Event ID overview
The following table contains the most important event IDs of the device in ascending order.
–
Clicking the event ID shows you a detailed description of the event.
–
If the device displays an "internal event" that is not listed here, restart the device. If the event persists, make a note of the event ID and contact the manufacturer.
|
Event ID
|
Event
|
Severity
|
Configurable in
|
|
|
No error
|
Information
|
-
|
||
|
Short circuit or earth leakage at the motor end
|
Fault
|
-
|
||
|
Short circuit at the motor end
|
Fault
|
-
|
||
|
Motor utilization too high (i²xt)
|
Fehler > CiA402
|
|||
|
Trouble - utilization of the power section (ixt) too high
|
Fault
|
-
|
||
|
Warning - Utilization of the power section (ixt) too high
|
Warning
|
-
|
||
|
Fault - Device utilization (ixt) too high
|
Fault
|
-
|
||
|
Warning - Device utilization (ixt) too high
|
Warning
|
-
|
||
|
Ultimate motor current reached
|
Fault > CiA402
|
|||
|
Parameterized max. motor current > max. device current
|
Warning
|
-
|
||
|
Clamp is active
|
Warning
|
-
|
||
|
Clamp responded too often
|
Fault
|
-
|
||
|
Warning - device utilization (ixt) too high
|
Warning
|
-
|
||
|
Trouble - Device utilization (ixt) too high
|
Fault
|
-
|
||
|
Mains failure
|
Fault
|
-
|
||
|
Fault - DC bus overvoltage
|
Fault
|
-
|
||
|
Fault - DC bus undervoltage
|
Trouble
|
-
|
||
|
Fault - Power unit overtemperature
|
Fault
|
-
|
||
|
Fault - Heat sink temperature sensor
|
Fault
|
-
|
||
|
Heat sink fan warning
|
Warning
|
-
|
||
|
Thermal overload of control unit
|
Information
|
-
|
||
|
Motor overtemperature
|
Warning
|
|||
|
Fault - Motor temperature sensor
|
Warning
|
|||
|
Error - Motor temperature monitoring (PTC)
|
Fault > CiA402
|
|||
|
Motor overtemperature (load encoder/master encoder)
|
Warning
|
|||
|
Motor temperature sensor error (load encoder/master encoder)
|
Warning
|
|||
|
External supply voltage critical
|
Warning
|
-
|
||
|
Internal error
|
Warning
|
-
|
||
|
Warning - Internal fan
|
Warning
|
-
|
||
|
Incorrect parameter set download
|
Warning
|
-
|
||
|
Parameter error in object
|
Warning
|
-
|
||
|
Fault - Analog input 1
|
No response
|
|||
|
Analog input 2 fault
|
No response
|
|||
|
Connected network option is not supported
|
Fault
|
-
|
||
|
Fault - Pole position identification
|
Fault
|
-
|
||
|
Fault - Motor feedback
|
Fault > CiA402
|
|||
|
Error - Load encoder/master encoder
|
Fault > CiA402
|
|||
|
Motor encoder - Communication error
|
Fault > CiA402
|
|||
|
Motor encoder - wrong absolute value because motor speed is too high
|
Fault > CiA402
|
|||
|
Load encoder/master encoder - Communication error
|
Fault > CiA402
|
|||
|
Load encoder/master encoder - wrong absolute value because motor speed is too high
|
Fault > CiA402
|
|||
|
Motor encoder (EnDat) - Communication error
|
Fault
|
-
|
||
|
Load encoder (EnDat) - Communication error
|
Fault
|
-
|
||
|
Fatal internal error
|
Fault
|
-
|
||
|
Fatal internal communication error
|
Fault
|
-
|
||
|
Fault - Motor holding brake
|
|
-
|
||
|
Fatal internal error - task overflow
|
Fault
|
-
|
||
|
PPI - Motor movement too large
|
Fault > CiA402
|
|||
|
Safe torque off (STO) activated
|
Warning
|
-
|
||
|
Motor overspeed
|
Fault > CiA402
|
|||
|
Not permitted during identification or in test mode
|
Warning
|
-
|
||
|
Not permitted during identification
|
Warning
|
-
|
||
|
Motor phase missing
|
No response
|
|||
|
Motor phase failure phase U
|
No response
|
|||
|
Motor phase failure phase V
|
No response
|
|||
|
Motor phase failure phase W
|
No response
|
|||
|
No resolver connected - command cannot be executed
|
Warning
|
-
|
||
|
Speed too low - command cannot be executed
|
Warning
|
-
|
||
|
No resolver as motor encoder connected - command cannot be executed
|
Warning
|
-
|
||
|
Time-out during resolver identification
|
Warning
|
-
|
||
|
Numeric problem during resolver identification
|
Warning
|
-
|
||
|
Inverter error too large
|
Warning
|
-
|
||
|
Identification aborted
|
Fault > CiA402
|
|||
|
Not permitted in state 'operation enabled' or 'quick stop active'
|
Warning
|
-
|
||
|
No HIPERFACE® absolute value encoder as motor encoder connected - command cannot be executed
|
Warning
