IO-Link port 2

Analog output configuration for IO-Link port 2:
①
Mapping of the analog values
③
Scaling
⑤
②
Display of unscaled analog values
④
mappable objects (scaled analog values)
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2653:031
Analog output configuration: IOL2 AO1 source address
0 ... [0] ... 4294967295
Mapping of the parameter whose analog value is to be output via IO-Link.
–
Format of the mapping entry: 0xiiiissll (iiii = Index, ss = Subindex, ll = length in bits)
 
–
Transmit mapping must be allowed for the mapped parameter.
 
0x2653:032
Analog output configuration: IOL2 AO1 source value
–
Read only
 
Parameter object into which the value of a parameter is written by means of mapping (subindex 31). The value of the mapped parameter is the input value for scaling.
0x2653:034
Analog output configuration: IOL2 AO1 scaled value
–
Read only
 
Parameter object with scaled value that can be assigned to the process output data of IO-Link port 2 via the IOL2 TPDO mapping (0x24D3:001 ... 0x24D3:016).
–
Mapping entry = 0x265322xx (with xx = number of bits used)
 
0x2653:035
Analog output configuration: IOL2 AO1 data type input
0
Signed
1
Unsigned
0x2653:036
Analog output configuration: IOL2 AO1 bits input
2 ... [16] ... 32
Number of the valid bits.
0x2653:037
Analog output configuration: IOL2 AO1 scaling #A1min
-2147483648 ... [0] ... 2147483647
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
 
0x2653:038
Analog output configuration: IOL2 AO1 scaling #A2max
-2147483648 ... [65535] ... 2147483647
0x2653:039
Analog output configuration: IOL2 AO1 data type output
0
Signed
1
Unsigned
0x2653:040
Analog output configuration: IOL2 AO1 bits output
2 ... [16] ... 32
Number of the valid bits.
0x2653:041
Analog output configuration: IOL2 AO1 scaling #B1min
-2147483648 ... [0] ... 2147483647
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
 
0x2653:042
Analog output configuration: IOL2 AO1 scaling #B2max
-2147483648 ... [65535] ... 2147483647
0x2653:045
Analog output configuration: IOL2 AO1 status
–
For further possible settings, see parameter 0x2652:015.
 
0
Inactive
0x2653:046
Analog output configuration: IOL2 AO2 source address
0 ... [0] ... 4294967295
Mapping of the parameter whose analog value is to be output via IO-Link.
–
Format of the mapping entry: 0xiiiissll (iiii = Index, ss = Subindex, ll = length in bits)
 
–
Transmit mapping must be allowed for the mapped parameter.
 
0x2653:047
Analog output configuration: IOL2 AO2 source value
–
Read only
 
Parameter object into which the value of a parameter is written by means of mapping (subindex 46). The value of the mapped parameter is the input value for scaling.
0x2653:049
Analog output configuration: IOL2 AO2 scaled value
–
Read only
 
Parameter object with scaled value that can be assigned to the process output data of IO-Link port 2 via the IOL2 TPDO mapping (0x24D3:001 ... 0x24D3:016).
–
Mapping entry = 0x265331xx (with xx = number of bits used)
 
0x2653:050
Analog output configuration: IOL2 AO2 data type input
0
Signed
1
Unsigned
0x2653:051
Analog output configuration: IOL2 AO2 bits input
2 ... [16] ... 32
Number of the valid bits.
0x2653:052
Analog output configuration: IOL2 AO2 scaling #A1min
-2147483648 ... [0] ... 2147483647
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
 
0x2653:053
Analog output configuration: IOL2 AO2 scaling #A2max
-2147483648 ... [65535] ... 2147483647
0x2653:054
Analog output configuration: IOL2 AO2 data type output
0
Signed
1
Unsigned
0x2653:055
Analog output configuration: IOL2 AO2 bits output
2 ... [16] ... 32
Number of the valid bits.
0x2653:056
Analog output configuration: IOL2 AO2 scaling #B1min
-2147483648 ... [0] ... 2147483647
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
 
0x2653:057
Analog output configuration: IOL2 AO2 scaling #B2max
-2147483648 ... [65535] ... 2147483647
0x2653:060
Analog output configuration: IOL2 AO2 status
–
For further possible settings, see parameter 0x2652:015.
 
0
Inactive