Parameter attribute list

The parameter attribute list in particular contains some information required for reading and writing parameters via network.
 
The following conventions are used in this documentation for specifying the parameter address:
• The index is specified as a hexadecimal value.
• The subindex is specified as a decimal value.
 
 
–
The parameter attribute list contains all parameters of the inverter.
 
–
The parameter attribute list is sorted by addresses (index:subindex) in ascending order.
 
How to read the parameter attribute list:
Column
Meaning
Address
Address of the parameter in the object directory. Format: index:subindex
Name
Parameter name
Default setting
Default setting of the parameter
Category
Functional assignment of the parameter, for example "general", "EtherNet/IP" or "MCTRL" (Motor control).
Data type
Data type of the parameter:
I8
1 byte, with sign
I16
2 bytes with sign
I32
4 bytes with sign
I64
8 bytes with sign
U8
1 byte without sign
U16
2 bytes without sign
U32
4 bytes without sign
U64
8 bytes without sign
REAL32
4 bytes floating point
STRING[xx]
ASCII string (with character length xx)
OCTET[xx]
OCTET string (with xx bytes)
IDX
4 bytes without sign. Is used specially for addressing parameters.
Factor
Factor for data transmission via network,
depending on the number of decimal positions:
1
No decimal positions
10
1 decimal position
100
2 decimal positions
1000
3 decimal positions
10000
4 decimal positions
A
Attributes (combinations of several attributes also possible):
C
Setting can only be changed if the inverter is inhibited.
E
Value is displayed as IP address in the engineering tool.
H
Value is displayed as hexadecimal value in the engineering tool.
I
Parameter is not displayed.
K
Parameter is read-only with the keypad.
O
Parameter can be recorded with the oscilloscope function.
P
Setting is saved in the memory module.
X
Parameter is not displayed in the engineering tools.
M
Mapping:
r
Receive mapping permissible.
t
Transmit mapping permissible.
rt
Receive and transmit mapping permissible.
-
Mapping not permissible.
 
Parameter attribute list (short overview of all parameter indexes)
Address
Name
Default setting
Category
Data type
Factor
A
M
Device data: Product code
- (Read only)
general
STRING[18]
-
-
Device data: Serial number
- (Read only)
general
STRING[50]
-
-
Device data: CU firmware version
- (Read only)
general
STRING[50]
-
-
Device data: CU firmware type
- (Read only)
general
STRING[50]
-
-
Device data: CU bootloader version
- (Read only)
general
STRING[50]
-
-
Device data: PU firmware version
- (Read only)
general
STRING[12]
-
-
Device data: PU firmware type
- (Read only)
general
STRING[12]
-
-
Device data: PU bootloader version
- (Read only)
general
STRING[12]
-
-
Device data: PU bootloader type
- (Read only)
general
STRING[12]
-
-
Device data: Communication firmware revision number
- (Read only)
Network
STRING[50]
-
-
Device data: Safety firmware type
- (Read only)
general
STRING[12]
-
-
Device data: Safety module version
- (Read only)
general
STRING[50]
-
-
Device data: Motor control library version
- (Read only)
MCTRL
STRING[11]
-
-
Device data: RFID firmware version
- (Read only)
general
STRING[11]
-
-
Device data: Security version
- (Read only)
general
STRING[50]
-
-
Device name
"My Device"
general
STRING[128]
PK
-
Error history buffer: Keypad display
- (Read only)
general
U8
1
-
-
Error history buffer: Maximum number of messages
- (Read only)
general
U8
1
-
-
Error history buffer: Latest message
- (Read only)
general
U8
1
-
-
Error history buffer: Latest acknowledgement message
0
general
U8
1
-
-
Error history buffer: New message
- (Read only)
general
U8
1
-
t
Error history buffer: Configuration/Status
1
general
U16
1
-
-
Error history buffer: Message 0
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 1
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 2
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 3
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 4
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 5
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 6
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 7
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 8
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 9
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 10
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 11
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 12
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 13
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 14
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 15
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 16
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 17
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 18
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 19
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 20
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 21
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 22
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 23
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 24
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 25
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 26
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 27
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 28
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 29
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 30
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message 31
- (Read only)
general
OCTET[115]
-
-
Error history buffer: Message number
1
general
U8
1
-
-
Error history buffer: Time stamp
x.xx s (Read only)
general
U32
100
-
-
Error history buffer: Response to error
- (Read only)
general
U8
1
-
-
Error history buffer: Message ID
- (Read only)
general
U16
1
-
-
Error history buffer: Diag Code Ident
- (Read only)
general
U16
1
-
-
Error history buffer: Message counter
- (Read only)
general
U8
1
-
-
Device information: Supported functions
- (Read only)
general
STRING[6]
-
-
Application information: Project name
- (Read only)
general
STRING[128]
-
-
Optical tracking: Start detection
Stop [0]
general
U8
1
-
-
Optical tracking: Blinking duration
5 s
general
U16
1
-
-
Device commands: Load default settings
Off / ready [0]
general
U8
1
C
-
Device commands: Save user data
Off / ready [0]
general
U8
1
-
-
Device commands: Load user data
Off / ready [0]
general
U8
1
C
-
Device commands: Load OEM data
Off / ready [0]
general
U8
1
C
-
Device commands: Save OEM data
Off / ready [0]
general
U8
1
-
-
Device commands: Load parameter set 1
Off / ready [0]
general
U8
1
-
-
Device commands: Load parameter set 2
Off / ready [0]
general
U8
1
-
-
Device commands: Load parameter set 3
Off / ready [0]
general
U8
1
-
-
Device commands: Load parameter set 4
Off / ready [0]
general
U8
1
-
-
Device commands: Save parameter set 1
Off / ready [0]
general
U8
1
-
-
Device commands: Save parameter set 2
Off / ready [0]
general
U8
1
-
-
Device commands: Save parameter set 3
Off / ready [0]
general
U8
1
-
-
Device commands: Save parameter set 4
Off / ready [0]
general
U8
1
-
-
Device commands: Delete logbook
Off / ready [0]
general
U8
1
X
-
Device commands: Disable PDO Communication
Off / ready [0]
general
U8
1
-
-
Device commands: Activate PDO Communication
Off / ready [0]
general
U8
1
-
-
Device commands: Restart Device
Off / ready [0]
general
U8
1
XC
-
Device commands: Start PLC application
Off / ready [0]
general
U8
1
C
-
Device commands: Stop PLC application
Off / ready [0]
general
U8
1
C
-
Device commands: Cold restart PLC application
Off / ready [0]
general
U8
1
-
-
Device commands: Delete PLC application
Off / ready [0]
general
U8