|
-
|
||
|
Connected HIPERFACE® motor encoder is not supported
|
Fault > CiA402
|
|||
|
Connected HIPERFACE® motor encoder is not supported - command cannot be executed
|
Warning
|
-
|
||
|
Communication time-out in manual control mode
|
Fault
|
-
|
||
|
Motor parameter identification fault
|
Fault
|
-
|
||
|
Connected HIPERFACE® load encoder/master encoder is not supported
|
Fault > CiA402
|
|||
|
Connected HIPERFACE® load encoder/master encoder is not supported - command cannot be executed
|
Warning
|
-
|
||
|
No resolver as load encoder/master encoder connected - command cannot be executed
|
Warning
|
-
|
||
|
No HIPERFACE® absolute value encoder as load encoder/master encoder connected - command cannot be executed
|
Warning
|
-
|
||
|
FIQ runtime error
|
Fault
|
-
|
||
|
Brand protection - check failed
|
Warning
|
-
|
||
|
Time-out holding brake feedforward control
|
Fault
|
-
|
||
|
Velocity error
|
Fault
|
-
|
||
|
Position error
|
Fault
|
-
|
||
|
Cable check - Motor movement too large
|
Fault
|
-
|
||
|
Cable check - Wrong motor angle detected
|
Fault
|
-
|
||
|
Connected motor encoder is not supported
|
Fault
|
-
|
||
|
Connected load encoder/master encoder is not supported
|
Fault
|
-
|
||
|
Warning - Brake resistor overload
|
Warning
|
-
|
||
|
Backup created via device command
|
Information
|
-
|
||
|
Backup restored via device command
|
Information
|
-
|
||
|
Error - Brake transistor
|
Fault
|
-
|
||
|
Error - Charging circuit
|
Fault
|
-
|
||
|
Mains phase failure
|
Fault
|
-
|
||
|
Motor encoder requires restart of the device
|
Fault
|
-
|
||
|
Load encoder requires restart of the device
|
Fault
|
-
|
||
|
General error (see manual)
|
Fault
|
-
|
||
|
Internal communication to PLC failed
|
Fault
|
-
|
||
|
Invalid module combination in slot A and slot B
|
Fault
|
-
|
||
|
Initialization - Parameter value could not be written
|
Information
|
-
|
||
|
Load default setting - Parameter value could not be written
|
Warning
|
-
|
||
|
Parameters - Initialization failed
|
Warning
|
-
|
||
|
Parameters - Loading default values failed
|
Warning
|
-
|
||
|
Parameters - Loading TA default values failed
|
Warning
|
-
|
||
|
Opening the parameter description failed
|
Fault
|
-
|
||
|
Opening the parameter set failed
|
Fault
|
-
|
||
|
Logbook: Corrupt restore data
|
Information
|
-
|
||
|
Logbook cleared
|
Information
|
-
|
||
|
Logbook: Timeout restoring data
|
Information
|
-
|
||
|
Logbook: Error restoring data
|
Information
|
-
|
||
|
First boot with this firmware version
|
Information
|
-
|
||
|
Logbook was restored.
|
Information
|
-
|
||
|
Logbook: Error reading persistent data.
|
Information
|
-
|
||
|
The chronology of the logbook is not consistent
|
Information
|
-
|
||
|
CmpLenzeErrorManagementAccess loaded without errors
|
Information
|
-
|
||
|
Test-Mode - More Application Credit required, application is starting delayed
|
Warning
|
-
|
||
|
Application-Credit - Invalid license data
|
Warning
|
-
|
||
|
Application-Credit - License data missing
|
Warning
|
-
|
||
|
Boot application - More Application Credit required
|
Warning
|
-
|
||
|
Application was downloaded.
|
Information
|
-
|
||
|
Internal error - AIS
|
Warning
|
-
|
||
|
Internal error - AIE
|
Warning
|
-
|
||
|
Internal error - Button S82
|
Warning
|
-
|
||
|
IRS - Internal error
|
Warning
|
-
|
||
|
IRL - Internal error
|
Warning
|
-
|
||
|
SD-Inx/CLx - Error
|
Warning
|
-
|
||
|
Internal switch-off path - Error
|
Warning
|
-
|
||
|
Internal switch-off path - Test pulse error
|
Warning
|
-
|
||
|
SBC - Test pulse error
|
Warning
|
-
|
||
|
SBC - Remains stuck at LOW
|
Warning
|
-
|
||
|
Faulty internal adjustment data
|
Warning
|
-
|
||
|
Reference voltage error
|
Warning
|
-
|
||
|
6 V voltage error
|
Warning
|
-
|
||
|
5 V voltage error
|
Warning
|
-
|
||
|
3.3 V voltage error
|
Warning
|
-
|
||
|
Internal error - STO activated
|
Warning
|
-
|
||
|
Communication error - Basic device
|
Warning
|
-
|
||
|
Synchronization error - Basic device
|
Information
|
-
|
||
|
SBC - Device configuration incompatible
|
Warning
|
-
|
||
|
F-parameter error
|
Information
|
-
|
||
|
F_Dest_Add unequal F-address
|
Information
|
-
|
||
|
F_Dest_Add = 0 or FFFFhex
