IO-Link port 4
Analog input configuration for IO-Link port 4:
|
①
|
③
|
Scaling
|
⑤
|
Optional mapping of the scaled analog values to parameters of the inverter
|
|
|
②
|
Display of unscaled analog values
|
④
|
Display of scaled analog values
|
|
The analog inputs can not only be used as frequency setpoint source, but are also available for selection in other parameters.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2652:092
|
Analog input configuration: IOL4 AI1 source value
–
Read only
|
Parameter object that can be assigned to the process input data of IO-Link port 4 via the IOL4-RPDO mapping (0x24D6:001 ... 0x24D6:016).
–
Mapping entry = 0x26525Cxx (with xx = number of bits used)
|
|
|
0x2652:093
|
Analog input configuration: IOL4 AI1 target address
0 ... [0] ... 4294967295
|
||
|
0x2652:094
|
Analog input configuration: IOL4 AI1 scaled value
–
Read only
|
Display of the scaled value.
|
|
|
0x2652:095
|
Analog input configuration: IOL4 AI1 data type input
|
||
|
0
|
Signed
|
||
|
1
|
Unsigned
|
||
|
2
|
Float32
|
||
|
0x2652:096
|
Analog input configuration: IOL4 AI2 bits input
2 ... [16] ... 32
|
Number of the valid bits.
|
|
|
0x2652:097
|
Analog input configuration: IOL4 AI1 scaling #A1min
-2147483648 ... [0] ... 2147483647
|
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
|
|
|
0x2652:098
|
Analog input configuration: IOL4 AI1 scaling #A2max
-2147483648 ... [65535] ... 2147483647
|
||
|
0x2652:099
|
Analog input configuration: IOL4 AI1 data type output
|
||
|
0
|
Signed
|
||
|
1
|
Unsigned
|
||
|
0x2652:100
|
Analog input configuration: IOL4 AI1 bits output
2 ... [16] ... 32
|
Number of the valid bits.
|
|
|
0x2652:101
|
Analog input configuration: IOL4 AI1 scaling #B1min
-2147483648 ... [0] ... 2147483647
|
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
|
|
|
0x2652:102
|
Analog input configuration: IOL4 AI1 scaling #B2max
-2147483648 ... [65535] ... 2147483647
|
||
|
0x2652:105
|
Analog input configuration: IOL4 AI1 status
|
||
|
0
|
Inactive
|
||
|
0x2652:107
|
Analog input configuration: IOL4 AI2 source value
–
Read only
|
Parameter object that can be assigned to the process input data of IO-Link port 4 via the IOL4-RPDO mapping (0x24D6:001 ... 0x24D6:016).
–
Mapping entry = 0x26526Bxx (with xx = number of bits used)
|
|
|
0x2652:108
|
Analog input configuration: IOL4 AI2 target address
0 ... [0] ... 4294967295
|
||
|
0x2652:109
|
Analog input configuration: IOL4 AI2 scaled value
–
Read only
|
Display of the scaled value.
|
|
|
0x2652:110
|
Analog input configuration: IOL4 AI2 data type input
|
||
|
0
|
Signed
|
||
|
1
|
Unsigned
|
||
|
2
|
Float32
|
||
|
0x2652:111
|
Analog input configuration: IOL4 AI2 bits input
2 ... [16] ... 32
|
Number of the valid bits.
|
|
|
0x2652:112
|
Analog input configuration: IOL4 AI2 scaling #A1min
-2147483648 ... [0] ... 2147483647
|
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
|
|
|
0x2652:113
|
Analog input configuration: IOL4 AI2 scaling #A2max
-2147483648 ... [65535] ... 2147483647
|
||
|
0x2652:114
|
Analog input configuration: IOL4 AI2 data type output
|
||
|
0
|
Signed
|
||
|
1
|
Unsigned
|
||
|
0x2652:115
|
Analog input configuration: IOL4 AI2 bits output
2 ... [16] ... 32
|
Number of the valid bits.
|
|
|
0x2652:116
|
Analog input configuration: IOL4 AI2 scaling #B1min
-2147483648 ... [0] ... 2147483647
|
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
|
|
|
0x2652:117
|
Analog input configuration: IOL4 AI2 scaling #B2max
-2147483648 ... [65535] ... 2147483647
|
||
|
0x2652:120
|
Analog input configuration: IOL4 AI2 status
|
||
|
0
|
Inactive
|
||