1
-
-
Device commands: Reset to factory settings
Off / ready [0]
general
U8
1
XC
-
Device commands: Secure device reset for downgrade
Off / ready [0]
general
U8
1
XC
-
Special settings: Configure default setting
0
general
U16
1
P
-
Special settings: Configure STO
0
general
U16
1
PC
-
Special settings: STO reaction
No response [0]
general
U8
1
P
-
CRC parameter set
- (Read only)
general
U32
1
-
-
Safety commands: STO and service state
Off / ready [0]
U8
1
-
-
Safety commands: SS1 and service state
Off / ready [0]
U8
1
-
-
Safety commands: Change to service state
Off / ready [0]
U8
1
-
-
Safety commands: Load and check parameters
Off / ready [0]
U8
1
-
-
Safety commands: Accept parameters
Off / ready [0]
U8
1
-
-
Safety commands: Discard parameters
Off / ready [0]
U8
1
-
-
Safety commands: Export all parameters
Off / ready [0]
U8
1
-
-
Safety commands: Reset safety address
Off / ready [0]
U8
1
-
-
Safety commands: Verify safety address
Off / ready [0]
U8
1
-
-
Safety commands: Enable parameters
Off / ready [0]
U8
1
-
-
Safety commands: Activate muting
Off / ready [0]
U8
1
-
-
Safety commands: Reset error
Off / ready [0]
U8
1
-
-
Safety commands: Acknowledge restart
Off / ready [0]
U8
1
-
-
Safety commands: Reset Output Ownership
Off / ready [0]
U8
1
-
-
Safety commands: Confirm sw-updates
Off / ready [0]
U8
1
-
-
Safety commands: State
- (Read only)
U16
1
-
-
Safety commands: Password
0
U32
1
-
-
Parameter set: Version
iSM ES-SOE V1.5 [10505]
Safety
U16
1
P
-
Parameter set: Project CRC
0
U32
1
P
-
Parameter set: Status
- (Read only)
U8
1
-
-
Parameter set: Current CRC
- (Read only)
U32
1
-
-
Parameter set: Last valid CRC
- (Read only)
U32
1
-
-
Parameter set: Parameter setting time stamp
x s (Read only)
U32
1
-
-
Parameter set: Error information 1
- (Read only)
U32
1
-
-
Parameter set: Error information 2
- (Read only)
U32
1
-
-
Parameter set: Error information 3
- (Read only)
U32
1
-
-
Parameter set: Current CRC without specific identifiers
- (Read only)
U32
1
-
-
SD-In: SD-In1 sensor type
Input disabled [0]
Safety
U8
1
P
-
SD-In: SD-In2 sensor type
Input disabled [0]
Safety
U8
1
P
-
SD-In: SD-In1-A sensor type
Input disabled [0]
Safety
U8
1
P
-
SD-In: SD-In1-B sensor type
Input disabled [0]
Safety
U8
1
P
-
SD-In: SD-In2-A sensor type
Input disabled [0]
Safety
U8
1
P
-
SD-In: SD-In2-B sensor type
Input disabled [0]
Safety
U8
1
P
-
SD-In: SD-In1 configuration
Test pulses 1+2, 4+5 [0]
Safety
U8
1
P
-
SD-In: SD-In2 configuration
Test pulses 1+2, 4+5 [0]
Safety
U8
1
P
-
SD-In: SD-In1 A+B configuration
Test pulses 1+2, 4+5 [0]
Safety
U8
1
P
-
SD-In: SD-In2 A+B configuration
Test pulses 1+2, 4+5 [0]
Safety
U8
1
P
-
SD-In: SD-In1 discrepancy time
10 ms
Safety
U16
1
P
-
SD-In: SD-In2 discrepancy time
10 ms
Safety
U16
1
P
-
SD-In: SD-In1 input delay
0 ms
Safety
U16
1
P
-
SD-In: SD-In2 input delay
0 ms
Safety
U16
1
P
-
SD-In: SD-In1-A input delay
0 ms
Safety
U16
1
P
-
SD-In: SD-In1-B input delay
0 ms
Safety
U16
1
P
-
SD-In: SD-In2-A input delay
0 ms
Safety
U16
1
P
-
SD-In: SD-In2-B input delay
0 ms
Safety
U16
1
P
-
Input image
- (Read only)
U32
1
-
-
Status bits inputs: SD-In1
- (Read only)
BOOL
1
X
-
Status bits inputs: SD-In2
- (Read only)
BOOL
1
X
-
Status bits inputs: AIS Dig-In
- (Read only)
BOOL
1
X
-
Status bits inputs: AIE Dig-In
- (Read only)
BOOL
1
X
-
Status bits inputs: SD-In1-A
- (Read only)
BOOL
1
X
-
Status bits inputs: SD-In1-B
- (Read only)
BOOL
1
X
-
Status bits inputs: SD-In2-A
- (Read only)
BOOL
1
X
-
Status bits inputs: SD-In2-B
- (Read only)
BOOL
1
X
-
SD-In: "SD-In1" - Output
Disabled [0]
U8
1
P
-
SD-In: "SD-In2" - Output
Disabled [0]
U8
1
P
-
SD-In: "SD-In1-A" - Output
Disabled [0]
U8
1
P
-
SD-In: "SD-In1-B" - Output
Disabled [0]
U8
1
P
-
SD-In: "SD-In2-A" - Output
Disabled [0]
U8
1
P
-
SD-In: "SD-In2-B" - Output
Disabled [0]
U8
1
P
-
SD-Out: SD-Out1 source S-Bus
Deactivated [0]
Safety
U8
1
P
-
SD-Out: SD-Out1 logic function
OR [0]
Safety
U8
1
P
-
SD-Out: "Error active" - Output
Disabled [0]
U8
1
P
-
Output image
- (Read only)
U16
1
-
-
Status bits outputs: SD-Out1
- (Read only)
BOOL
1
X
-
S-Bus configuration
No safety bus [0]
Safety
U8
1
P
-
S-Bus control bits: SD-Out1
- (Read only)
BOOL
1
X
-
S-Bus: FSoE project CRC
0
Safety
U32
1
-
-
S-Bus: PROFIsafe status
- (Read only)
U8
1
-
-
S-Bus: PROFIsafe status byte
- (Read only)
U8
1
-
-
S-Bus: PROFIsafe control byte
- (Read only)
U8
1
-
-
S-Bus: CIP Safety - Node-ID
276605120
Safety
U32
1
P
-
S-Bus: CIP Safety - SNN Date
4
Safety
U16
1
P
-
S-Bus: CIP Safety - SNN Time
1
Safety
U32
1
P
-
S-Bus: CIP Safety - SCTS Date
18993
Safety
U16
1
P
-
S-Bus: CIP Safety - SCTS Time
43200000
Safety
U32
1
P
-
S-Bus: CIP Safety - status
- (Read only)
U8
1
-
-
S-Bus: CIP Safety - Password
0
Safety
U32
1
P
-
S-Bus: PROFIsafe adress typ 2
1
Safety
U16
1
P
-
Safety software: Firmware version
- (Read only)
STRING[32]
1
-
-
Safety software: Bootloader version
- (Read only)
STRING[32]
1
-
-
Safety software: Supported S-Bus protocols
- (Read only)
U16
1
-
-
Safety software: Diagnostic-bits
- (Read only)
U16
1
-
-
Safety event history: Current severity
- (Read only)
U8
1
-
-
Safety event history: Internal event 1
- (Read only)
U16
1
-
-
Safety event history: Internal event 2
- (Read only)
U16
1
-
-
Safety event history: Internal event 3
- (Read only)
U16
1
-
-
Safety event history: Internal event 4
- (Read only)
U16
1
-
-
Safety event history: Internal event 5
- (Read only)
U16
1
-
-
Safety event history: Internal event 6
- (Read only)
U16
1
-
-
Safety event history: Internal event 7
- (Read only)
U16
1
-
-
Safety event history: Internal event 8
- (Read only)
U16
1
-
-
Safety event history: Internal event 9
- (Read only)
U16
1
-
-
Safety event history: Internal event 10
- (Read only)
U16
1
-
-
Safety event history: Internal event 11
- (Read only)
U16
1
-
-
Safety event history: Internal event 12
- (Read only)
U16
1
-
-
Safety event history: Internal event 13
- (Read only)
U16
1
-
-
Safety event history: Internal event 14
- (Read only)
U16
1
-
-
Safety event history: Internal event 15
- (Read only)
U16
1
-
-
Safety event history: Internal event 16
- (Read only)
U16
1
-
-
Safety hardware: Power-on time
x s (Read only)
U32
1
-
-
Safety status
- (Read only)
U16
1
-
-
0x2133:001
Internal interface: Debug 1
- (Read only)
Safety
U32
1
-
-
0x2133:002
Internal interface: Debug 2
- (Read only)
Safety
U32
1
-
-
0x2133:003
Internal interface: Debug 3
- (Read only)
Safety
U32
1
-
-
0x2133:004
Internal interface: Debug 4
- (Read only)
Safety
U32
1
-
-
0x2133:005
Internal interface: Debug 5
- (Read only)
Safety
U32
1
-
-
0x2133:006
Internal interface: Debug 6
Off / ready [0]
Safety
U8
1
-
-
0x2133:007
Internal interface: Debug 7
0
Safety
U32
1
-
-
0x2133:008
Internal interface: Debug 8
0
Safety
U32
1
-
-
S-Event history CSS: Internal event 1
- (Read only)
U16
1
-
-
S-Event history CSS: Internal event 2
- (Read only)
U16
1
-
-
S-Event history CSS: Internal event 3
- (Read only)
U16
1
-
-
MUT: Mute S-Bus
No muting [0]
Safety
U8
1
P
-
MUT: Mute SD-In1
No muting [0]
Safety
U8
1
P
-
MUT: Mute SD-In2
No muting [0]
Safety
U8
1
P
-
MUT: Mute SD-In1-A
No muting [0]
Safety
U8
1
P
-
MUT: Mute SD-In1-B
No muting [0]
Safety
U8
1
P
-
MUT: Mute SD-In2-A
No muting [0]
Safety
U8
1
P
-
MUT: Mute SD-In2-B
No muting [0]
Safety
U8
1
P
-
MUT: Password
0
Safety
U32
1
P
-
MUT: Remaining time
x s (Read only)
U32
1
-
-
MUT "MUT active" - Output
Disabled [0]
Safety
U8
1
P
-
Communication module ID: Active module ID
- (Read only)
general
U8
1
-
-
Communication module ID: Network selection
0
general
U8
1
C
-
Modbus communication
No action/no error [0]
U8
1
-
-
Modbus settings: Node ID
1
U8
1
P
-
Modbus settings: Baud rate
Automatic [0]
U8
1
P
-
Modbus settings: Data format
Automatic [0]
U8