|
Information
|
-
|
||
|
F_Source_Add = 0 or FFFFhex
|
Information
|
-
|
||
|
F_WD_Time = 0 ms
|
Information
|
-
|
||
|
F_SIL exceeds technical SIL
|
Information
|
-
|
||
|
F_CRC_Length error
|
Information
|
-
|
||
|
Wrong F-parameter version
|
Information
|
-
|
||
|
F_Block_ID not supported
|
Information
|
-
|
||
|
Safety parameter set deleted
|
Information
|
-
|
||
|
New safety parameter set loaded
|
Information
|
-
|
||
|
Memory module - Access error
|
Warning
|
-
|
||
|
Different safety parameter sets
|
Warning
|
-
|
||
|
Extended Safety - No safety parameter set
|
Warning
|
-
|
||
|
Extended Safety - Safety parameter set defect
|
Warning
|
-
|
||
|
Safety parameter set - Format error
|
Warning
|
-
|
||
|
Safety parameter set - Plausibility error
|
Warning
|
-
|
||
|
Safety parameter set - Communication error
|
Warning
|
-
|
||
|
Different safety addresses detected
|
Warning
|
-
|
||
|
SSM - Wrong PDO version
|
Warning
|
-
|
||
|
Memory module release information - access error
|
Information
|
-
|
||
|
PROFIsafe passivated
|
Information
|
-
|
||
|
PROFIsafe has left data exchange
|
Information
|
-
|
||
|
PROFIsafe - CRC1 error
|
Information
|
-
|
||
|
PROFIsafe - Device specific error
|
Information
|
-
|
||
|
iParameters - Saving, watchdog expired
|
Information
|
-
|
||
|
FSoE - Unexpected command
|
Information
|
-
|
||
|
FSoE - Unknown command
|
Information
|
-
|
||
|
FSoE - Invalid connection ID
|
Information
|
-
|
||
|
FSoE - CRC error
|
Information
|
-
|
||
|
FSoE - Watchdog expired
|
Information
|
-
|
||
|
FSoE - Invalid communication parameter data
|
Information
|
-
|
||
|
FSoE - Invalid application parameter length
|
Information
|
-
|
||
|
FSoE - Invalid application parameter data
|
Information
|
-
|
||
|
FSoE - Passivated
|
Information
|
-
|
||
|
iParameters - Restore, watchdog expired
|
Information
|
-
|
||
|
PROFIsafe - iParCRC error
|
Information
|
-
|
||
|
PROFIsafe - CRC2 error
|
Information
|
-
|
||
|
F_WD_Time or F_WD_Time_2 expired
|
Information
|
-
|
||
|
Reserved (PROFIsafe standard)
|
Information
|
-
|
||
|
FSoE - Invalid slave address
|
Information
|
-
|
||
|
FSoE - Invalid communication parameter length
|
Information
|
-
|
||
|
FSoE - Data exchange left
|
Information
|
-
|
||
|
Discrepancy check or function check error - SD-In1
|
Warning
|
-
|
||
|
Discrepancy check or function check error - SD-In2
|
Warning
|
-
|
||
|
Discrepancy check or function check error - SD-In3
|
Warning
|
-
|
||
|
Discrepancy check or function check error - SD-In4
|
Warning
|
-
|
||
|
Disabled SD-In1 = HIGH
|
Warning
|
-
|
||
|
Disabled SD-In2 = HIGH
|
Warning
|
-
|
||
|
Disabled SD-In3 = HIGH
|
Warning
|
-
|
||
|
Disabled SD-In4 = HIGH
|
Warning
|
-
|
||
|
SD-Out1 - Channel A remains stuck at HIGH
|
Warning
|
-
|
||
|
SD-Out1 - Channel A remains stuck at LOW
|
Warning
|
-
|
||
|
SD-Out1 - Channel B remains stuck at HIGH
|
Warning
|
-
|
||
|
SD-Out1 - Channel B remains stuck at LOW
|
Warning
|
-
|
||
|
SD-In1 - Channel A remains stuck at HIGH
|
Warning
|
-
|
||
|
SD-In1 - Channel B remains stuck at HIGH
|
Warning
|
-
|
||
|
SD-In2 - Channel A remains stuck at HIGH
|
Warning
|
-
|
||
|
SD-In2 - Channel B remains stuck at HIGH
|
Warning
|
-
|
||
|
SD-In3 - Channel A remains stuck at HIGH
|
Warning
|
-
|
||
|
SD-In3 - Channel B remains stuck at HIGH
|
Warning
|
-
|
||
|
SD-In4 - Channel A remains stuck at HIGH
|
Warning
|
-
|
||
|
SD-In4 - Channel B remains stuck at HIGH
|
Warning
|
-
|
||
|
CLA/CLB - Short circuit
|
Warning
|
-
|
||
|
SS1/SS2 - Stop time exceeded
|
Warning
|
-
|
||
|
SLS1 - Nlim1 exceeded
|
Warning
|
-
|
||
|
SLS2 - Nlim2 exceeded
|
Warning
|
-
|
||
|
SLS3 - Nlim3 exceeded
|
Warning
|
-
|
||
|
SLS4 - Nlim4 exceeded
|
Warning
|
-
|
||
|
SLS/SMS - Error stop not executed
|
Warning
|
-
|
||
|
SDIpos - Wrong direction
|
Warning
|
-
|
||
|
SDIneg - Wrong direction
|
Warning
|
-
|
||
|
SMS - Nmax exceeded
|
Warning
|
-
|
||
|
SOS - Tolerance limit exceeded
|
Warning
|
-
|
||
|
No feedback system configured
|
Warning
|
-
|
||
|
CAS - Round trip time exceeded
|
Warning
|
-
|
||
|
CAS - Hardware or discrepancy error
|
Warning
|
-
|
||
|
SS1/SS2 - Speed ramp exceeded
|
Warning
|
-
|
||
|
SLI - Safely limited increment exceeded
