Analog input configuration
Selection and configuration of analog values received via IO-Link for use within the inverter.
Details
Individual analog values of the IO-Link process input data can be mapped to internal variables, so-called "analog inputs". The analog inputs can be set, for example, in 0x2860:001 as setpoint source for frequency control or in 0x2860:003 as setpoint source for torque control.
–
2 analog inputs are available for each IO-Link port.
–
For each analog input, there is a parameter object that can be assigned to the corresponding IO-Link process input data via the data mapping.
Note: Each port has its own input signals. It is not allowed to enter a signal from another port in the process data mapping.
Note: Each port has its own input signals. It is not allowed to enter a signal from another port in the process data mapping.
–
The analog values can have a data length of 2 ... 32 bit.
–
A scaling can be parameterized for the analog values:
–
The analog inputs are available for selection in the following parameters:
|
Address
|
Name
|
|
Frequency control: Default setpoint source
|
|
|
PID control: Default setpoint source
|
|
|
Torque control: Default setpoint source
|
|
|
Speed limitation: Upper speed limit source
|
|
|
Speed limitation: Lower speed limit source
|
|
|
Torque limit source selection: Positive torque limit source
|
|
|
Torque limit source selection: Negative torque limit source
|
|
|
Process controller setup (PID): PID process variable
|
|
|
Process controller setup (PID): Speed feedforward control source
|