Scenarios for the restart

Start position 1

Start position 2

Start position 3

Position limits IrWindowsPos + IrWindowsNeg

Position limits subindex 136 + 137 (tolerance window SetPos = ActPos )

Initial situation for the scenarios 1 - 3
  1. xStayInLastState = TRUE
  2. STO is activated
  3. The setpoint position of the axis corresponds to the switch-off position
  4. STO is canceled
Scenario 1
  • When the STO is canceled, the actual position of the inverter is at start position 1
  • xMoveLastSetPos = FALSE
    • The setpoint position remains at the value of the switch-off position. A compensation movement takes place due to the following error by the position controller.
    • xReadyToContinue = TRUE
  • xMoveLastSetPos = TRUE
    • It is positioned to the switch-off position with the values specified at the lrSetVel , lrSetAcc and lrSetJerk inputs.
    • After the positioning is completed, the output is xReadyToContinue = TRUE.
Scenario 2
  • When STO is canceled, the actual position of the inverter is at start position 2
  • xMoveLastSetPos = FALSE
    • The target position is set to the actual position.
    • The reaction set in subindex 107 (response - inverter disabled in operation) takes place.
  • xMoveLastSetPos = TRUE
    • It is positioned to the switch-off position with the values specified at the lrSetVel , lrSetAcc and lrSetJerk inputs.
    • After the positioning is completed, the output is xReadyToContinue = TRUE.
Scenario 3
  • When STO is canceled, the actual position of the inverter is at the start position 3
  • xMoveLastSetPos = FALSE
    • The target position is set to the actual position.
    • The reaction set in subindex 107 (response - inverter disabled in operation) takes place.
  • xMoveLastSetPos = TRUE
    • The target position is set to the actual position.
    • The reaction set in subindex 107 (response - inverter disabled in operation) takes place.