IO-Link port 3
Analog input configuration for IO-Link port 3:
|
①
|
③
|
Scaling
|
⑤
|
Optional mapping of the scaled analog values to parameters of the inverter
|
|
|
②
|
Display of unscaled analog values
|
④
|
Display of scaled analog values
|
|
The analog inputs can not only be used as frequency setpoint source, but are also available for selection in other parameters.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2652:062
|
Analog input configuration: IOL3 AI1 source value
–
Read only
|
Parameter object that can be assigned to the process input data of IO-Link port 3 via the IOL3-RPDO mapping (0x24D4:001 ... 0x24D4:016).
–
Mapping entry = 0x26523Exx (with xx = number of bits used)
|
|
|
0x2652:063
|
Analog input configuration: IOL3 AI1 target address
0 ... [0] ... 4294967295
|
||
|
0x2652:064
|
Analog input configuration: IOL3 AI1 scaled value
–
Read only
|
Display of the scaled value.
|
|
|
0x2652:065
|
Analog input configuration: IOL3 AI1 data type input
|
||
|
0
|
Signed
|
||
|
1
|
Unsigned
|
||
|
2
|
Float32
|
||
|
0x2652:066
|
Analog input configuration: IOL3 AI1 bits input
2 ... [16] ... 32
|
Number of the valid bits.
|
|
|
0x2652:067
|
Analog input configuration: IOL3 AI1 scaling #A1min
-2147483648 ... [0] ... 2147483647
|
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
|
|
|
0x2652:068
|
Analog input configuration: IOL3 AI1 scaling #A2max
-2147483648 ... [65535] ... 2147483647
|
||
|
0x2652:069
|
Analog input configuration: IOL3 AI1 data type output
|
||
|
0
|
Signed
|
||
|
1
|
Unsigned
|
||
|
0x2652:070
|
Analog input configuration: IOL3 AI1 bits output
2 ... [16] ... 32
|
Number of the valid bits.
|
|
|
0x2652:071
|
Analog input configuration: IOL3 AI1 scaling #B1min
-2147483648 ... [0] ... 2147483647
|
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
|
|
|
0x2652:072
|
Analog input configuration: IOL3 AI1 scaling #B2max
-2147483648 ... [65535] ... 2147483647
|
||
|
0x2652:075
|
Analog input configuration: IOL3 AI1 status
|
||
|
0
|
Inactive
|
||
|
0x2652:077
|
Analog input configuration: IOL3 AI2 source value
–
Read only
|
Parameter object that can be assigned to the process input data of IO-Link port 3 via the IOL3-RPDO mapping (0x24D4:001 ... 0x24D4:016).
–
Mapping entry = 0x26524Dxx (with xx = number of bits used)
|
|
|
0x2652:078
|
Analog input configuration: IOL3 AI2 target address
0 ... [0] ... 4294967295
|
||
|
0x2652:079
|
Analog input configuration: IOL3 AI2 scaled value
–
Read only
|
Display of the scaled value.
|
|
|
0x2652:080
|
Analog input configuration: IOL3 AI2 data type input
|
||
|
0
|
Signed
|
||
|
1
|
Unsigned
|
||
|
2
|
Float32
|
||
|
0x2652:081
|
Analog input configuration: IOL3 AI2 bits input
2 ... [16] ... 32
|
Number of the valid bits.
|
|
|
0x2652:082
|
Analog input configuration: IOL3 AI2 scaling #A1min
-2147483648 ... [0] ... 2147483647
|
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
|
|
|
0x2652:083
|
Analog input configuration: IOL3 AI2 scaling #A2max
-2147483648 ... [65535] ... 2147483647
|
||
|
0x2652:084
|
Analog input configuration: IOL3 AI2 data type output
|
||
|
0
|
Signed
|
||
|
1
|
Unsigned
|
||
|
0x2652:085
|
Analog input configuration: IOL3 AI2 bits output
2 ... [16] ... 32
|
Number of the valid bits.
|
|
|
0x2652:086
|
Analog input configuration: IOL3 AI2 scaling #B1min
-2147483648 ... [0] ... 2147483647
|
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
|
|
|
0x2652:087
|
Analog input configuration: IOL3 AI2 scaling #B2max
-2147483648 ... [65535] ... 2147483647
|
||
|
0x2652:090
|
Analog input configuration: IOL3 AI2 status
|
||
|
0
|
Inactive
|
||