Scenarios for the restart
|
Start position 1
Start position 2
Start position 3
Position limits
IrWindowsPos
+
IrWindowsNeg
Position limits subindex 136 + 137 (tolerance window
SetPos
=
ActPos
)
|
-
xStayInLastState
= TRUE
-
STO is activated
-
The setpoint position of the axis corresponds to the switch-off position
-
STO is canceled
-
When the STO is canceled, the actual position of the inverter is at start position 1
-
xMoveLastSetPos
= FALSE
-
The setpoint position remains at the value of the switch-off position. A compensation movement takes place due to the following error by the position controller.
-
xReadyToContinue
= TRUE
-
xMoveLastSetPos
= TRUE
-
It is positioned to the switch-off position with the values specified at the
lrSetVel
,
lrSetAcc
and
lrSetJerk
inputs.
-
After the positioning is completed, the output is
xReadyToContinue
= TRUE.
-
When STO is canceled, the actual position of the inverter is at start position 2
-
xMoveLastSetPos
= FALSE
-
xMoveLastSetPos
= TRUE
-
It is positioned to the switch-off position with the values specified at the
lrSetVel
,
lrSetAcc
and
lrSetJerk
inputs.
-
After the positioning is completed, the output is
xReadyToContinue
= TRUE.
-
When STO is canceled, the actual position of the inverter is at the start position 3
-
xMoveLastSetPos
= FALSE
-
xMoveLastSetPos
= TRUE