01_PosEdge(TP1) |
DigIn01_PosEdge(TP1) |
|||||||||||
|
2 |
DigIn01_NegEdge(TP1) |
DigIn01_NegEdge(TP1) |
|||||||||||
|
3 |
DigIn01_AnyEdge(TP1) |
DigIn01_AnyEdge(TP1) |
|||||||||||
|
4 |
ZeroPulse(TP1) |
ZeroPulse(TP1) |
|||||||||||
|
11 |
DigIn02_PosEdge(TP2) |
DigIn02_PosEdge(TP2) |
|||||||||||
|
12 |
DigIn02_NegEdge(TP2) |
DigIn02_NegEdge(TP2) |
|||||||||||
|
13 |
DigIn02_AnyEdge(TP2) |
DigIn02_AnyEdge(TP2) |
|||||||||||
|
14 |
ZeroPulse(TP2) |
ZeroPulse(TP2) |
|||||||||||
|
21 |
DigIn03_PosEdge(TP3) |
DigIn03_PosEdge(TP3) |
|||||||||||
|
22 |
DigIn03_NegEdge(TP3) |
DigIn03_NegEdge(TP3) |
|||||||||||
|
23 |
DigIn03_AnyEdge(TP3) |
DigIn03_AnyEdge(TP3) |
|||||||||||
|
24 |
ZeroPulse(TP3) |
ZeroPulse(TP3) |
|||||||||||
|
31 |
DigIn04_PosEdge(TP4) |
DigIn04_PosEdge(TP4) |
|||||||||||
|
32 |
DigIn04_NegEdge(TP4) |
DigIn04_NegEdge(TP4) |
|||||||||||
|
33 |
DigIn04_AnyEdge(TP4) |
DigIn04_AnyEdge(TP4) |
|||||||||||
|
34 |
ZeroPulse(TP4) |
ZeroPulse(TP4) |
|||||||||||
|
5 |
ZeroPulse2ndFdb(TP1) |
ZeroPulse2ndFdb(TP1) |
|||||||||||
|
15 |
ZeroPulse2ndFdb(TP2) |
ZeroPulse2ndFdb(TP2) |
|||||||||||
|
25 |
ZeroPulse2ndFdb(TP3) |
ZeroPulse2ndFdb(TP3) |
|||||||||||
|
35 |
ZeroPulse2ndFdb(TP4) |
ZeroPulse2ndFdb(TP4) |
|||||||||||
|
|
UNSIGNED_32 |
||||||||||||
The motor has only one position encoder and therefore only one zero pulse. However, two evaluation channels are available to the user. This means that one channel can be used for homing while the other channel is used for the TP (MC_Touchprobe) at the same time.
Example: If channel 1 (mode 4) is used for the MC_Touchprobe, channel 2 (mode 14) must be selected for the zero pulse when homing.
If the reference information is no longer available when the system is restarted, this may be caused by an encoder error or a defective encoder cable. Please check the logbook entries of the control.
|
Logbook entry |
Cause |
|---|---|
|
PosReconstr.:Data inconsistent |
Data not consistent |
|
PosReconstr.:HomePosAvailable not active |
Reference not known before mains switching |
|
PosReconstr.:PosReconstr. not activated |
Post reconstruction was not active before mains switching |
|
PosReconstr.:Axis was virtual |
Axis was virtual before mains switching |
|
PosReconstr.:Orientation Changed |
Mounting position different before mains switching |
|
PosReconstr.:TraversingRange Changed |
Traversing range different before mains switching |
|
PosReconstr.:CycleLength Changed |
Cycle length different before mains switching |
|
PosReconstr.:Unitfactor Changed |
Unit factor different before mains switching |
|
PosReconstr.:DataVersion Changed |
Internal error retain data |
|
PosReconstr.:No Data Available |
Internal error retain data |
|
PosReconstr.:Pos. Outside RestoreTreshold |
Difference between current position and the position stored safe against mains failure is greater than the set tolerance. |
|
PosReconstr.:Enc.CRC Changed |
|
|
PosReconstr.:No FeedbackPos Available |
|
|
PosReconstr.:MotorRev. Eq. Zero |
|
|
PosReconstr.:Reset by Feedb. Open circ. |
Resolver: Wire breakage error |
|
PosReconstr.:Reset by Enc. Error |
Encoder monitoring: Pulse deviation detected |
|
PosReconstr.:Reset by Feedb. Changed |
Hiperface absolute value encoder: Home position lost after temporary interruption of 24 V supply |
|
PosReconstr.:No Memory Available |
Internal error retain data |