IO-Link port 1
Binary output configuration for IO-Link port 1:
|
①
|
Selection of the status signals
|
②
|
Inversion (optional)
|
③
|
Mappable objects
|
④
|
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2651:001
|
Binary output configuration: IOL1 BO1 value
–
Read only
|
Parameter object that can be assigned to the process output data of IO-Link port 1 via the IOL1-TPDO mapping (0x24D1:001 ... 0x24D1:016).
–
Mapping entry = 0x26510101
|
|
|
0x2651:002
|
Binary output configuration: IOL1 BO1 source
|
||
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
|
1
|
Constant TRUE
|
Trigger is constantly TRUE.
|
|
|
11
|
Digital input 1
|
State of X3/DI1, taking an inversion set in 0x2632:001 into consideration.
|
|
|
12
|
Digital input 2
|
State of X3/DI2, taking an inversion set in 0x2632:002 into consideration.
|
|
|
13
|
Digital input 3
|
State of X3/DI3, taking an inversion set in 0x2632:003 into consideration.
|
|
|
14
|
Digital input 4
|
State of X3/DI4, taking an inversion set in 0x2632:004 into consideration.
|
|
|
15
|
Digital input 5
|
State of X3/DI5, taking an inversion set in 0x2632:005 into consideration.
|
|
|
16
|
Digital input 6
|
State of X3/DI6, taking an inversion set in 0x2632:006 into consideration.
|
|
|
17
|
Digital input 7
|
State of X3/DI7, taking an inversion set in 0x2632:007 into consideration.
|
|
|
18
|
Digital input 8
|
State of X3/DI8, taking an inversion set in 0x2632:008 into consideration.
|
|
|
30
|
NetWordIN1 - bit 12
|
State of NetWordIN1/bit 12 ... 15.
–
Display of NetWordIN1 in 0x4008:001.
–
For implementing an individual control word format, NetWordIN1 can be mapped to a process data input word.
|
|
|
31
|
NetWordIN1 - bit 13
|
||
|
32
|
NetWordIN1 - bit 14
|
||
|
33
|
NetWordIN1 - bit 15
|
||
|
34
|
NetWordIN2 - bit 0
|
State of NetWordIN2/bit 0 ... bit 15.
–
Display of NetWordIN2 in 0x4008:002.
–
For controlling the digital outputs via network, NetWordIN2 can be mapped to a process data input word.
|
|
|
35
|
NetWordIN2 - bit 1
|
||
|
36
|
NetWordIN2 - bit 2
|
||
|
37
|
NetWordIN2 - bit 3
|
||
|
38
|
NetWordIN2 - bit 4
|
||
|
39
|
NetWordIN2 - bit 5
|
||
|
40
|
NetWordIN2 - bit 6
|
||
|
41
|
NetWordIN2 - bit 7
|
||
|
42
|
NetWordIN2 - bit 8
|
||
|
43
|
NetWordIN2 - bit 9
|
||
|
44
|
NetWordIN2 - bit 10
|
||
|
45
|
NetWordIN2 - bit 11
|
||
|
46
|
NetWordIN2 - bit 12
|
||
|
47
|
NetWordIN2 - bit 13
|
||
|
48
|
NetWordIN2 - bit 14
|
||
|
49
|
NetWordIN2 - bit 15
|
||
|
50
|
Running
|
TRUE if inverter and start are enabled and output frequency > 0 Hz. Otherwise FALSE.
Exception, quick stop mode: TRUE if inverter and start are enabled and output frequency > 0.2 Hz. Otherwise FALSE.
|
|
|
51
|
Ready for operation
|
TRUE if inverter is ready for operation (no error active, no STO active and DC-bus voltage ok). Otherwise FALSE.
|
|
|
52
|
Operation enabled
|
TRUE if inverter and start are enabled. Otherwise FALSE.
|
|
|
53
|
Stop active
|
TRUE if inverter is enabled and motor is not started and output frequency = 0.
|
|
|
54
|
Quick stop active
|
TRUE if quick stop is active. Otherwise FALSE.
|
|
|
55
|
Inverter disabled (safety)
|
TRUE if the integrated safety system has inhibited the inverter. Otherwise FALSE.
|
|
|
56
|
Fault active
|
TRUE if error is active. Otherwise FALSE.
|
|
|
57
|
Error (non-resettable) active
|
TRUE if non-resettable error is active. Otherwise FALSE.
|
|
|
58
|
Device warning active
|
TRUE if warning is active. Otherwise FALSE.
