Speed limitation by master
Reducing the line speed is used to:
–
Reduce the drive power of the winding drive.
–
The permissible input speed of the motor.
Here, below a diameter dVmax, the line velocity setpoint is throttled in such a way that the motor speed to be limited is not exceeded. To throttle the motor speed, a limiter is required in the master drive of the system with variable vref- to vmax limitation. The values for calculating the limitation are stored in the winder drive.
The necessity of limiting the line velocity between vref and vmax is made clear by the following graph. The graph refers to a rewinder that starts at dmin and does not exceed nmax.
Fig. 1: Dialog overview "Monitoring setting - Limitation master speed".
In the case of an unwinder, a limitation may also be required.
Parameter
Example application of the limitation value:
When an unwinder and a rewinder specify different limitation values, the overall limitation can be implemented via a series connection of 2 limiters in the master.
Fig. 2: Example of speed limitation in the master
The required limitation value is permanently provided at the fieldbus interface. The master is not limited, the provided signal becomes smaller than the Line velocity reference.
0x5051:012
0x5051:012For a diameter that does not require a limitation, the limit value of the master corresponds to the reference line speed.
|
Parameter index
|
Parameter name
|
|
|
|
|
Winder reference speed at dmin
|
|
|
Actual diameter
|
|
|
Master speed limit
|
|
The limitation is implemented in the line speed master. The limit value is provided by the winder.
Preconditions:
–
The diameter is known.
–
The maximum winder speed in the parameter Max. permissible winding velocity is configured to match the limit value.
0x5051:097
0x5051:097