Replace Certificate for HA Proxy

To replace the automatically generated certificate, open the Security Screen in the »PLC Designer« and select the "Device" tab.

A screenshot of a computer

Description automatically generated with low confidence

Replace Certificate

Details of this automatic generated certificate can be found in this documentation, (refer to chapter Controller.CertificateStore.HAProxy:Certificate

At this point, the certificate for the "Lenze HA Proxy" can be recreated or deleted. Details on this can also be called up.

  • A certificate is mandatory for a secure https connection. Existing connections are also terminated if the HA Proxy certificate has been deleted and a new one has not yet been generated.

    Example:

    A web browser is connected via https to the diagnosis visualization of the controller and the user has passed the authentication successfully. With an existing https connection, the certificate is deleted with the »PLC Designer«. As a reaction, the connection is immediately interrupted and an error message appears in the browser "…Client cannot communicate. Socket is not available…". If now a new HA Proxy certificate is generated with the »PLC Designer« and the user pushes the reload button on the browser page, the https connection will be established and the user has to authenticate again.

Behavior when HA Proxy certificate is deleted after different reset levels:

Reset Level

Behavior

Manually stop and start the application

The HA Proxy Certificate is still deleted.

Reset Warm

The HA Proxy Certificate is still deleted.

Reset Cold

The HA Proxy Certificate is still deleted.

Reset Origin and create the application again

The HA Proxy Certificate is still deleted.

Boot the Controller

The HA Proxy Certificate is automatically generated new.