1
P
-
Modbus settings: Minimum response time
0 ms
U16
1
P
-
Active Modbus settings: Active node ID
- (Read only)
U8
1
-
-
Active Modbus settings: Active baud rate
- (Read only)
U8
1
-
-
Active Modbus settings: Data format
- (Read only)
U8
1
-
-
Modbus monitoring: Time-out time
2.0 s
U16
10
P
-
Modbus statistics: Messages received
- (Read only)
U32
1
-
-
Modbus statistics: Valid messages received
- (Read only)
U32
1
-
-
Modbus statistics: Messages with exceptions
- (Read only)
U32
1
-
-
Modbus statistics: Messages with errors
- (Read only)
U32
1
-
-
Modbus statistics: Messages sent
- (Read only)
U32
1
-
-
Modbus parameter mapping: Parameter 1 ... Parameter 24
0
IDX
PH
-
Modbus register assignment: Register 1 ... Register 24
- (Read only)
U16
1
-
-
Modbus verification code
- (Read only)
U16
1
-
-
Modbus diagnostics of last Rx data: Offset
0
U8
1
-
-
Modbus diagnostics of last Rx data: Data byte 0
- (Read only)
U8
1
H
-
Modbus diagnostics of last Rx data: Data byte 1
- (Read only)
U8
1
H
-
Modbus diagnostics of last Rx data: Data byte 2
- (Read only)
U8
1
H
-
Modbus diagnostics of last Rx data: Data byte 3
- (Read only)
U8
1
H
-
Modbus diagnostics of last Rx data: Data byte 4
- (Read only)
U8
1
H
-
Modbus diagnostics of last Rx data: Data byte 5
- (Read only)
U8
1
H
-
Modbus diagnostics of last Rx data: Data byte 6
- (Read only)
U8
1
H
-
Modbus diagnostics of last Rx data: Data byte 7
- (Read only)
U8
1
H
-
Modbus diagnostics of last Rx data: Data byte 8
- (Read only)
U8
1
H
-
Modbus diagnostics of last Rx data: Data byte 9
- (Read only)
U8
1
H
-
Modbus diagnostics of last Rx data: Data byte 10
- (Read only)
U8
1
H
-
Modbus diagnostics of last Rx data: Data byte 11
- (Read only)
U8
1
H
-
Modbus diagnostics of last Rx data: Data byte 12
- (Read only)
U8
1
H
-
Modbus diagnostics of last Rx data: Data byte 13
- (Read only)
U8
1
H
-
Modbus diagnostics of last Rx data: Data byte 14
- (Read only)
U8
1
H
-
Modbus diagnostics of last Rx data: Data byte 15
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Offset
0
U8
1
-
-
Modbus diagnostics of last Tx data: Data byte 0
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Data byte 1
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Data byte 2
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Data byte 3
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Data byte 4
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Data byte 5
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Data byte 6
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Data byte 7
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Data byte 8
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Data byte 9
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Data byte 10
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Data byte 11
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Data byte 12
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Data byte 13
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Data byte 14
- (Read only)
U8
1
H
-
Modbus diagnostics of last Tx data: Data byte 15
- (Read only)
U8
1
H
-
EtherCAT communication
No action/no error [0]
EtherCAT
U8
1
-
-
EtherCAT settings: Device ID
0
EtherCAT
U16
1
P
-
Active EtherCAT settings: EoE IP address
- (Read only)
EtherCAT
U32
1
E
-
Active EtherCAT settings: EoE subnet mask
- (Read only)
EtherCAT
U32
1
E
-
Active EtherCAT settings: EoE gateway
- (Read only)
EtherCAT
U32
1
E
-
Active EtherCAT settings: Device ID
- (Read only)
EtherCAT
U16
1
-
-
Active EtherCAT settings: EoE virtual MAC address
- (Read only)
EtherCAT
OCTET[6]
-
-
Active EtherCAT settings: Station address
- (Read only)
EtherCAT
U16
1
-
-
Active EtherCAT settings: Tx length
- (Read only)
EtherCAT
U16
1
-
-
Active EtherCAT settings: Rx length
- (Read only)
EtherCAT
U16
1
-
-
EtherCAT service status: Download parameter file
- (Read only)
EtherCAT
U8
1
-
-
EtherCAT status
- (Read only)
EtherCAT
U16
1
-
-
EtherCAT error
- (Read only)
EtherCAT
U16
1
-
-
PROFINET communication
No action/no error [0]
PROFINET
U8
1
-
-
PROFINET settings: IP address
0.0.0.0
PROFINET
U32
1
PE
-
PROFINET settings: Subnet
0.0.0.0
PROFINET
U32
1
PE
-
PROFINET settings: Gateway
0.0.0.0
PROFINET
U32
1
PE
-
PROFINET settings: Station name
"0"
PROFINET
STRING[240]
P
-
PROFINET settings: I&M1 System designation
"0"
PROFINET
STRING[32]
P
-
PROFINET settings: I&M1 Installation site
"0"
PROFINET
STRING[22]
P
-
PROFINET settings: I&M2 Installation date
"0"
PROFINET
STRING[16]
P
-
PROFINET settings: I&M3 additional information
"0"
PROFINET
STRING[54]
P
-
PROFINET settings: I&M4 signature code
"0"
PROFINET
OCTET[54]
P
-
Active PROFINET settings: IP address
- (Read only)
PROFINET
U32
1
E
-
Active PROFINET settings: Subnet
- (Read only)
PROFINET
U32
1
E
-
Active PROFINET settings: Gateway
- (Read only)
PROFINET
U32
1
E
-
Active PROFINET settings: Station name
- (Read only)
PROFINET
STRING[240]
-
-
Active PROFINET settings: MAC Address
- (Read only)
PROFINET
OCTET[6]
-
-
PROFINET status
- (Read only)
PROFINET
U16
1
-
-
PROFINET error: Error 1
- (Read only)
PROFINET
U16
1
-
-
PROFINET error: Error 2
- (Read only)
PROFINET
U16
1
-
-
EtherNet/IP communication
No action/no error [0]
EtherNet/IP
U8
1
-
-
EtherNet/IP settings: IP address
192.168.124.16
EtherNet/IP
U32
1
PE
-
EtherNet/IP settings: Subnet
255.255.255.0
EtherNet/IP
U32
1
PE
-
EtherNet/IP settings: Gateway
0.0.0.0
EtherNet/IP
U32
1
PE
-
EtherNet/IP settings: Host name
"0"
EtherNet/IP
STRING[64]
P
-
EtherNet/IP settings: IP configuration
BOOTP [1]
EtherNet/IP
U8
1
P
-
EtherNet/IP settings: Multicast TTL
1
EtherNet/IP
U8
1
P
-
EtherNet/IP settings: Multicast allocation
Default allocation [0]
EtherNet/IP
U8
1
P
-
EtherNet/IP settings: Multicast IP address
239.64.2.224
EtherNet/IP
U32
1
PE
-
EtherNet/IP settings: Multicast number
1
EtherNet/IP
U8
1
P
-
EtherNet/IP settings: Timeout
10000 ms
EtherNet/IP
U16
1
P
-
EtherNet/IP settings: Inactivity timeout
120 s
EtherNet/IP
U16
1
P
-
Active EtherNet/IP settings: IP address
- (Read only)
EtherNet/IP
U32
1
E
-
Active EtherNet/IP settings: Subnet
- (Read only)
EtherNet/IP
U32
1
E
-
Active EtherNet/IP settings: Gateway
- (Read only)
EtherNet/IP
U32
1
E
-
Active EtherNet/IP settings: MAC address
- (Read only)
EtherNet/IP
OCTET[6]
-
-
Active EtherNet/IP settings: Multicast address
- (Read only)
EtherNet/IP
U32
1
E
-
Port settings: Port 1
Auto-Negotiation [0]
EtherNet/IP
U16
1
P
-
Port settings: Port 2
Auto-Negotiation [0]
EtherNet/IP
U16
1
P
-
Active port settings: Port 1 (X266)
- (Read only)
EtherNet/IP
U16
1
-
-
Active port settings: Port 2 (X267)
- (Read only)
EtherNet/IP
U16
1
-
-
Quality of service
802.1Q Tag disable [0]
EtherNet/IP
U8
1
P
-
CIP module status
- (Read only)
EtherNet/IP
U16
1
-
-
EtherNet/IP status
- (Read only)
EtherNet/IP
U16
1
-
-
Address conflict settings: Detection
Activated [1]
EtherNet/IP
U8
1
P
-
Address conflict settings: Status
- (Read only)
EtherNet/IP
U8
1
-
-
Address conflict settings: Last conflicted MAC addr.
- (Read only)
EtherNet/IP
OCTET[6]
-
-
Address conflict settings: Last conflicted IP address
- (Read only)
EtherNet/IP
U32
1
E
-
DLR network diagnostics: Topology
- (Read only)
EtherNet/IP
U8
1
-
-
DLR network diagnostics: Status
- (Read only)
EtherNet/IP
U8
1
-
-
DLR network diagnostics: Supervisor IP address
- (Read only)
EtherNet/IP
U32
1
E
-
DLR network diagnostics: Supervisor MAC address
- (Read only)
EtherNet/IP
OCTET[6]
-
-
DLR network diagnostics: Beacon interval
x µs (Read only)
EtherNet/IP
U32
1
-
-
DLR network diagnostics: Beacon timeout
x µs (Read only)
EtherNet/IP
U32
1
-
-
DLR network diagnostics: Port1 beacon frames count.
- (Read only)
EtherNet/IP
U32
1
-
-
DLR network diagnostics: Port2 beacon frames count.