–
A warning has no impact on the operating status of the inverter.
–
A warning is reset automatically if the cause has been eliminated.
|
|
|
59
|
Device trouble active
|
TRUE if a fault is active. Otherwise FALSE.
–
In the event of a fault, the motor is brought to a standstill with the quick stop ramp. The inverter is then disabled.
–
Exception: In case of a serious fault, the inverter is disabled immediately. The motor has no torque (coasts).
–
The error state will be left automatically if the error condition is not active anymore.
–
The restart behaviour after trouble can be configured.
Automatic restart after a fault |
|
|
60
|
Heatsink temperature warning active
|
TRUE if current heatsink temperature > warning threshold for temperature monitoring. Otherwise FALSE.
–
Display of the current heatsink temperature in 0x2D84:001.
–
Setting of the warning threshold in 0x2D84:002.
|
|
|
65
|
Motor PTC error active
|
TRUE if an error of the motor PTC has been detected. Otherwise FALSE.
–
The trigger is set irrespective of the response set in 0x2D49:002 when the motor temperature monitoring is triggered.
|
|
|
66
|
Flying restart circuit active
|
TRUE if flying restart circuit active is active. Otherwise FALSE.
|
|
|
67
|
DC braking active
|
TRUE if DC braking is active. Otherwise FALSE.
|
|
|
68
|
Stop command active
|
TRUE if delay to standstill active. Otherwise FALSE.
|
|
|
69
|
Rotational direction reversed
|
TRUE if output frequency is negative. Otherwise FALSE.
|
|
|
70
|
Frequency threshold exceeded
|
TRUE if current output frequency > frequency threshold. Otherwise FALSE.
|
|
|
71
|
Actual speed = 0
|
TRUE if actual output frequency = 0 Hz (
± 0.3 Hz), irrespective of the operating mode. Otherwise FALSE. |
|
|
72
|
Setpoint speed reached
|
TRUE if frequency setpoint reached. Otherwise FALSE.
|
|
|
73
|
PID feedback = setpoint
|
TRUE if the controlled feedback variable = process controller setpoint (± in 0x404D:003 set hysteresis). Otherwise FALSE.
|
|
|
74
|
PID sleep mode active
|
TRUE if the inverter is in "PID sleep mode". Otherwise FALSE.
|
|
|
75
|
PID MIN alarm active
|
TRUE if feedback variable (with activated PID control) < MIN alarm threshold. Otherwise FALSE.
|
|
|
76
|
PID MAX alarm active
|
TRUE if the feedback variable (with activated PID control) > MAX alarm threshold. Otherwise FALSE.
|
|
|
77
|
PID MIN-MAX alarm active
|
TRUE if no PID alarm is active with activated PID control (MIN alarm threshold < feedback variable < MAX alarm threshold). Otherwise FALSE.
|
|
|
78
|
Current limit reached
|
TRUE if current motor current
≥ maximum current. Otherwise FALSE. |
|
|
79
|
Torque limit reached
|
TRUE if torque limit has been reached or exceeded. Otherwise FALSE.
–
Setting "Actual positive torque limit" in 0x2949:003.
–
Setting "Actual negative torque limit" in 0x2949:004.
|
|
|
81
|
Error of analog input 1 active
|
TRUE if the monitoring of the input signal at the analog input 1 has responded. Otherwise FALSE.
This trigger is set as a function of the following settings:
–
Monitoring threshold 0x2636:008
–
Monitoring condition 0x2636:009
The setting of the Error response in 0x2636:010 has no effect on this trigger.
|
|
|
82
|
Error of analog input 2 active
|
TRUE if the monitoring of the input signal at the analog input 2 has responded. Otherwise FALSE.
This trigger is set as a function of the following settings:
–
Monitoring threshold 0x2637:008
–
Monitoring condition 0x2637:009
The setting of the Error response in 0x2637:010 has no effect on this trigger.
|
|
|
83
|
Load loss detected
|
TRUE if actual motor current < threshold for load loss detection after delay time of the load loss detection has elapsed. Otherwise FALSE.
