Open-loop tension control based on torque controller

Parameters to be set

Setting the scPar.lrTensCtrlGain parameter determines which of the two basic methods is to be used.

See also: L_TW2P_scPar_WinderTensionCtrlState basic functions

Control mode

 

Parameter- settings

eTensCtrlMode

lrTensCtrlGain

Torque-based open-loop

0: "TorqueBased"

= 0

Torque-based closed-loop

0: "TorqueBased"

³ 0

Speed-based closed loop

1: "SpeedBased"

³ 0

If no actual tensile force value is available for a closed tension control loop, simple open-loop tension control is used. The parameter settings are:

  • eTensCtrlMode = 0: "TorqueBased"

  • lrTensCtrlGain = 0 (torque-based open loop)

In open-loop tension control, motor torque is controlled directly depending on the tensile force setpoint and the current diameter. The motor speed is not regulated, it is merely limited via speed limitation in the event of a web break.

Enabling of open-loop/closed-loop tension control

The input xTensCtrl = TRUE activates open-loop/closed-loop tension control. The technology module switches to the TENSIONCTRL state and the status output xWindingBusy = TRUE is set.

Ramp generator for the tensile force setpoint

The tensile force setpoint is initially guided by a ramp generator to prevent setpoint jumps. The ramp function must be adapted to the required time response in the application via the scPar.lrTensRamp parameter. For instance, if the default value of 50 N/s is used, it takes 2 s to generate 100 N of tension on the material. The ramp function is initialised with a starting value of zero as long as open-loop/closed-loop tension control is not active.

The current tensile force setpoint after the ramp function can be diagnosed in the signal flow via the MP_lrSetTensPoint measuring point [N].

The tensile force [N] is evaluated using the current diameter and converted into torque [Nm].

If unwinding mode is active, the resulting torque is inverted. The resulting torque setpoint from open-loop tension control is displayed in the signal flow via the MP_lrSetTensTrq measuring point [Nm].

Parameters to be set

Identifier

Data type

Description

 

eTensCtrlMode

L_TW2P_WinderTensionControlMode

Selection of the axis control mode for the reel

The mode is effective in winding mode when the tension control/regulation is activated.

  • Initial value: 0

0

"TorqueBased"

The torque control is activated in the drive when the technology module changes to the "TENSIONCTRL" state.

1

"SpeedBased"

Speed control is activated in the drive when the technology module changes to the "TENSIONCTRL" state.

lrTensCtrlGain

LREAL

Controller gain

  • Initial value: 0

lrTensRef

LREAL

Maximum permissible tensile force

  • Unit: N

  • Initial value: 50

lrTensRamp

LREAL

Acceleration ramp for the tensile force setpoint

  • Unit: N/s

  • Initial value: 50