|
Warning
|
-
|
||
|
SLP1 - Position limits exceeded
|
Warning
|
-
|
||
|
SLP2 - Position limits exceeded
|
Warning
|
-
|
||
|
SLP3 - Position limits exceeded
|
Warning
|
-
|
||
|
SLP4 - Position limits exceeded
|
Warning
|
-
|
||
|
SLP - No home position
|
Warning
|
-
|
||
|
PDSS - Velocity exceeded
|
Warning
|
-
|
||
|
PDSS - Creep velocity SCS exceeded
|
Warning
|
-
|
||
|
PDSS - No diagnostic mark detected
|
Warning
|
-
|
||
|
PDSS - Diagnostic mark detected at invalid position
|
Warning
|
-
|
||
|
SHom - Time-out
|
Warning
|
-
|
||
|
SHom - Home position deleted
|
Information
|
-
|
||
|
SHom - Maximum slip value exceeded
|
Warning
|
-
|
||
|
SHom - Tolerance of start position exceeded
|
Warning
|
-
|
||
|
SHom - Tolerance of position comparison exceeded
|
Warning
|
-
|
||
|
SSM - Invalid safe velocity
|
Warning
|
-
|
||
|
SSM - Encoder error
|
Warning
|
-
|
||
|
SSM - Resolver error
|
Warning
|
-
|
||
|
SSM - Error in standard device data
|
Warning
|
-
|
||
|
SSM - Speed deviation too high
|
Warning
|
-
|
||
|
SSM - Synchronization error
|
Warning
|
-
|
||
|
MUT - Muting function active
|
Information
|
-
|
||
|
MUT - Muting function completed
|
Information
|
-
|
||
|
MUT - Muting function aborted
|
Information
|
-
|
||
|
HDSL encoder - ID was set
|
Information
|
-
|
||
|
Internal error
|
Warning
|
-
|
||
|
Internal error
|
Warning
|
-
|
||
|
Internal error
|
Warning
|
-
|
||
|
Internal error
|
Warning
|
-
|
||
|
Internal error
|
Warning
|
-
|
||
|
Internal error
|
Warning
|
-
|
||
|
Internal error
|
Warning
|
-
|
||
|
CTRL - Feature not supported
|
Warning
|
-
|
||
|
CTRL - Invalid index
|
Warning
|
-
|
||
|
ISW - Invalid offset
|
Warning
|
-
|
||
|
CTRL - Invalid size
|
Warning
|
-
|
||
|
ISW - Invalid data
|
Warning
|
-
|
||
|
ISW - Not ready
|
Warning
|
-
|
||
|
CTRL - Busy
|
Warning
|
-
|
||
|
ISW - Cannot queue acyclic EtherCAT command
|
Warning
|
-
|
||
|
CFG - No memory left
|
Warning
|
-
|
||
|
CTRL - Invalid parameter
|
Warning
|
-
|
||
|
CTRL - Not found
|
Warning
|
-
|
||
|
ISW - Invalid state
|
Warning
|
-
|
||
|
ISW - Cannot add slave to timer list
|
Warning
|
-
|
||
|
SLV - Time-out
|
Warning
|
-
|
||
|
ISW - Open failed
|
Warning
|
-
|
||
|
LLA - Send failed
|
Warning
|
-
|
||
|
CFG - Error when queuing a mailbox command
|
Warning
|
-
|
||
|
ISW - Invalid mailbox command
|
Warning
|
-
|
||
|
ISW - Unknown mailbox protocol command
|
Warning
|
-
|
||
|
ISW - Access denied
|
Warning
|
-
|
||
|
CFG - Invalid product key
|
Warning
|
-
|
||
|
PRJ - Wrong format of master XML file
|
Warning
|
-
|
||
|
CTRL - Function disabled
|
Warning
|
-
|
||
|
PRJ - Mismatch of bus configuration and number of connected slaves
|
Warning
|
-
|
||
|
PRJ - Error reading master XML file
|
Warning
|
-
|
||
|
PRJ - Configurator error - cyclic commands are missing in master XML file
|
Warning
|
-
|
||
|
PRJ - AL_STATUS register read command is missing in master XML file
|
Warning
|
-
|
||
|
ISW - Fatal internal McSm error
|
Warning
|
-
|
||
|
SLV - Slave error
|
Warning
|
-
|
||
|
SLV - Frame lost, IDX mismatch
|
Warning
|
-
|
||
|
SLV - At least one EtherCAT command is missing in the received frame
|
Warning
|
-
|
||
|
CTRL - IOCTL EC_IOCTL_DC_LATCH_REQ_LTIMVALS not possible in DC Latching auto read mode
|
Warning
|
-
|
||
|
SLV - Auto increment address - increment mismatch (slave missing)
|
Warning
|
-
|
||
|
CTRL - Slave in invalid state, e.g. not in OP (API not callable in this state)
|
Warning
|
-
|
||
|
SLV - Fixed station address lost or slave missing - FPRD to AL_STATUS failed
|
Warning
|
-
|
||
|
PRJ - Too many cyclic commands in XML configuration file
|
Warning
|
-
|
||
|
RAP - Master core not accessible
|
Warning
|
-
|
||
|
SLV - COE mailbox send - WKC error
|
Warning
|
-
|
||
|
SLV - COE mailbox receive - WKC error
|
Warning
|
-
|
||
|
CTRL - No mailbox support
|
Warning
|
-
|
||
|
CoE - Protocol not supported
|
Warning
|
-
|
||
|
PRJ - EoE protocol not supported
|
Warning
|
-
|
||
|
FoE . Protocol not supported
|
Warning
|
-
|
||
|
PRJ - SoE protocol not supported
|
Warning
|
-
|
||
|
PRJ - VoE protocol not supported
|
Warning
|
-
|
||
|
PRJ - Configuration violates evaluation limits
|
Warning
|
-
|
||
|