–
Display of the actual current in 0x6078.
–
Setting Threshold in 0x4006:001.
–
Setting Delay time in 0x4006:002.
|
|
|
84
|
Heavy load monitoring
|
TRUE if the actual apparent current of the motor exceeds the threshold for longer than the delay time.
FALSE if the actual apparent current of the motor falls below the threshold value minus 5 % (hysteresis).
|
|
|
108
|
Parameter set 1 active
|
TRUE if parameter set 1 is loaded and active. Otherwise FALSE.
|
|
|
109
|
Parameter set 2 active
|
TRUE if parameter set 2 is loaded and active. Otherwise FALSE.
|
|
|
110
|
Parameter set 3 active
|
TRUE if parameter set 3 is loaded and active. Otherwise FALSE.
|
|
|
111
|
Parameter set 4 active
|
TRUE if parameter set 4 is loaded and active. Otherwise FALSE.
|
|
|
112
|
Parameter set load OK
|
TRUE after any parameter set has been loaded. Otherwise FALSE.
|
|
|
113
|
Parameter set load fail
|
TRUE if any of the parameter sets could not be loaded. Otherwise FALSE.
|
|
|
115
|
Release holding brake
|
Trigger signal for releasing the holding brake (TRUE = release holding brake).
Note!
If this trigger is assigned to the relay or a digital output, the deceleration times set for the respective output are not effective (are internally set to "0"). Only the deceleration time set in 0x2820:012 for closing the holding brake influences in this case the time-dependent behaviour of the output.
|
|
|
117
|
Motor phase failure
|
TRUE if a motor phase failure has been detected. Otherwise FALSE.
Note!
In the "SLSM-PSM" motor control mode, detection for motor phase failure is deactivated if HF injection is active in the low-speed range.
|
|
|
119
|
Holding brake released
|
TRUE, if holding brake is released. Otherwise FALSE.
|
|
|
120
|
Homing active
|
Status signals output by the "Table positioning" function.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
|
|
|
121
|
Homing done
|
||
|
122
|
Manual jog active
|
||
|
123
|
Halt active
|
||
|
124
|
Motor control in limitation
|
||
|
125
|
Set position reached
|
||
|
126
|
Abort active
|
||
|
127
|
Standstill
|
||
|
128
|
Active profile (bit 1)
|
||
|
129
|
Active profile (bit 2)
|
||
|
130
|
Active profile (bit 3)
|
||
|
131
|
Active profile (bit 4)
|
||
|
132
|
Positioning profile active
|
||
|
133
|
Positioning profile done
|
||
|
134
|
Negative hardware limit switch active
|
||
|
135
|
Positive hardware limit switch active
|
||
|
136
|
Touch probe detected
|
||
|
137
|
External position active
|
||
|
155
|
STO active
|
TRUE if the integrated safety system has triggered the "Safe
torque off (STO)" function and if the safe inputs SIA and SIB = LOW (simultaneously). Otherwise FALSE.
|
|
|
169
|
Logic PLC Out bit 0
|
Binary values output by the integrated Logic PLC.
–
These selection options are only available for the I65AMxxxxxxxxxP product variant.
|
|
|
170
|
Logic PLC Out bit 1
|
||
|
171
|
Logic PLC Out bit 2
|
||
|
172
|
Logic PLC Out bit 3
|
||
|
173
|
Logic PLC Out bit 4
|
||
|
174
|
Logic PLC Out bit 5
|
||
|
175
|
Logic PLC Out bit 6
|
||
|
176
|
Logic PLC Out bit 7
|
||
|
177
|
Logic PLC Out bit 8
|
||
|
178
|
Logic PLC Out bit 9
|
||
|
179
|
Logic PLC Out bit 10
|
||
|
180
|
Logic PLC Out bit 11
|
||
|
181
|
Logic PLC Out bit 12
|
||
|
182
|
Logic PLC Out bit 13
|
||
|
183
|
Logic PLC Out bit 14
|
||
|
184
|
Logic PLC Out bit 15
|
||
|
0x2651:003
|
Binary output configuration: IOL1 BO1 inversion
|
||
|
0
|
Not inverted
|
||
|
1
|
Inverted
|
||
|
0x2651:005
|
Binary output configuration: IOL1 BO2 value
–
Read only
|
Parameter object that can be assigned to the process output data of IO-Link port 1 via the IOL1-TPDO mapping (0x24D1:001 ... 0x24D1:016).
