IO-Link port 3
Analog output configuration for IO-Link port 3:
|
①
|
Mapping of the analog values
|
③
|
Scaling
|
⑤
|
|
|
②
|
Display of unscaled analog values
|
④
|
mappable objects (scaled analog values)
|
||
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2653:061
|
Analog output configuration: IOL3 AO1 source address
0 ... [0] ... 4294967295
|
Mapping of the parameter whose analog value is to be output via IO-Link.
–
Format of the mapping entry: 0xiiiissll (iiii = Index, ss = Subindex, ll = length in bits)
–
Transmit mapping must be allowed for the mapped parameter.
|
|
|
0x2653:062
|
Analog output configuration: IOL3 AO1 source value
–
Read only
|
Parameter object into which the value of a parameter is written by means of mapping (subindex 61). The value of the mapped parameter is the input value for scaling.
|
|
|
0x2653:064
|
Analog output configuration: IOL3 AO1 scaled value
–
Read only
|
Parameter object with scaled value that can be assigned to the process output data of IO-Link port 3 via the IOL3 TPDO mapping (0x24D5:001 ... 0x24D5:016).
–
Mapping entry = 0x265340xx (with xx = number of bits used)
|
|
|
0x2653:065
|
Analog output configuration: IOL3 AO1 data type input
|
||
|
0
|
Signed
|
||
|
1
|
Unsigned
|
||
|
0x2653:066
|
Analog output configuration: IOL3 AO1 bits input
2 ... [16] ... 32
|
Number of the valid bits.
|
|
|
0x2653:067
|
Analog output configuration: IOL3 AO1 scaling #A1min
-2147483648 ... [0] ... 2147483647
|
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
|
|
|
0x2653:068
|
Analog output configuration: IOL3 AO1 scaling #A2max
-2147483648 ... [65535] ... 2147483647
|
||
|
0x2653:069
|
Analog output configuration: IOL3 AO1 data type output
|
||
|
0
|
Signed
|
||
|
1
|
Unsigned
|
||
|
0x2653:070
|
Analog output configuration: IOL3 AO1 bits output
2 ... [16] ... 32
|
Number of the valid bits.
|
|
|
0x2653:071
|
Analog output configuration: IOL3 AO1 scaling #B1min
-2147483648 ... [0] ... 2147483647
|
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
|
|
|
0x2653:072
|
Analog output configuration: IOL3 AO1 scaling #B2max
-2147483648 ... [65535] ... 2147483647
|
||
|
0x2653:075
|
Analog output configuration: IOL3 AO1 status
|
||
|
0
|
Inactive
|
||
|
0x2653:076
|
Analog output configuration: IOL3 AO2 source address
0 ... [0] ... 4294967295
|
Mapping of the parameter whose analog value is to be output via IO-Link.
–
Format of the mapping entry: 0xiiiissll (iiii = Index, ss = Subindex, ll = length in bits)
–
Transmit mapping must be allowed for the mapped parameter.
|
|
|
0x2653:077
|
Analog output configuration: IOL3 AO2 source value
–
Read only
|
Parameter object into which the value of a parameter is written by means of mapping (subindex 76). The value of the mapped parameter is the input value for scaling.
|
|
|
0x2653:079
|
Analog output configuration: IOL3 AO2 scaled value
–
Read only
|
Parameter object with scaled value that can be assigned to the process output data of IO-Link port 3 via the IOL3 TPDO mapping (0x24D5:001 ... 0x24D5:016).
–
Mapping entry = 0x26534Fxx (with xx = number of bits used)
|
|
|
0x2653:080
|
Analog output configuration: IOL3 AO2 data type input
|
||
|
0
|
Signed
|
||
|
1
|
Unsigned
|
||
|
0x2653:081
|
Analog output configuration: IOL3 AO2 bits input
2 ... [16] ... 32
|
Number of the valid bits.
|
|
|
0x2653:082
|
Analog output configuration: IOL3 AO2 scaling #A1min
-2147483648 ... [0] ... 2147483647
|
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
|
|
|
0x2653:083
|
Analog output configuration: IOL3 AO2 scaling #A2max
-2147483648 ... [65535] ... 2147483647
|
||
|
0x2653:084
|
Analog output configuration: IOL3 AO2 data type output
|
||
|
0
|
Signed
|
||
|
1
|
Unsigned
|
||
|
0x2653:085
|
Analog output configuration: IOL3 AO2 bits output
2 ... [16] ... 32
|
Number of the valid bits.
|
|
|
0x2653:086
|
Analog output configuration: IOL3 AO2 scaling #B1min
-2147483648 ... [0] ... 2147483647
|
Scaling
–
The data range depends on the data type (signed/unsigned) and the set number of valid bits.
|
|
|
0x2653:087
|
Analog output configuration: IOL3 AO2 scaling #B2max
-2147483648 ... [65535] ... 2147483647
|
||
|
0x2653:090
|
Analog output configuration: IOL3 AO2 status
|
||
|
0
|
Inactive
|
||