- (Read only)
EtherNet/IP
U32
1
-
-
Modbus TCP communication
No action/no error [0]
Modbus TCP
U8
1
-
-
Modbus -TCP/IP settings: IP address
192.168.124.16
Modbus TCP
U32
1
PE
-
Modbus -TCP/IP settings: Subnet
255.255.255.0
Modbus TCP
U32
1
PE
-
Modbus -TCP/IP settings: Gateway
0.0.0.0
Modbus TCP
U32
1
PE
-
Modbus -TCP/IP settings: IP configuration
Stored IP [0]
Modbus TCP
U8
1
P
-
Modbus -TCP/IP settings: Time-to-live value (TTL)
32
Modbus TCP
U8
1
P
-
Modbus -TCP/IP settings: Ethernet time-out
10 s
Modbus TCP
U16
1
P
-
Modbus -TCP/IP settings: Secondary port
502
Modbus TCP
U16
1
P
-
Active Modbus TCP settings: Active IP address
- (Read only)
Modbus TCP
U32
1
E
-
Active Modbus TCP settings: Active subnet
- (Read only)
Modbus TCP
U32
1
E
-
Active Modbus TCP settings: Active gateway
- (Read only)
Modbus TCP
U32
1
E
-
Active Modbus TCP settings: MAC address
- (Read only)
Modbus TCP
OCTET[6]
-
-
Port settings: Port 1
Auto-Negotiation [0]
Modbus TCP
U16
1
P
-
Port settings: Port 2
Auto-Negotiation [0]
Modbus TCP
U16
1
P
-
Active port settings: Port 1
- (Read only)
Modbus TCP
U16
1
-
-
Active port settings: Port 2
- (Read only)
Modbus TCP
U16
1
-
-
Time-out monitoring: Time-out time
2.0 s
Modbus TCP
U16
10
P
-
Time-out monitoring: Keep alive time-out time
2.0 s
Modbus TCP
U16
10
P
-
Time-out monitoring: Keep alive register
0
Modbus TCP
U16
1
K
-
Modbus TCP module status
- (Read only)
Modbus TCP
U16
1
-
-
Modbus TCP/IP network status
- (Read only)
Modbus TCP
U16
1
-
-
Modbus TCP statistics: Messages received
- (Read only)
Modbus TCP
U32
1
-
-
Modbus TCP statistics: Valid messages received
- (Read only)
Modbus TCP
U32
1
-
-
Modbus TCP statistics: Messages with exceptions
- (Read only)
Modbus TCP
U32
1
-
-
Modbus TCP statistics: Messages sent
- (Read only)
Modbus TCP
U32
1
-
-
Modbus TCP/IP parameter mapping: Parameter 1 ... Parameter 24
0
Modbus TCP
IDX
PH
-
Register assignment: Register 1 ... Register 24
- (Read only)
Modbus TCP
U16
1
-
-
Verification code
- (Read only)
Modbus TCP
U16
1
-
-
Modbus TCP/IP diagnostics of last Rx/Tx data: Receive offset
0
Modbus TCP
U8
1
-
-
Modbus TCP/IP diagnostics of last Rx/Tx data: Last Rx message
- (Read only)
Modbus TCP
OCTET[64]
-
-
Modbus TCP/IP diagnostics of last Rx/Tx data: Transmit offset
0
Modbus TCP
U8
1
-
-
Modbus TCP/IP diagnostics of last Rx/Tx data: Last Tx message
- (Read only)
Modbus TCP
OCTET[64]
-
-
IO-Link master: SMI access
"0"
general
OCTET[250]
-
-
IO-Link port 1: Current vendor ID
- (Read only)
general
U16
1
-
-
IO-Link port 1: Current device ID
- (Read only)
general
U32
1
-
-
IO-Link port 1: Product name
- (Read only)
general
STRING[64]
-
-
IO-Link port 1: Firmware version
- (Read only)
general
STRING[64]
-
-
IO-Link port 1: Serial number
- (Read only)
general
STRING[16]
-
-
IO-Link port 1: Product ID
- (Read only)
general
STRING[64]
-
-
IO-Link port 1: Vendor ID
0
general
U16
1
P
-
IO-Link port 1: Device ID
0
general
U32
1
P
-
IO-Link port 1: Validation method
No check [0]
general
U8
1
P
-
IO-Link port 1: Backup method
No data storage [0]
general
U8
1
P
-
IO-Link port 1: Revision ID
0x00
general
U8
1
PH
-
IO-Link port 1: Cycle time
0.0 ms
general
U16
10
P
-
IO-Link port 1: Process data handling in case of error
Keep last data [0]
general
U8
1
P
-
IO-Link port 1: Communication status
- (Read only)
general
U8
1
-
t
IO-Link port 1: Current cycle time
x.x ms (Read only)
general
U16
10
-
-
IO-Link port 1: RPDO data length
- (Read only)
general
U8
1
-
-
IO-Link port 1: Received RPDO data
- (Read only)
general
OCTET[32]
-
-
IO-Link port 1: TPDO data length
- (Read only)
general
U8
1
-
-
IO-Link port 1: Transmitted TPDO data
"0"
general
OCTET[32]
X
-
IO-Link port 1: Enable TPDO data
No action [0]
general
U8
1
X
-
IO-Link port 1: Status PDO data
- (Read only)
general
U8
1
-
t
IO-Link port 1: SDCI protocol
- (Read only)
general
U8
1
H
-
IO-Link port 1: Transmission rate
- (Read only)
general
U8
1
-
-
IO-Link port 1: Error response
No response [0]
general
U8
1
P
-
IO-Link port 1: Warning response
No response [0]
general
U8
1
P
-
IO-Link port 1: Diagnostic data length
- (Read only)
general
U8
1
-
-
IO-Link port 1: Diagnostic entry 0
- (Read only)
general
U32
1
H
-
IO-Link port 1: Diagnostic entry 1
- (Read only)
general
U32
1
H
-
IO-Link port 1: Diagnostic entry 2
- (Read only)
general
U32
1
H
-
IO-Link port 1: Diagnostic entry 3
- (Read only)
general
U32
1
H
-
IO-Link port 1: Diagnostic entry 4
- (Read only)
general
U32
1
H
-
IO-Link port 1: Diagnostic entry 5
- (Read only)
general
U32
1
H
-
IO-Link port 1: Diagnostic entry 6
- (Read only)
general
U32
1
H
-
IO-Link port 1: Diagnostic entry 7
- (Read only)
general
U32
1
H
-
IO-Link port 1: Diagnostic entry 8
- (Read only)
general
U32
1
H
-
IO-Link port 1: Diagnostic entry 9
- (Read only)
general
U32
1
H
-
IO-Link port 2: Current vendor ID
- (Read only)
general
U16
1
-
-
IO-Link port 2: Current device ID
- (Read only)
general
U32
1
-
-
IO-Link port 2: Product name
- (Read only)
general
STRING[64]
-
-
IO-Link port 2: Firmware version
- (Read only)
general
STRING[64]
-
-
IO-Link port 2: Serial number
- (Read only)
general
STRING[16]
-
-
IO-Link port 2: Product ID
- (Read only)
general
STRING[64]
-
-
IO-Link port 2: Vendor ID
0
general
U16
1
P
-
IO-Link port 2: Device ID
0
general
U32
1
P
-
IO-Link port 2: Validation method
No check [0]
general
U8
1
P
-
IO-Link port 2: Backup method
No data storage [0]
general
U8
1
P
-
IO-Link port 2: Revision ID
0x00
general
U8
1
PH
-
IO-Link port 2: Cycle time
0.0 ms
general
U16
10
P
-
IO-Link port 2: Process data handling in case of error
Keep last data [0]
general
U8
1
P
-
IO-Link port 2: Communication status
- (Read only)
general
U8
1
-
t
IO-Link port 2: Current cycle time
x.x ms (Read only)
general
U16
10
-
-
IO-Link port 2: RPDO data length
- (Read only)
general
U8
1
-
-
IO-Link port 2: Received RPDO data
- (Read only)
general
OCTET[32]
-
-
IO-Link port 2: TPDO data length
- (Read only)
general
U8
1
-
-
IO-Link port 2: Transmitted TPDO data
"0"
general
OCTET[32]
X
-
IO-Link port 2: Enable TPDO data
No action [0]
general
U8
1
X
-
IO-Link port 2: Status PDO data
- (Read only)
general
U8
1
-
t
IO-Link port 2: SDCI protocol
- (Read only)
general
U8
1
H
-
IO-Link port 2: Transmission rate
- (Read only)
general
U8
1
-
-
IO-Link port 2: Error response
No response [0]
general
U8
1
P
-
IO-Link port 2: Warning response
No response [0]
general
U8
1
P
-
IO-Link port 2: Diagnostic data length
- (Read only)
general
U8
1
-
-
IO-Link port 2: Diagnostic entry 0
- (Read only)
general
U32
1
H
-
IO-Link port 2: Diagnostic entry 1
- (Read only)
general
U32
1
H
-
IO-Link port 2: Diagnostic entry 2
- (Read only)
general
U32
1
H
-
IO-Link port 2: Diagnostic entry 3
- (Read only)
general
U32
1
H
-
IO-Link port 2: Diagnostic entry 4
- (Read only)
general
U32
1
H
-
IO-Link port 2: Diagnostic entry 5
- (Read only)
general
U32
1
H
-
IO-Link port 2: Diagnostic entry 6
- (Read only)
general
U32
1
H
-
IO-Link port 2: Diagnostic entry 7
- (Read only)
general
U32
1
H
-
IO-Link port 2: Diagnostic entry 8
- (Read only)
general
U32
1
H
-
IO-Link port 2: Diagnostic entry 9
- (Read only)
general
U32
1
H
-
IO-Link port 3: Current vendor ID
- (Read only)
general
U16
1
-
-
IO-Link port 3: Current device ID
- (Read only)
general
U32
1
-
-
IO-Link port 3: Product name
- (Read only)
general
STRING[64]
-
-
IO-Link port 3: Firmware version
- (Read only)
general
STRING[64]
-
-
IO-Link port 3: Serial number
- (Read only)
general
STRING[16]
-
-
IO-Link port 3: Product ID
- (Read only)
general
STRING[64]
-
-
IO-Link port 3: Vendor ID
0
general
U16
1
P
-
IO-Link port 3: Device ID
0
general
U32
1
P
-
IO-Link port 3: Validation method
No check [0]
general
U8
1
P
-
IO-Link port 3: Backup method
No data storage [0]
general
U8
1
P
-
IO-Link port 3: Revision ID
0x00
general
U8
1
PH
-
IO-Link port 3: Cycle time
0.0 ms
general
U16
10
P
-
IO-Link port 3: Process data handling in case of error
Keep last data [0]
general
U8
1
P
-
IO-Link port 3: Communication status
- (Read only)
general
U8
1
-
t
IO-Link port 3: Current cycle time
x.x ms (Read only)
general
U16
10
-
-
IO-Link port 3: RPDO data length
- (Read only)
general
U8
1
-
-
IO-Link port 3: Received RPDO data
- (Read only)
general
OCTET[32]
-
-
IO-Link port 3: TPDO data length
- (Read only)
general
U8
1
-
-
IO-Link port 3: Transmitted TPDO data
"0"
general
OCTET[32]
X
-
IO-Link port 3: Enable TPDO data
No action [0]
general
U8
1
X
-
IO-Link port 3: Status PDO data
- (Read only)
general
U8
1
-
t
IO-Link port 3: SDCI protocol
- (Read only)
general
U8
1
H
-
IO-Link port 3: Transmission rate
- (Read only)
general
U8
1
-
-
IO-Link port 3: Error response
No response [0]
general
U8
1
P
-
IO-Link port 3: Warning response
No response [0]
general
U8
1
P
-
IO-Link port 3: Diagnostic data length
- (Read only)
general
U8
1
-
-
IO-Link port 3: Diagnostic entry 0
- (Read only)
general
U32
1
H
-
IO-Link port 3: Diagnostic entry 1
- (Read only)
general
U32
1
H
-
IO-Link port 3: Diagnostic entry 2
- (Read only)
general
U32
1
H
-
IO-Link port 3: Diagnostic entry 3
- (Read only)
general
U32
1
H
-
IO-Link port 3: Diagnostic entry 4
- (Read only)
general
U32
1
H
-
IO-Link port 3: Diagnostic entry 5
- (Read only)
general
U32
1
H
-
IO-Link port 3: Diagnostic entry 6
- (Read only)
general
U32
1
H
-
IO-Link port 3: Diagnostic entry 7
- (Read only)
general
U32
1
H
-
IO-Link port 3: Diagnostic entry 8
- (Read only)
general
U32
1
H
-
IO-Link port 3: Diagnostic entry 9
- (Read only)
general
U32
1
H
-
IO-Link port 4: Current vendor ID
- (Read only)
general
U16
1
-
-
IO-Link port 4: Current device ID
- (Read only)
general
U32
1
-
-
IO-Link port 4: Product name
- (Read only)
general
STRING[64]
-
-
IO-Link port 4: Firmware version
- (Read only)
general
STRING[64]
-
-
IO-Link port 4: Serial number
- (Read only)
general
STRING[16]
-
-
IO-Link port 4: Product ID
- (Read only)
general
STRING[64]
-
-
IO-Link port 4: Vendor ID
0
general
U16
1
P
-
IO-Link port 4: Device ID
0
general
U32
1
P
-
IO-Link port 4: Validation method
No check [0]
general
U8
1
P
-
IO-Link port 4: Backup method
No data storage [0]
general
U8
1
P
-
IO-Link port 4: Revision ID
0x00
general
U8
1
PH
-
IO-Link port 4: Cycle time
0.0 ms
general
U16
10
P
-
IO-Link port 4: Process data handling in case of error
Keep last data [0]
general
U8
1
P
-
IO-Link port 4: Communication status
- (Read only)
general
U8
1
-
t
IO-Link port 4: Current cycle time
x.x ms (Read only)
general
U16
10
-
-
IO-Link port 4: RPDO data length
- (Read only)
general
U8
1
-
-
IO-Link port 4: Received RPDO data
- (Read only)
general
OCTET[32]
-
-
IO-Link port 4: TPDO data length
- (Read only)
general
U8
1
-
-
IO-Link port 4: Transmitted TPDO data
"0"
general
OCTET[32]
X
-
IO-Link port 4: Enable TPDO data
No action [0]
general
U8
1
X
-
IO-Link port 4: Status PDO data
- (Read only)