–
Mapping entry = 0x26510501
|
|
|
0x2651:006
|
Binary output configuration: IOL1 BO2 source
|
||
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
|
0x2651:007
|
Binary output configuration: IOL1 BO2 inversion
|
||
|
0
|
Not inverted
|
||
|
1
|
Inverted
|
||
|
0x2651:009
|
Binary output configuration: IOL3 BO3 value
–
Read only
|
Parameter object that can be assigned to the process output data of IO-Link port 1 via the IOL1-TPDO mapping (0x24D1:001 ... 0x24D1:016).
–
Mapping entry = 0x26510901
|
|
|
0x2651:010
|
Binary output configuration: IOL3 BO3 source
|
||
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
|
0x2651:011
|
Binary output configuration: IOL1 BO3 inversion
|
||
|
0
|
Not inverted
|
||
|
1
|
Inverted
|
||
|
0x2651:013
|
Binary output configuration: IOL1 BO4 value
–
Read only
|
Parameter object that can be assigned to the process output data of IO-Link port 1 via the IOL1-TPDO mapping (0x24D1:001 ... 0x24D1:016).
–
Mapping entry = 0x26510D01
|
|
|
0x2651:014
|
Binary output configuration: IOL1 BO4 source
|
||
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
|
0x2651:015
|
Binary output configuration: IOL1 BO4 inversion
|
||
|
0
|
Not inverted
|
||
|
1
|
Inverted
|
||
|
0x2651:017
|
Binary output configuration: IOL1 BO5 value
–
Read only
|
Parameter object that can be assigned to the process output data of IO-Link port 1 via the IOL1-TPDO mapping (0x24D1:001 ... 0x24D1:016).
–
Mapping entry = 0x26511101
|
|
|
0x2651:018
|
Binary output configuration: IOL1 BO5 source
|
||
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
|
0x2651:019
|
Binary output configuration: IOL1 BO5 inversion
|
||
|
0
|
Not inverted
|
||
|
1
|
Inverted
|
||
|
0x2651:021
|
Binary output configuration: IOL1 BO6 value
–
Read only
|
Parameter object that can be assigned to the process output data of IO-Link port 1 via the IOL1-TPDO mapping (0x24D1:001 ... 0x24D1:016).
–
Mapping entry = 0x26511501
|
|
|
0x2651:022
|
Binary output configuration: IOL1 BO6 source
|
||
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
|
0x2651:023
|
Binary output configuration: IOL1 BO6 inversion
|
||
|
0
|
Not inverted
|
||
|
1
|
Inverted
|
||
|
0x2651:025
|
Binary output configuration: IOL1 BO7 value
–
Read only
|
Parameter object that can be assigned to the process output data of IO-Link port 1 via the IOL1-TPDO mapping (0x24D1:001 ... 0x24D1:016).
–
Mapping entry = 0x26511901
|
|
|
0x2651:026
|
Binary output configuration: IOL1 BO7 source
|
||
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
|
0x2651:027
|
Binary output configuration: IOL1 BO7 inversion
|
||
|
0
|
Not inverted
|
||
|
1
|
Inverted
|
||
|
0x2651:029
|
Binary output configuration: IOL1 BO8 value
–
Read only
|
Parameter object that can be assigned to the process output data of IO-Link port 1 via the IOL1-TPDO mapping (0x24D1:001 ... 0x24D1:016).
–
Mapping entry = 0x26511D01
|
|
|
0x2651:030
|
Binary output configuration: IOL1 BO8 source
|
||
|
0
|
Not connected
|
No trigger assigned (trigger is constantly FALSE).
|
|
|
0x2651:031
|
Binary output configuration: IOL1 BO8 inversion
|
||
|
0
|
Not inverted
|
||
|
1
|
Inverted
|
||
Safe torque off (STO)