CFG - Evaluation time expired
|
Warning
|
-
|
||
|
COE - invalid slave state
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Toggle bit not alternated (0x05030000)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'SDO protocol time-out (0x05040000)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Client/server command specifier not valid or unknown (0x05040001)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Invalid block size (block mode only) (0x05040002)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Invalid sequence number (block mode only) (0x05040003)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'CRC error (block mode only) (0x05040004)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Out of memory (0x05040005)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Unsupported access to an object (0x06010000)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Attempt to read a write only object (0x06010001)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Attempt to write a read only object (0x06010002)'
|
Warning
|
-
|
||
|
CoE - SDO-Abort 'Object does not exist in the object dictionary (0x06020000)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Object cannot be mapped to the PDO (0x06040041)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Number and length of objects to be mapped exceed PDO length (0x06040042)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'General parameter incompatibility (0x06040043)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'General internal incompatibility in the device (0x06040047)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Access failed due to an hardware error (0x06060000)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Data type or length of service parameters do not match (0x06070010)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Data type does not match, service parameter too high (0x06070012)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Data type does not match, service parameter too low (0x06070013)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Subindex does not exist (0x06090011)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Write access - Parameter value exceeds limits (0x06090030)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Write access - Parameter value too high (0x06090031)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Write access - Parameter value too low (0x06090032)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Maximum value less than minimum value (0x06090036)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'General error (0x08000000)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Data cannot be transferred/stored in application (0x08000020)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Local control - Data cannot be transferred/stored in application (0x08000021)'
|
Warning
|
-
|
||
|
CoE- SDO Abort 'Actual device state - Data cannot be transferred/stored in application (0x08000022)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Object dictionary - Dynamic generation fails or object dictionary is missing (0x08000023)'
|
Warning
|
-
|
||
|
CoE - SDO Abort 'Unknown abort code'
|
Warning
|
-
|
||
|
CoE - Invalid parameter
|
Warning
|
-
|
||
|
CoE - CoE protocol not supported
|
Warning
|
-
|
||
|
CoE - Unknown FoE error
|
Warning
|
-
|
||
|
CoE - FoE error 'Not found'
|
Warning
|
-
|
||
|
CoE - FoE error 'Access denied'
|
Warning
|
-
|
||
|
CoE - FoE error 'Disk full'
|
Warning
|
-
|
||
|
CoE - FoE error 'Illegal'
|
Warning
|
-
|
||
|
CoE - FoE error 'Wrong packet number'
|
Warning
|
-
|
||
|
CoE - FoE error 'Already existing'
|
Warning
|
-
|
||
|
CoE - FoE error 'User missing'
|
Warning
|
-
|
||
|
CoE - FoE error 'Only possible in bootstrap'
|
Warning
|
-
|
||
|
CoE - FoE error 'No bootstrap'
|
Warning
|
-
|
||
|
CoE - FoE error 'No access rights'
|
Warning
|
-
|
||
|
CoE - FoE error 'Program error'
|
Warning
|
-
|
||
|
CoE - FoE error 'Invalid parameter'
|
Warning
|
-
|
||
|
CTRL - Master configuration not found
|
Warning
|
-
|
||
|
SLV - Command error while EEPROM upload
|
Warning
|
-
|
||
|
SLV - Command error while EEPROM download
|
Warning
|