general
U8
1
-
t
IO-Link port 4: SDCI protocol
- (Read only)
general
U8
1
H
-
IO-Link port 4: Transmission rate
- (Read only)
general
U8
1
-
-
IO-Link port 4: Error response
No response [0]
general
U8
1
P
-
IO-Link port 4: Warning response
No response [0]
general
U8
1
P
-
IO-Link port 4: Diagnostic data length
- (Read only)
general
U8
1
-
-
IO-Link port 4: Diagnostic entry 0
- (Read only)
general
U32
1
H
-
IO-Link port 4: Diagnostic entry 1
- (Read only)
general
U32
1
H
-
IO-Link port 4: Diagnostic entry 2
- (Read only)
general
U32
1
H
-
IO-Link port 4: Diagnostic entry 3
- (Read only)
general
U32
1
H
-
IO-Link port 4: Diagnostic entry 4
- (Read only)
general
U32
1
H
-
IO-Link port 4: Diagnostic entry 5
- (Read only)
general
U32
1
H
-
IO-Link port 4: Diagnostic entry 6
- (Read only)
general
U32
1
H
-
IO-Link port 4: Diagnostic entry 7
- (Read only)
general
U32
1
H
-
IO-Link port 4: Diagnostic entry 8
- (Read only)
general
U32
1
H
-
IO-Link port 4: Diagnostic entry 9
- (Read only)
general
U32
1
H
-
IOL1-RPDO mapping: Highest subindex
0
general
U8
1
P
-
IOL1-RPDO mapping: Entry 1
0x00000000
general
U32
1
PH
-
IOL1-RPDO mapping: Entry 2
0x00000000
general
U32
1
PH
-
IOL1-RPDO mapping: Entry 3
0x00000000
general
U32
1
PH
-
IOL1-RPDO mapping: Entry 4
0x00000000
general
U32
1
PH
-
IOL1-RPDO mapping: Entry 5
0x00000000
general
U32
1
PH
-
IOL1-RPDO mapping: Entry 6
0x00000000
general
U32
1
PH
-
IOL1-RPDO mapping: Entry 7
0x00000000
general
U32
1
PH
-
IOL1-RPDO mapping: Entry 8
0x00000000
general
U32
1
PH
-
IOL1-RPDO mapping: Entry 9
0x00000000
general
U32
1
PH
-
IOL1-RPDO mapping: Entry 10
0x00000000
general
U32
1
PH
-
IOL1-RPDO mapping: Entry 11
0x00000000
general
U32
1
PH
-
IOL1-RPDO mapping: Entry 12
0x00000000
general
U32
1
PH
-
IOL1-RPDO mapping: Entry 13
0x00000000
general
U32
1
PH
-
IOL1-RPDO mapping: Entry 14
0x00000000
general
U32
1
PH
-
IOL1-RPDO mapping: Entry 15
0x00000000
general
U32
1
PH
-
IOL1-RPDO mapping: Entry 16
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Highest subindex
0
general
U8
1
P
-
IOL1-TPDO mapping: Entry 1
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Entry 2
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Entry 3
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Entry 4
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Entry 5
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Entry 6
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Entry 7
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Entry 8
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Entry 9
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Entry 10
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Entry 11
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Entry 12
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Entry 13
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Entry 14
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Entry 15
0x00000000
general
U32
1
PH
-
IOL1-TPDO mapping: Entry 16
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Highest subindex
0
general
U8
1
P
-
IOL2-RPDO mapping: Entry 1
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Entry 2
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Entry 3
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Entry 4
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Entry 5
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Entry 6
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Entry 7
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Entry 8
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Entry 9
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Entry 10
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Entry 11
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Entry 12
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Entry 13
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Entry 14
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Entry 15
0x00000000
general
U32
1
PH
-
IOL2-RPDO mapping: Entry 16
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Highest subindex
0
general
U8
1
P
-
IOL2-TPDO mapping: Entry 1
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Entry 2
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Entry 3
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Entry 4
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Entry 5
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Entry 6
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Entry 7
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Entry 8
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Entry 9
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Entry 10
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Entry 11
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Entry 12
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Entry 13
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Entry 14
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Entry 15
0x00000000
general
U32
1
PH
-
IOL2-TPDO mapping: Entry 16
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Highest subindex
0
general
U8
1
P
-
IOL3-RPDO mapping: Entry 1
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Entry 2
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Entry 3
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Entry 4
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Entry 5
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Entry 6
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Entry 7
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Entry 8
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Entry 9
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Entry 10
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Entry 11
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Entry 12
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Entry 13
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Entry 14
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Entry 15
0x00000000
general
U32
1
PH
-
IOL3-RPDO mapping: Entry 16
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Highest subindex
0
general
U8
1
P
-
IOL3-TPDO mapping: Entry 1
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Entry 2
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Entry 3
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Entry 4
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Entry 5
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Entry 6
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Entry 7
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Entry 8
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Entry 9
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Entry 10
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Entry 11
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Entry 12
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Entry 13
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Entry 14
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Entry 15
0x00000000
general
U32
1
PH
-
IOL3-TPDO mapping: Entry 16
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Highest subindex
0
general
U8
1
P
-
IOL4-RPDO mapping: Entry 1
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Entry 2
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Entry 3
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Entry 4
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Entry 5
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Entry 6
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Entry 7
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Entry 8
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Entry 9
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Entry 10
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Entry 11
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Entry 12
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Entry 13
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Entry 14
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Entry 15
0x00000000
general
U32
1
PH
-
IOL4-RPDO mapping: Entry 16
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Highest subindex
0
general
U8
1
P
-
IOL4-TPDO mapping: Entry 1
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Entry 2
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Entry 3
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Entry 4
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Entry 5
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Entry 6
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Entry 7
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Entry 8
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Entry 9
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Entry 10
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Entry 11
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Entry 12
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Entry 13
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Entry 14
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Entry 15
0x00000000
general
U32
1
PH
-
IOL4-TPDO mapping: Entry 16
0x00000000
general
U32
1
PH
-
Generic RPDO mapping: Highest subindex
2
general
U8
1
P
-
Generic RPDO mapping: Entry 1
0x60400010
general
U32
1
PH
-
Generic RPDO mapping: Entry 2
0x60420010
general
U32
1
PH
-
Generic RPDO mapping: Entry 3
0x00000000
general
U32
1
PH
-
Generic RPDO mapping: Entry 4
0x00000000
general
U32
1
PH
-
Generic RPDO mapping: Entry 5
0x00000000
general
U32
1
PH
-
Generic RPDO mapping: Entry 6
0x00000000
general
U32
1
PH
-
Generic RPDO mapping: Entry 7
0x00000000
general
U32
1
PH
-
Generic RPDO mapping: Entry 8
0x00000000
general
U32
1
PH
-
Generic RPDO mapping: Entry 9
0x00000000
general
U32
1
PH
-
Generic RPDO mapping: Entry 10
0x00000000
general
U32
1
PH
-
Generic RPDO mapping: Entry 11
0x00000000
general
U32
1
PH
-
Generic RPDO mapping: Entry 12
0x00000000
general
U32
1
PH
-
Generic RPDO mapping: Entry 13
0x00000000
general
U32
1
PH
-
Generic RPDO mapping: Entry 14
0x00000000
general
U32
1
PH
-
Generic RPDO mapping: Entry 15
0x00000000
general
U32
1
PH
-
Generic RPDO mapping: Entry 16
0x00000000
general
U32
1
PH
-
Generic TPDO mapping: Highest subindex
3
general
U8
1
P
-
Generic TPDO mapping: Entry 1
0x60410010
general
U32
1
PH
-
Generic TPDO mapping: Entry 2
0x60440010
general
U32
1
PH
-
Generic TPDO mapping: Entry 3
0x603F0010
general
U32
1
PH
-
Generic TPDO mapping: Entry 4
0x00000000
general
U32
1
PH
-
Generic TPDO mapping: Entry 5
0x00000000
general
U32
1
PH
-
Generic TPDO mapping: Entry 6
0x00000000
general
U32
1
PH
-
Generic TPDO mapping: Entry 7
0x00000000
general
U32
1
PH
-
Generic TPDO mapping: Entry 8
0x00000000
general
U32
1
PH
-
Generic TPDO mapping: Entry 9
