Homing: TP-Configuration (subindex 80 )

Virtual axis Encoder 9400 HighLine i700 servo inverter i500 inverter i950 servo inverter

Homing: TP-Configuration

Selection list (Lenze setting printed in bold)

Info

0

ExternalSource

ExternalSource

1

DigIn01_PosEdge(TP1)

DigIn01_PosEdge(TP1)

2

DigIn01_NegEdge(TP1)

DigIn01_NegEdge(TP1)

3

DigIn01_AnyEdge(TP1)

DigIn01_AnyEdge(TP1)

4

ZeroPulse(TP1)

ZeroPulse(TP1)

11

DigIn02_PosEdge(TP2)

DigIn02_PosEdge(TP2)

12

DigIn02_NegEdge(TP2)

DigIn02_NegEdge(TP2)

13

DigIn02_AnyEdge(TP2)

DigIn02_AnyEdge(TP2)

14

ZeroPulse(TP2)

ZeroPulse(TP2)

21

DigIn03_PosEdge(TP3)

DigIn03_PosEdge(TP3)

22

DigIn03_NegEdge(TP3)

DigIn03_NegEdge(TP3)

23

DigIn03_AnyEdge(TP3)

DigIn03_AnyEdge(TP3)

24

ZeroPulse(TP3)

ZeroPulse(TP3)

31

DigIn04_PosEdge(TP4)

DigIn04_PosEdge(TP4)

32

DigIn04_NegEdge(TP4)

DigIn04_NegEdge(TP4)

33

DigIn04_AnyEdge(TP4)

DigIn04_AnyEdge(TP4)

34

ZeroPulse(TP4)

ZeroPulse(TP4)

5

ZeroPulse2ndFdb(TP1)

ZeroPulse2ndFdb(TP1)

15

ZeroPulse2ndFdb(TP2)

ZeroPulse2ndFdb(TP2)

25

ZeroPulse2ndFdb(TP3)

ZeroPulse2ndFdb(TP3)

35

ZeroPulse2ndFdb(TP4)

ZeroPulse2ndFdb(TP4)

Read access Write access Can only be changed in "Disabled" state No download

UNSIGNED_32

The motor has only one position encoder and therefore only one zero pulse. However, two evaluation channels are available to the user. This means that one channel can be used for homing while the other channel is used for the TP (MC_Touchprobe) at the same time.

Example: If channel 1 (mode 4) is used for the MC_Touchprobe, channel 2 (mode 14) must be selected for the zero pulse when homing.

If the reference information is no longer available when the system is restarted, this may be caused by an encoder error or a defective encoder cable. Please check the logbook entries of the control.

Logbook entry

Cause

PosReconstr.:Data inconsistent

Data not consistent

PosReconstr.:HomePosAvailable not active

Reference not known before mains switching

PosReconstr.:PosReconstr. not activated

Post reconstruction was not active before mains switching

PosReconstr.:Axis was virtual

Axis was virtual before mains switching

PosReconstr.:Orientation Changed

Mounting position different before mains switching

PosReconstr.:TraversingRange Changed

Traversing range different before mains switching

PosReconstr.:CycleLength Changed

Cycle length different before mains switching

PosReconstr.:Unitfactor Changed

Unit factor different before mains switching

PosReconstr.:DataVersion Changed

Internal error retain data

PosReconstr.:No Data Available

Internal error retain data

PosReconstr.:Pos. Outside RestoreTreshold

Difference between current position and the position stored safe against mains failure is greater than the set tolerance.

PosReconstr.:Enc.CRC Changed

 

PosReconstr.:No FeedbackPos Available

 

PosReconstr.:MotorRev. Eq. Zero

 

PosReconstr.:Reset by Feedb. Open circ.

Resolver: Wire breakage error

PosReconstr.:Reset by Enc. Error

Encoder monitoring: Pulse deviation detected

PosReconstr.:Reset by Feedb. Changed

Hiperface absolute value encoder: Home position lost after temporary interruption of 24 V supply

PosReconstr.:No Memory Available

Internal error retain data