-
|
||
|
PRJ - Cyclic command too long
|
Warning
|
-
|
||
|
PRJ - Invalid input offset in cyc cmd, please check InputOffs
|
Warning
|
-
|
||
|
PRJ - Invalid output offset in cyc cmd, please check OutputOffs
|
Warning
|
-
|
||
|
RAP - Invalid cookie
|
Warning
|
-
|
||
|
RAP - Watchdog expired
|
Warning
|
-
|
||
|
RAP - Connecting 2nd server denied, multi server support is disabled
|
Warning
|
-
|
||
|
RAP - Logon aborted
|
Warning
|
-
|
||
|
RAP - Invalid version
|
Warning
|
-
|
||
|
RAP - Server stopped
|
Warning
|
-
|
||
|
RAP - Watchdog expired
|
Warning
|
-
|
||
|
RAP - Reconnect time expired
|
Warning
|
-
|
||
|
RAP - Client logged on
|
Warning
|
-
|
||
|
RAP - Client reconnected
|
Warning
|
-
|
||
|
RAP - Socket changed after reconnect
|
Warning
|
-
|
||
|
DCM - Init function not called or call not successful
|
Warning
|
-
|
||
|
DCM - Controller error - synchronization out of limit
|
Warning
|
-
|
||
|
DCM - Not enough memory
|
Warning
|
-
|
||
|
DCM - Hardware layer - (BSP) invalid
|
Warning
|
-
|
||
|
DCM - Hardware layer - Error while modifying the timer
|
Warning
|
-
|
||
|
DCM - Hardware layer - Timer is not running
|
Warning
|
-
|
||
|
DCM - Hardware layer - Function is called on wrong CPU
|
Warning
|
-
|
||
|
EtherCAT - State change of master successful
|
Warning
|
-
|
||
|
EtherCAT - Bus scan successful
|
Warning
|
-
|
||
|
EtherCAT - Bus scan error
|
Warning
|
-
|
||
|
EtherCAT - Distributed clocks state
|
Warning
|
-
|
||
|
EtherCAT - Distributed clocks - Latching state
|
Warning
|
-
|
||
|
CoE - SDO download failure
|
Warning
|
-
|
||
|
CoE - SDO upload failure
|
Warning
|
-
|
||
|
CoE - OD-list upload failure
|
Warning
|
-
|
||
|
CoE - Object description upload failure
|
Warning
|
-
|
||
|
CoE - Object entry description upload failure
|
Warning
|
-
|
||
|
CoE - Emergency transfer failure
|
Warning
|
-
|
||
|
CoE - Emergency request
|
Warning
|
-
|
||
|
Cyclic command WKC error
|
Warning
|
-
|
||
|
Master init command WKC error
|
Warning
|
-
|
||
|
Slave init command WKC error
|
Warning
|
-
|
||
|
EoE receive WKC error
|
Warning
|
-
|
||
|
CoE receive WKC error
|
Warning
|
-
|
||
|
FoE receive WKC error
|
Warning
|
-
|
||
|
SoE receive - WKC error
|
Warning
|
-
|
||
|
EoE send WKC error
|
Warning
|
-
|
||
|
CoE send WKC error
|
Warning
|
-
|
||
|
FoE send WKC error
|
Warning
|
-
|
||
|
SoE send - WKC error
|
Warning
|
-
|
||
|
Retry sending a frame
|
Warning
|
-
|
||
|
Response on Ethernet frame
|
Warning
|
-
|
||
|
Additional error information
|
Warning
|
-
|
||
|
EtherCAT command - IDX actual value
|
Warning
|
-
|
||
|
EtherCAT command - IDX set value
|
Warning
|
-
|
||
|
Init command response error - No response
|
Warning
|
-
|
||
|
Init command response error - Validation error
|
Warning
|
-
|
||
|
Init command response error - Failed
|
Warning
|
-
|
||
|
Master init command response error - No response
|
Warning
|
-
|
||
|
Master init command response error - Validation error
|
Warning
|
-
|
||
|
Missing EtherCAT command in Ethernet frame
|
Warning
|
-
|
||
|
Mailbox init command timeout
|
Warning
|
-
|
||
|
At least one EtherCAT slave not in 'Operational'
|
Warning
|
-
|
||
|
EtherCAT cable connected
|
Warning
|
-
|
||
|
EtherCAT cable not connected
|
Warning
|
-
|
||
|
Cyclic commands - Time-out
|
Warning
|
-
|
||
|
Redundant operation - Ethernet cable is missing at 2nd EtherCAT interface
|
Warning
|
-
|
||
|
At least one slave is in state 'Error'
|
Warning
|
-
|
||
|
Slave error
|
Warning
|
-
|
||
|
Communication to device interrupted
|
Warning
|
-
|
||
|
SDO abort
|
Warning
|
-
|
||
|
DC slaves are 'in-sync'
|
Warning
|
-
|
||
|
DC slaves are 'out-of-sync'
|
Warning
|
-
|
||
|
DC single latch on slave
|
Warning
|
-
|
||
|
MbxTferRcv - file upload failure
|
Warning
|
-
|
||
|
MbxTferRcv - file download failure
|
Warning
|
-
|
||
|
Client registration lost
|
Warning
|
-
|
||
|
Redundant operation - Ethernet cable connected
|
Warning
|
-
|
||
|
SoE write error init command mbox
|
Warning
|
-
|
||
|
Hot Connect - all groups detected
|
Warning
|
-
|
||
|
Hot Connect - all group errors detected
|
Warning
|
-
|
||
|
Slave removed from bus
|
Warning
|
-
|
||
|
Slave added to bus
|
Warning
|
-
|
||
|
