Closed-loop tension control

A closed control loop can be added to the concept of simple open-loop tension control. It is used if excessive tensile force deviations are expected or detected despite friction and acceleration compensation. A closed-loop tension controller with PID structure has a corrective function and an additive effect on the torque feedforward control path from open-loop tension control.

For tension control, the drive can be switched to torque-based or speed-based mode. The tension controller with PID structure works in a corrective manner and has an additive effect

  • on the torque feedforward control path from the tension control if the eTensCtrlMode = 0 ("TorqueBased") parameter is set or

  • set to the speed feedforward control path from the speed control if eTensCtrlMode = 1 ("SpeedBased") is set.

Closed-loop tension control is activated as soon as a factor greater than 0% is present at the lrTensCtrlInfluence input with a P gain of scPar.lrTensCtrlGain > 0. The closed-loop tension controller has a direct multiplicative effect on the correcting variable of the controller.

The actual tensile force is expected from the lrActTensIn input in the unit [N] to be used in closed-loop tension control. Filtering the actual tensile force value using a PT1 filter can have a positive effect on the stability of the control loop. However, using a PT1 filter can result in dead times in the control loop that must be avoided if high dynamic performance is required. The filter time can be optimised via the scPar.rFiltTimeActTensIn parameter.

The correcting variable of the PI controller is also guided via a limiter before multiplying the influencing factor. This allows the scPar.lrTensCtrlLimitPos and scPar.lrTensCtrlLimitNeg parameters to be used for limitation.

The I-component of the PI controller is switched off with the input xResetICtrl = TRUE. The control value (controller output) from the I-component is set to '0' via the ramp function. The control value from the P-component is not affected.

Note: The I-component of the PI controller is automatically switched off when the control value is at a standstill.

Torque based mode

Settings for the implementation of this control procedure:

  • Parameter eTensCtrlMode = 0: "TorqueBased"

  • Parameter lrTensCtrlGain > 0

Signal flow for tension control in torque based mode

Speed based mode

Settings for the implementation of this control procedure:

  • Parameter eTensCtrlMode = 1: "SpeedBased"

  • Parameter lrTensCtrlGain > 0

Signal flow for tension control in speed based mode

Parameters to be set

Identifier

Data type

Description

 

 

eTensCtrlMode

L_TW2P_WinderTensionControlMode

Selection of the axis control mode for the reel

The mode is effective in winding mode when the tension control/regulation is activated.

  • Initial value: 0

0

"TorqueBased"

The torque control is activated in the drive when the technology module changes to the "TENSIONCTRL" state.

1

"SpeedBased"

Speed control is activated in the drive when the technology module changes to the "TENSIONCTRL" state.

lrTensCtrlGain

LREAL

Controller gain

  • Initial value: 0

lrTensCtrlResetTime

LREAL

Controller reset time

  • Unit: s

  • Initial value: 0 (reset time deactivated)

lrTensCtrlLimitPos

LREAL

Limitation of the tensile force controller correcting variable (output of the controller) in positive direction

  • Unit: [N]

  • Initial value: 2147483648 (0.5 x 232)

lrTensCtrlLimitNeg

LREAL

Limitation of the tensile force controller correcting variable (output of the controller) in negative direction

  • Unit: [N]

  • Initial value: -2147483648 (-0.5 x 232)