0x00000000
general
U32
1
PH
-
Generic TPDO mapping: Entry 10
0x00000000
general
U32
1
PH
-
Generic TPDO mapping: Entry 11
0x00000000
general
U32
1
PH
-
Generic TPDO mapping: Entry 12
0x00000000
general
U32
1
PH
-
Generic TPDO mapping: Entry 13
0x00000000
general
U32
1
PH
-
Generic TPDO mapping: Entry 14
0x00000000
general
U32
1
PH
-
Generic TPDO mapping: Entry 15
0x00000000
general
U32
1
PH
-
Generic TPDO mapping: Entry 16
0x00000000
general
U32
1
PH
-
Process data handling in case of error: Behavior
Keep last data [0]
general
U8
1
P
-
Logic PLC RPDO mapping: Highest subindex
0
general
U8
1
PC
-
Logic PLC RPDO mapping: Entry 1
0x00000000
general
U32
1
PH
-
Logic PLC RPDO mapping: Entry 2
0x00000000
general
U32
1
PH
-
Logic PLC RPDO mapping: Entry 3
0x00000000
general
U32
1
PH
-
Logic PLC RPDO mapping: Entry 4
0x00000000
general
U32
1
PH
-
Logic PLC RPDO mapping: Entry 5
0x00000000
general
U32
1
PH
-
Logic PLC RPDO mapping: Entry 6
0x00000000
general
U32
1
PH
-
Logic PLC RPDO mapping: Entry 7
0x00000000
general
U32
1
PH
-
Logic PLC RPDO mapping: Entry 8
0x00000000
general
U32
1
PH
-
Logic PLC RPDO mapping: Entry 9
0x00000000
general
U32
1
PH
-
Logic PLC RPDO mapping: Entry 10
0x00000000
general
U32
1
PH
-
Logic PLC RPDO mapping: Entry 11
0x00000000
general
U32
1
PH
-
Logic PLC RPDO mapping: Entry 12
0x00000000
general
U32
1
PH
-
Logic PLC RPDO mapping: Entry 13
0x00000000
general
U32
1
PH
-
Logic PLC RPDO mapping: Entry 14
0x00000000
general
U32
1
PH
-
Logic PLC RPDO mapping: Entry 15
0x00000000
general
U32
1
PH
-
Logic PLC RPDO mapping: Entry 16
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Highest subindex
0
general
U8
1
PC
-
Logic PLC TPDO mapping: Entry 1
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Entry 2
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Entry 3
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Entry 4
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Entry 5
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Entry 6
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Entry 7
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Entry 8
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Entry 9
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Entry 10
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Entry 11
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Entry 12
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Entry 13
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Entry 14
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Entry 15
0x00000000
general
U32
1
PH
-
Logic PLC TPDO mapping: Entry 16
0x00000000
general
U32
1
PH
-
Hardware-Diagnose: External supply voltage
x.x V (Read only)
general
U16
10
-
-
Mains settings: Rated mains voltage
230 Veff [0]
general
U8
1
PC
-
Mains settings: Undervoltage warning threshold
0 V
general
U16
1
P
-
Mains settings: Undervoltage error threshold
x V (Read only)
general
U16
1
-
-
Mains settings: Undervoltage reset threshold
x V (Read only)
general
U16
1
-
-
Mains settings: Overvoltage warning threshold
0 V
general
U16
1
P
-
Mains settings: Overvoltage error threshold
x V (Read only)
general
U16
1
-
-
Mains settings: Overvoltage reset threshold
x V (Read only)
general
U16
1
-
-
Brake energy management: Operating mode
Ramp function generator stop (RFGS) [1]
general
U8
1
P
-
Brake energy management: Active threshold
x V (Read only)
general
U16
1
-
-
Brake energy management: Reduced threshold
0 V
general
U16
1
P
-
Brake energy management: Additional frequency
0.0 Hz
general
U16
10
P
-
Brake energy management: Deceleration override time
2.0 s
general
U16
10
P
-
Power recovery management: Status
- (Read only)
general
U8
1
O
-
Favorites settings: Parameter 1
769458176
general
U32
1
P
-
Favorites settings: Parameter 2
1618477056
general
U32
1
P
-
Favorites settings: Parameter 3
763953152
general
U32
1
P
-
Favorites settings: Parameter 4
1614741504
general
U32
1
P
-
Favorites settings: Parameter 5
673447936
general
U32
1
P
-
Favorites settings: Parameter 6
677380352
general
U32
1
P
-
Favorites settings: Parameter 7
674758912
general
U32
1
P
-
Favorites settings: Parameter 8
674759424
general
U32
1
P
-
Favorites settings: Parameter 9
624951552
general
U32
1
P
-
Favorites settings: Parameter 10
689242112
general
U32
1
P
-
Favorites settings: Parameter 11
689307648
general
U32
1
P
-
Favorites settings: Parameter 12
689766656
general
U32
1
P
-
Favorites settings: Parameter 13
689766912
general
U32
1
P
-
Favorites settings: Parameter 14
738197504
general
U32
1
P
-
Favorites settings: Parameter 15
721420288
general
U32
1
P
-
Favorites settings: Parameter 16
721486080
general
U32
1
P
-
Favorites settings: Parameter 17
721486336
general
U32
1
P
-
Favorites settings: Parameter 18
674889728
general
U32
1
P
-
Favorites settings: Parameter 19
691601408
general
U32
1
P
-
Favorites settings: Parameter 20
759890176
general
U32
1
P
-
Favorites settings: Parameter 21
722600192
general
U32
1
P
-
Favorites settings: Parameter 22
1618280448
general
U32
1
P
-
Favorites settings: Parameter 23
1618149376
general
U32
1
P
-
Favorites settings: Parameter 24
640745728
general
U32
1
P
-
Favorites settings: Parameter 25
640745984
general
U32
1
P
-
Favorites settings: Parameter 26
640746240
general
U32
1
P
-
Favorites settings: Parameter 27
640746496
general
U32
1
P
-
Favorites settings: Parameter 28
640746752
general
U32
1
P
-
Favorites settings: Parameter 29
640747008
general
U32
1
P
-
Favorites settings: Parameter 30
640747264
general
U32
1
P
-
Favorites settings: Parameter 31
640747520
general
U32
1
P
-
Favorites settings: Parameter 32
640747776
general
U32
1
P
-
Favorites settings: Parameter 33
640748800
general
U32
1
P
-
Favorites settings: Parameter 34
640750080
general
U32
1
P
-
Favorites settings: Parameter 35
640750336
general
U32
1
P
-
Favorites settings: Parameter 36
640750592
general
U32
1
P
-
Favorites settings: Parameter 37
640942336
general
U32
1
P
-
Favorites settings: Parameter 38
640942592
general
U32
1
P
-
Favorites settings: Parameter 39
641073408
general
U32
1
P
-
Favorites settings: Parameter 40
641073664
general
U32
1
P
-
Favorites settings: Parameter 41
641073920
general
U32
1
P
-
Favorites settings: Parameter 42
641270016
general
U32
1
P
-
Favorites settings: Parameter 43
641270272
general
U32
1
P
-
Favorites settings: Parameter 44
641270528
general
U32
1
P
-
Favorites settings: Parameter 45
641270784
general
U32
1
P
-
Favorites settings: Parameter 46
688980224
general
U32
1
P
-
Favorites settings: Parameter 47
688980480
general
U32
1
P
-
Favorites settings: Parameter 48
688980736
general
U32
1
P
-
Favorites settings: Parameter 49
688980992
general
U32
1
P
-
Favorites settings: Parameter 50
0
general
U32
1
P
-
Settings for digital inputs: Assertion level
HIGH active [1]
general
U8
1
P
-
Settings for digital inputs: Plug X3.1 configuration
DI2 + DI1 [1]
general
U8
1
PC
-
Settings for digital inputs: Plug X3.2 configuration
DI4 + DI3 [1]
general
U8
1
PC
-
Settings for digital inputs: Plug X3.3 configuration
AI1 + DI5 [48]
general
U8
1
PC
-
Settings for digital inputs: Plug X3.4 configuration
AO1 [64]
general
U8
1
PC
-
Settings for digital inputs: Response to overload
Fault > inverter disabled [23]
general
U8
1
P
-
Function list: Enable inverter
Constant TRUE [1]
general
U8
1
PC
-
Function list: Run
Digital input 1 [11]
general
U8
1
PC
-
Function list: Activate quick stop
Not connected [0]
general
U8
1
PC
-
Function list: Reset fault
Digital input 2 [12]
general
U8
1
P
-
Function list: Activate DC braking
Not connected [0]
general
U8
1
P
-
Function list: Start forward (CW)
Not connected [0]
general
U8
1
PC
-
Function list: Start reverse (CCW)
Not connected [0]
general
U8
1
PC
-
Function list: Run forward (CW)
Not connected [0]
general
U8
1
PC
-
Function list: Run reverse (CCW)
Not connected [0]
general
U8
1
PC
-
Function list: Jog forward (CW)
Not connected [0]
general
U8
1
PC
-
Function list: Jog reverse (CCW)
Not connected [0]
general
U8
1
PC
-
Function list: Reverse rotational direction
Digital input 3 [13]
general
U8
1
PC
-
Function list: Activate AI1 setpoint
Not connected [0]
general
U8
1
PC
-
Function list: Activate AI2 setpoint
Not connected [0]
general
U8
1
PC
-
Function list: Activate network setpoint
Not connected [0]
general
U8
1
P
-
Function list: Activate preset (bit 0)
Digital input 4 [14]
general
U8
1
P
-
Function list: Activate preset (bit 1)
Not connected [0]
general
U8
1
P
-
Function list: Activate preset (bit 2)
Not connected [0]
general
U8
1
P
-
Function list: Activate preset (bit 3)
Not connected [0]
general
U8
1
P
-
Function list: MOP setpoint up
Not connected [0]
general
U8
1
P
-
Function list: MOP setpoint down
Not connected [0]
general
U8
1
P
-
Function list: Activate MOP setpoint
Not connected [0]
general
U8
1
P
-
Function list: Activate network control
Not connected [0]
general
U8
1
P
-
Function list: Activate ramp 2
Not connected [0]
general
U8
1
P
-
Function list: Load parameter set
Not connected [0]
general
U8
1
PC
-
Function list: Select parameter set (bit 0)
Not connected [0]
general
U8
1
PC
-
Function list: Select parameter set (bit 1)
Not connected [0]
general
U8
1
PC
-
Function list: Activate fault 1
Not connected [0]
general
U8
1
P
-
Function list: Activate fault 2
Not connected [0]
general
U8
1
P
-
Function list: Disable PID controller
Not connected [0]
general
U8
1
P
-
Function list: Set process controller output to 0
Not connected [0]
general
U8
1
P
-
Function list: Inhibit process controller I-component
Not connected [0]
general
U8
1
P
-
Function list: Activate PID influence ramp
Constant TRUE [1]
general
U8
1
P
-
Function list: Open holding brake
Not connected [0]
general
U8
1
PC
-
Function list: Set position counter
Not connected [0]
general
U8
1
P
-
Function list: Source of negative hardware limit switch
Not connected [0]
general
U8
1
P
-
Function list: Source of positive hardware limit switch
Not connected [0]
general
U8
1
P
-
Function list: Source of flying homing
Not connected [0]
general
U8
1
P
-
Function list: Source of homing switch
Not connected [0]
general
U8
1
P
-
Function list: Manual jog positive
Not connected [0]
general
U8
1
P
-
Function list: Manual jog negative
Not connected [0]
general
U8
1
P
-
Function list: Halt
Not connected [0]
general
U8
1
P
-
Function list: Start homing
Not connected [0]
general
U8
1
P
-
Function list: Reset home position
Not connected [0]
general
U8
1
P
-
Function list: Abort
Not connected [0]
general
U8
1
P
-
Function list: Activate velocity overrride
Not connected [0]
general
U8
1
P
-
Function list: Profile number (bit 0)
Not connected [0]
general
U8
1
P
-
Function list: Profile number (bit 1)
Not connected [0]
general
U8
1
P
-
Function list: Profile number (bit 2)
Not connected [0]
general
U8
1
P
-
Function list: Profile number (bit 3)