Topology was changed
|
Warning
|
-
|
||
|
Port closed
|
Warning
|
-
|
||
|
MbxTferRcv - Write IDN failure
|
Warning
|
-
|
||
|
MbxTferRcv - Read IDN failure
|
Warning
|
-
|
||
|
SoE - Emergency transfer failure
|
Warning
|
-
|
||
|
SoE - Emergency request
|
Warning
|
-
|
||
|
SoE - Notification transfer failure
|
Warning
|
-
|
||
|
SoE - Notification request
|
Warning
|
-
|
||
|
FoE abort
|
Warning
|
-
|
||
|
Bus scan state
|
Warning
|
-
|
||
|
Latch/Edge - No edge
|
Warning
|
-
|
||
|
Remote API diagnosis port - Connection established
|
Warning
|
-
|
||
|
Remote API diagnosis port - Connection disconnected
|
Warning
|
-
|
||
|
Client registered from cookie
|
Warning
|
-
|
||
|
Client unregistered from cookie
|
Warning
|
-
|
||
|
Unknown notification
|
Warning
|
-
|
||
|
Slave latched
|
Warning
|
-
|
||
|
Bus scan - Error
|
Warning
|
-
|
||
|
Invalid number of slaves
|
Warning
|
-
|
||
|
Cannot get SlaveInfo
|
Warning
|
-
|
||
|
Deviation of slave
|
Warning
|
-
|
||
|
Slave is not configured
|
Warning
|
-
|
||
|
SlaveInfo
|
Warning
|
-
|
||
|
SLV - Error retrieving configuration data
|
Warning
|
-
|
||
|
Bus scan - Deviation
|
Warning
|
-
|
||
|
Communication to device interrupted
|
Warning
|
-
|
||
|
Slave is not in expected status
|
Warning
|
-
|
||
|
Wrong response on 'configured fix address request' for slave
|
Warning
|
-
|
||
|
Wrong response on 'alias address' request for slave
|
Warning
|
-
|
||
|
Cannot execute EC_IOCTL_DC_SLV_SYNC_DEVLIMIT_GET
|
Warning
|
-
|
||
|
Cannot read latch timer
|
Warning
|
-
|
||
|
Cannot execute EC_IOCTL_DC_SLV_SYNC_RESTART
|
Warning
|
-
|
||
|
RAP - Invalid parameter size
|
Warning
|
-
|
||
|
RAP - Marshaling error
|
Warning
|
-
|
||
|
Unable to enqueue (missing calls to ProcessNotificationJobs)
|
Warning
|
-
|
||
|
No connection to slaves
|
Warning
|
-
|
||
|
ecatSetTargetState cannot set EtherCAT master into target state, master is busy (time-out)
|
Warning
|
-
|
||
|
ecatStop() returns 'Busy', retry...
|
Warning
|
-
|
||
|
Mailbox transfer request - Error
|
Warning
|
-
|
||
|
Mailbox transfer
|
Warning
|
-
|
||
|
Waiting for mailbox transfer from master...
|
Warning
|
-
|
||
|
Mailbox transfer - Fatal time-out error
|
Warning
|
-
|
||
|
Bus cycle and Sync period are different
|
Warning
|
-
|
||
|
Error getting the bus scan state
|
Warning
|
-
|
||
|
Wrong response on DC supported request or slave
|
Warning
|
-
|
||
|
Unable to set 'DC slave sync disable'
|
Warning
|
-
|
||
|
Error when restarting bus scan
|
Warning
|
-
|
||
|
Bus scan timeout
|
Warning
|
-
|
||
|
Configuration error - Check of VendorID failed
|
Warning
|
-
|
||
|
Configuration error - Check of ProductCode failed
|
Warning
|
-
|
||
|
Configuration error - Check of Revision failed
|
Warning
|
-
|
||
|
Configuration error - Check of VendorID failed
|
Warning
|
-
|
||
|
Configuration error - Odd device at bus end
|
Warning
|
-
|
||
|
Internal error counter resetted
|
Warning
|
-
|
||
|
All slaves 'Operational' again
|
Warning
|
-
|
||
|
Cyclic command WKC error
|
Warning
|
-
|
||
|
Frame response error
|
Warning
|
-
|
||
|
Not all slaves are 'Operational'
|
Warning
|
-
|
||
|
Emergency message - Overflow, further messages blocked
|
Warning
|
-
|
||
|
New configuration loaded
|
Warning
|
-
|
||
|
New configuration loaded, no slaves defined
|
Warning
|
-
|
||
|
Master - Start failed, configuration error
|
Warning
|
-
|
||
|
New configuration loaded from slaves EEPROM
|
Warning
|
-
|
||
|
Master - Start failed
|
Warning
|
-
|
||
|
Master - Start failed, bus configuration error
|
Warning
|
-
|
||
|
Master - Start failed, EtherCAT cable disconnected
|
Warning
|
-
|
||
|
Master - Start failed, DC/DCM configuration
|
Warning
|
-
|
||
|
Master - Start failed, cannot set slaves to 'Pre-Operational'
|
Warning
|
-
|
||
|
Master - Set 'Operational' failed
|
Warning
|
-
|
||
|
Master - Set 'Operational' failed, Master not initialized
|
Warning
|
-
|
||
|
Master - Set 'Operational' failed, EtherCAT cable disconnected
|
Warning
|
-
|
||
|
Master - Set 'Operational' failed, DCM not in-sync
|
Warning
|
-
|
||
|
Master - Set 'Operational' failed, bus cycle and DC different
|
Warning
|
-
|
||
|
Master - Set 'Operational' takes some time...
