IO-Link port 2

Analog input configuration for IO-Link port 2:
①
③
Scaling
⑤
Optional mapping of the scaled analog values to parameters of the inverter
②
Display of unscaled analog values
④
Display of scaled analog values
The analog inputs can not only be used as frequency setpoint source, but are also available for selection in other parameters.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2652:032
Analog input configuration: IOL2 AI1 source value
–
Read only
 
Parameter object that can be assigned to the process input data of IO-Link port 2 via the IOL2-RPDO mapping (0x24D2:001 ... 0x24D2:016).
–
Mapping entry = 0x265220xx (with xx = number of bits used)
 
0x2652:033
Analog input configuration: IOL2 AI1 target address
0 ... [0] ... 4294967295
0x2652:034
Analog input configuration: IOL2 AI1 scaled value
–
Read only
 
Display of the scaled value.
0x2652:035
Analog input configuration: IOL2 AI1 data type input
0
Signed
1
Unsigned
2
Float32
0x2652:036
Analog input configuration: IOL2 AI2 bits input
2 ... [16] ... 32
Number of the valid bits.
0x2652:037
Analog input configuration: IOL2 AI1 scaling #A1min
-2147483648 ... [0] ... 2147483647
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
 
0x2652:038
Analog input configuration: IOL2 AI1 scaling #A2max
-2147483648 ... [65535] ... 2147483647
0x2652:039
Analog input configuration: IOL2 AI1 data type output
0
Signed
1
Unsigned
0x2652:040
Analog input configuration: IOL2 AI1 bits output
2 ... [16] ... 32
Number of the valid bits.
0x2652:041
Analog input configuration: IOL2 AI1 scaling #B1min
-2147483648 ... [0] ... 2147483647
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
 
0x2652:042
Analog input configuration: IOL2 AI1 scaling #B2max
-2147483648 ... [65535] ... 2147483647
0x2652:045
Analog input configuration: IOL2 AI1 status
–
For further possible settings, see parameter 0x2652:015.
 
0
Inactive
0x2652:047
Analog input configuration: IOL2 AI2 source value
–
Read only
 
Parameter object that can be assigned to the process input data of IO-Link port 2 via the IOL2-RPDO mapping (0x24D2:001 ... 0x24D2:016).
–
Mapping entry = 0x26522Fxx (with xx = number of bits used)
 
0x2652:048
Analog input configuration: IOL2 AI2 target address
0 ... [0] ... 4294967295
0x2652:049
Analog input configuration: IOL2 AI2 scaled value
–
Read only
 
Display of the scaled value.
0x2652:050
Analog input configuration: IOL2 AI2 data type input
0
Signed
1
Unsigned
2
Float32
0x2652:051
Analog input configuration: IOL2 AI2 bits input
2 ... [16] ... 32
Number of the valid bits.
0x2652:052
Analog input configuration: IOL2 AI2 scaling #A1min
-2147483648 ... [0] ... 2147483647
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
 
0x2652:053
Analog input configuration: IOL2 AI2 scaling #A2max
-2147483648 ... [65535] ... 2147483647
0x2652:054
Analog input configuration: IOL2 AI2 data type output
0
Signed
1
Unsigned
0x2652:055
Analog input configuration: IOL2 AI2 bits output
2 ... [16] ... 32
Number of the valid bits.
0x2652:056
Analog input configuration: IOL2 AI2 scaling #B1min
-2147483648 ... [0] ... 2147483647
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
 
0x2652:057
Analog input configuration: IOL2 AI2 scaling #B2max
-2147483648 ... [65535] ... 2147483647
0x2652:060
Analog input configuration: IOL2 AI2 status
–
For further possible settings, see parameter 0x2652:015.
 
0
Inactive