Not connected [0]
general
U8
1
P
-
Function list: Start
Not connected [0]
general
U8
1
P
-
Function list: Resume
Not connected [0]
general
U8
1
P
-
Function list: Deactivate touch probe
Not connected [0]
general
U8
1
P
-
Function list: Activate external set position
Not connected [0]
general
U8
1
P
-
Inversion of digital inputs: Digital input 1
Not inverted [0]
general
U8
1
P
-
Inversion of digital inputs: Digital input 2
Not inverted [0]
general
U8
1
P
-
Inversion of digital inputs: Digital input 3
Not inverted [0]
general
U8
1
P
-
Inversion of digital inputs: Digital input 4
Not inverted [0]
general
U8
1
P
-
Inversion of digital inputs: Digital input 5
Not inverted [0]
general
U8
1
P
-
Inversion of digital inputs: Digital input 6
Not inverted [0]
general
U8
1
P
-
Inversion of digital inputs: Digital input 7
Not inverted [0]
general
U8
1
P
-
Inversion of digital inputs: Digital input 8
Not inverted [0]
general
U8
1
P
-
Digital input debounce time: Digital input 1
1 ms
general
U8
1
P
-
Digital input debounce time: Digital input 2
1 ms
general
U8
1
P
-
Digital input debounce time: Digital input 3
1 ms
general
U8
1
P
-
Digital input debounce time: Digital input 4
1 ms
general
U8
1
P
-
Digital input debounce time: Digital input 5
1 ms
general
U8
1
P
-
Digital input debounce time: Digital input 6
1 ms
general
U8
1
P
-
Digital input debounce time: Digital input 7
1 ms
general
U8
1
P
-
Digital input debounce time: Digital input 8
1 ms
general
U8
1
P
-
Digital outputs function: Digital output 1
Operation enabled [52]
general
U8
1
P
-
Digital outputs function: Digital output 2
Fault active [56]
general
U8
1
P
-
Digital outputs function: Digital output 3
Not connected [0]
general
U8
1
P
-
Digital outputs function: Digital output 4
Not connected [0]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 0
Ready for operation [51]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 1
Not connected [0]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 2
Operation enabled [52]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 3
Fault active [56]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 4
Not connected [0]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 5
Quick stop active [54]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 6
Running [50]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 7
Device warning active [58]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 8
Not connected [0]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 9
Not connected [0]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 10
Setpoint speed reached [72]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 11
Current limit reached [78]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 12
Actual speed = 0 [71]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 13
Rotational direction reversed [69]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 14
Not connected [0]
general
U8
1
P
-
Digital outputs function: NetWordOUT1 - bit 15
Inverter disabled (safety) [55]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 0
Not connected [0]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 1
Not connected [0]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 2
Not connected [0]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 3
Not connected [0]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 4
Not connected [0]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 5
Not connected [0]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 6
Not connected [0]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 7
Not connected [0]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 8
Not connected [0]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 9
Not connected [0]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 10
Not connected [0]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 11
Not connected [0]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 12
Not connected [0]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 13
Not connected [0]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 14
Not connected [0]
general
U8
1
P
-
Digital outputs function: Logic PLC In bit 15
Not connected [0]
general
U8
1
P
-
Inversion of digital outputs: Digital output 1
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: Digital output 2
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: Digital output 3
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: Digital output 4
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.00
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.01
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.02
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.03
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.04
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.05
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.06
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.07
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.08
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.09
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.10
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.11
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.12
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.13
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.14
Not inverted [0]
general
U8
1
P
-
Inversion of digital outputs: NetWordOUT1.15
Not inverted [0]
general
U8
1
P
-
Analog input 1: Input range
0 ... 10 VDC [0]
general
U8
1
P
-
Analog input 1: Min frequency value
0.0 Hz
general
S16
10
P
-
Analog input 1: Max frequency value
60.0 Hz
general
S16
10
P
-
Analog input 1: Min PID value
0.00 PID unit
general
S16
100
P
-
Analog input 1: Max PID value
100.00 PID unit
general
S16
100
P
-
Analog input 1: Filter time
10 ms
general
U16
1
P
-
Analog input 1: Dead band
0.0 %
general
U16
10
P
-
Analog input 1: Monitoring threshold
0.0 %
general
S16
10
P
-
Analog input 1: Monitoring condition
Input value < trigger threshold [0]
general
U8
1
P
-
Analog input 1: Error response
Information [11]
general
U8
1
P
-
Analog input 1: Min torque value
0.0 %
general
S16
10
P
-
Analog input 1: Max torque value
100.0 %
general
S16
10
P
-
Analog input 1: Error response AI1
Information [11]
general
U8
1
P
-
Analog input 2: Input range
0 ... 10 VDC [0]
general
U8
1
P
-
Analog input 2: Min frequency value
0.0 Hz
general
S16
10
P
-
Analog input 2: Max frequency value
60.0 Hz
general
S16
10
P
-
Analog input 2: Min PID value
0.00 PID unit
general
S16
100
P
-
Analog input 2: Max PID value
100.00 PID unit
general
S16
100
P
-
Analog input 2: Filter time
10 ms
general
U16
1
P
-
Analog input 2: Dead band
0.0 %
general
U16
10
P
-
Analog input 2: Monitoring threshold
10.0 %
general
S16
10
P
-
Analog input 2: Monitoring condition
Input value > trigger threshold [1]
general
U8
1
P
-
Analog input 2: Error response
Information [11]
general
U8
1
P
-
Analog input 2: Min torque value
0.0 %
general
S16
10
P
-
Analog input 2: Max torque value
100.0 %
general
S16
10
P
-
Analog input 2: Error response AI2
Information [11]
general
U8
1
P
-
Prozess temperature monitoring: Actual temperature
x.x °C (Read only)
general
S16
10
O
t
Prozess temperature monitoring: Temperature sensor type
PT100 [0]
general
U8
1
P
-
Prozess temperature monitoring: Lower monitoring threshold
80.0 °C
general
S16
10
P
-
Prozess temperature monitoring: Upper monitoring threshold
100.0 °C
general
S16
10
P
-
Prozess temperature monitoring: Correction factor
0.00 Ω
general
U16
100
P
-
Prozess temperature monitoring: Fault reaction lower monitoring threshold
No response [0]
general
U8
1
P
-
Prozess temperature monitoring: Fault reaction upper monitoring threshold
No response [0]
general
U8
1
P
-
Prozess temperature monitoring: Status
- (Read only)
general
U8
1
O
-
Analog output 1: Output range
Inhibited [0]
general
U8
1
P
-
Analog output 1: Function
Output frequency [1]
general
U8
1
P
-
Analog output 1: Min. signal
0
general
S32
1
P
-
Analog output 1: Max. signal
1000
general
S32
1
P
-
Analog output 1: Filter time
250 ms
general
U16
1
P
-
HTL input settings: IN1 Filter time constant
10 ms
general
U16
1
P
-
HTL input settings: IN2 Filter time constant
10 ms
general
U16
1
P
-
HTL input monitoring: IN1 Minimal frequency threshold
0.0 Hz
general
S32
10
P
-
HTL input monitoring: IN1 Minimum delay threshold
5.0 s
general
U16
10
P
-
HTL input monitoring: IN1 Maximal frequency threshold
0.0 Hz
general
S32
10
P
-
HTL input monitoring: IN1 Maximum delay threshold
5.0 s
general
U16
10
P
-
HTL input monitoring: IN 1Monitoring conditions
Below minimum frequency [1]
general
U8
1
P
-
HTL input monitoring: IN1 Error response
No response [0]
general
U8
1
P
-
HTL input monitoring: IN2 Minimal frequency threshold
0.0 Hz
general
S32
10
P
-
HTL input monitoring: IN2 Minimum delay threshold
5.0 s
general
U16
10
P
-
HTL input monitoring: IN2 Maximal frequency threshold
0.0 Hz
general
S32
10
P
-
HTL input monitoring: IN2 Maximum delay threshold
5.0 s
general
U16
10
P
-
HTL input monitoring: IN2 Monitoring conditions
Below minimum frequency [1]
general
U8
1
P
-
HTL input monitoring: IN2 Error response
No response [0]
general
U8
1
P
-
HTL input diagnostics: Input frequency
x.x Hz (Read only)
general
S32
10
-
t
HTL input diagnostics: IN2 Input frequency
x.x Hz (Read only)
general
S32
10
-
t
DO1 frequency setup: Function
Not active [0]
general
U8
1
P
-
DO actual frequency: Digital output 1
x.x Hz (Read only)
general
S32
10
-
t