|
Warning
|
-
|
||
|
Master - Set 'Operational' failed, time-out
|
Warning
|
-
|
||
|
Master - Set 'Operational' failed, slave error
|
Warning
|
-
|
||
|
Master - Set 'Operational' aborted by reset command
|
Warning
|
-
|
||
|
Master - Stopping failed
|
Warning
|
-
|
||
|
Master - Stopping failed, cannot set Slaves 'Pre-Operational'
|
Warning
|
-
|
||
|
Master - Shutdown failed
|
Warning
|
-
|
||
|
Remote API Server - Start failed
|
Warning
|
-
|
||
|
Start Download Service
|
Warning
|
-
|
||
|
Download Service done
|
Warning
|
-
|
||
|
MMC - Internal error
|
Warning
|
-
|
||
|
MMC - 'Modular Machine Configuration' is active
|
Warning
|
-
|
||
|
MMC - Service started
|
Warning
|
-
|
||
|
MMC - Service stopped
|
Warning
|
-
|
||
|
MMC - Error in configuration files
|
Warning
|
-
|
||
|
MMC - File does not exist
|
Warning
|
-
|
||
|
MMC - Parsing error
|
Warning
|
-
|
||
|
MMC - parsing of file successful
|
Warning
|
-
|
||
|
MMC - Devices not sorted in ascending order or devices missing
|
Warning
|
-
|
||
|
MMC - Number of devices in device tree differs
|
Warning
|
-
|
||
|
MMC - Device type mismatch for Alias Address
|
Warning
|
-
|
||
|
MMC - Invalid Alias Address
|
Warning
|
-
|
||
|
MMC - Duplicated Alias Address
|
Warning
|
-
|
||
|
MMC - No configuration checks
|
Warning
|
-
|
||
|
MMC - Invalid configuration
|
Warning
|
-
|
||
|
MMC - Mandatory slave missing
|
Warning
|
-
|
||
|
MMC - Optional slave is present, but not allowed
|
Warning
|
-
|
||
|
MMC - No valid service active
|
Warning
|
-
|
||
|
MMC - Address assignment error, less slaves connected than configured
|
Warning
|
-
|
||
|
MMC - Address assignment error, more slaves connected than configured
|
Warning
|
-
|
||
|
MMC - Address assignment error, invalid device
|
Warning
|
-
|
||
|
MMC - Address assignment successful
|
Warning
|
-
|
||
|
MMC - Address assignment failed
|
Warning
|
-
|
||
|
MMC - Address assignment done
|
Warning
|
-
|
||
|
MMC - Address assignment error, writing address by CoE
|
Warning
|
-
|
||
|
MMC - Slave identification error
|
Warning
|
-
|
||
|
MMC - Slave identification error, slave ident data failed
|
Warning
|
-
|
||
|
MMC - Service state cannot be changed, set bus to 'INIT' first
|
Warning
|
-
|
||
|
CoE - Emergency request
|
Information
|
-
|
||
|
Last ETC message
|
Warning
|
-
|
||
|
EtherCAT - DC synchronization required
|
Warning
|
-
|
||
|
EtherCAT - Communication error
|
Fault > CiA402
|
|||
|
EtherCAT - Wrong sync manager address
|
Fault
|
-
|
||
|
EtherCAT - Wrong sync manager size
|
Fault
|
-
|
||
|
EtherCAT - Wrong sync manager settings
|
Fault
|
-
|
||
|
PDO mapping: Unknown object
|
Fault
|
-
|
||
|
No PDO mapping object
|
Fault
|
-
|
||
|
Too many objects mapped
|
Fault
|
-
|
||
|
PDO mapping error
|
Fault
|
-
|
||
|
PDO mapping object is already used by PLC.
|
Fault
|
-
|
||
|
EtherCAT - Sync error
|
Fault
|
-
|
||
|
Sync PLL - Time-out
|
Fault
|
-
|
||
|
Invalid Sync0 cycle time
|
Fault
|
-
|
||
|
Check OUT-port of EtherCAT master
|
|
-
|
||
|
Check IN-port of EtherCAT slave
|
|
-
|
||
|
Network - Time-out explicit message
|
|
-
|
||
|
Network - Overall communication time-out
|
Warning
|
|||
|
CAN: bus off
|
Warning
|
|||
|
CAN: warning
|
Warning
|
|||
|
CAN: heartbeat time-out consumer 1
|
Warning
|
|||
|
CAN: heartbeat time-out consumer 2
|
Warning
|
|||
|
CAN: heartbeat time-out consumer 3
|
Warning
|
|||
|
CAN: heartbeat time-out consumer 4
|
Warning
|
|||
|
Network - Watchdog time-out
|
Warning
|
|||
|
Network - Disruption of cyclic data exchange
|
No response
|
|||
|
Network - Initialization error
|
Warning
|
|||
|
Network - Invalid cyclic process data
|
Warning
|
|||
|
Network - Initialization with safety option failed
|
Information
|
-
|
||
|
Network - Communication time-out with safety option
|
Information
|
-
|
||
|
Network - Invalid configuration
|
Warning
|
|||
|
CAN: RPDO1 time-out
|
Warning
|
|||
|
CAN: RPDO2 time-out
|
Warning
|
|||
|
CAN: RPDO3 time-out
|
Warning
|
|||
|
CAN: RPDO4 time-out
|
Warning
|
|||