Binary input configuration: IOL1 BI1 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL1 BI1 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL1 BI2 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL1 BI2 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL1 BI3 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL1 BI3 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL1 BI4 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL1 BI4 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL1 BI5 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL1 BI5 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL1 BI6 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL1 BI6 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL1 BI7 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL1 BI7 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL1 BI8 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL1 BI8 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL2 BI1 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL2 BI1 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL2 BI2 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL2 BI2 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL2 BI3 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL2 BI3 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL2 BI4 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL2 BI4 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL2 BI5 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL2 BI5 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL2 BI6 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL2 BI6 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL2 BI7 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL2 BI7 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL2 BI8 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL2 BI8 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL3 BI1 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL3 BI1 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL3 BI2 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL3 BI2 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL3 BI3 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL3 BI3 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL3 BI4 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL3 BI4 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL3 BI5 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL3 BI5 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL3 BI6 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL3 BI6 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL3 BI7 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL3 BI7 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL3 BI8 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL3 BI8 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL4 BI1 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL4 BI1 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL4 BI2 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL4 BI2 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL4 BI3 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL4 BI3 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL4 BI4 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL4 BI4 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL4 BI5 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL4 BI5 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL4 BI6 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL4 BI6 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL4 BI7 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL4 BI7 inversion
Not inverted [0]
general
U8
1
P
-
Binary input configuration: IOL4 BI8 value
- (Read only)
general
U8
1
-
r
Binary input configuration: IOL4 BI8 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL1 BO1 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL1 BO1 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL1 BO1 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL1 BO2 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL1 BO2 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL1 BO2 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO3 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL3 BO3 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL1 BO3 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL1 BO4 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL1 BO4 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL1 BO4 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL1 BO5 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL1 BO5 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL1 BO5 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL1 BO6 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL1 BO6 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL1 BO6 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL1 BO7 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL1 BO7 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL1 BO7 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL1 BO8 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL1 BO8 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL1 BO8 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO1 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL2 BO1 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO1 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO2 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL2 BO2 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO2 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO3 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL2 BO3 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO3 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO4 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL2 BO4 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO4 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO5 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL2 BO5 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO5 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO6 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL2 BO6 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO6 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO7 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL2 BO7 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO7 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO8 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL2 BO8 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL2 BO8 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO1 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL3 BO1 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO1 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO2 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL3 BO2 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO2 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO3 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL3 BO3 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO3 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO4 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL3 BO4 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO4 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO5 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL3 BO5 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO5 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO6 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL3 BO6 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO6 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO7 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL3 BO7 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO7 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO8 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL3 BO8 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL3 BO8 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO1 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL4 BO1 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO1 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO2 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL4 BO2 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO2 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO3 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL4 BO3 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO3 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO4 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL4 BO4 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO4 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO5 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL4 BO5 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO5 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO6 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL4 BO6 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO6 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO7 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL4 BO7 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO7 inversion
Not inverted [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO8 value
- (Read only)
general
U8
1
-
t
Binary output configuration: IOL4 BO8 source
Not connected [0]
general
U8
1
P
-
Binary output configuration: IOL4 BO8 inversion
Not inverted [0]
general
U8
1
P
-
Analog input configuration: IOL1 AI1 source value
- (Read only)
general
S32
1
-
r
Analog input configuration: IOL1 AI1 target address
0
general
U32
1
P
-
Analog input configuration: IOL1 AI1 scaled value
- (Read only)
general
S32
1
-
t
Analog input configuration: IOL1 AI1 data type input
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL1 AI1 bits input
16
general
U8
1
P
-
Analog input configuration: IOL1 AI1 scaling #A1min
0
general
S32
1
P
-
Analog input configuration: IOL1 AI1 scaling #A2max
65535
general
S32
1
P
-
Analog input configuration: IOL1 AI1 data type output
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL1 AI1 bits output
16
general
U8
1
P
-
Analog input configuration: IOL1 AI1 scaling #B1min
0
general
S32
1
P
-
Analog input configuration: IOL1 AI1 scaling #B2max
65535
general
S32
1
P
-
Analog input configuration: IOL1 AI1 status
Inactive [0]
general
U8
1
P
-
Analog input configuration: IOL1 AI2 source value
- (Read only)
general
S32
1
-
r
Analog input configuration: IOL1 AI2 target address
0
general
U32
1
P
-
Analog input configuration: IOL1 AI2 scaled value
- (Read only)
general
S32
1
-
t
Analog input configuration: IOL1 AI2 data type input
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL1 AI2 bits input
16
general
U8
1
P
-
Analog input configuration: IOL1 AI2 scaling #A1min
0
general
S32
1
P
-
Analog input configuration: IOL1 AI2 scaling #A2max
65535
general
S32
1
P
-
Analog input configuration: IOL1 AI2 data type output
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL1 AI2 bits output
16
general
U8
1
P
-
Analog input configuration: IOL1 AI2 scaling #B1min
0
general
S32
1
P
-
Analog input configuration: IOL1 AI2 scaling #B2max
65535
general
S32
1
P
-
Analog input configuration: IOL1 AI2 status
Inactive [0]
general
U8
1
P
-
Analog input configuration: IOL2 AI1 source value
- (Read only)
general
S32
1
-
r
Analog input configuration: IOL2 AI1 target address
0
general
U32
1
P
-
Analog input configuration: IOL2 AI1 scaled value
- (Read only)
general
S32
1
-
t
Analog input configuration: IOL2 AI1 data type input
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL2 AI2 bits input
16
general
U8
1
P
-
Analog input configuration: IOL2 AI1 scaling #A1min
0
general
S32
1
P
-
Analog input configuration: IOL2 AI1 scaling #A2max
65535
general
S32
1
P
-
Analog input configuration: IOL2 AI1 data type output
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL2 AI1 bits output
16
general
U8
1
P
-
Analog input configuration: IOL2 AI1 scaling #B1min
0
general
S32
1
P
-
Analog input configuration: IOL2 AI1 scaling #B2max
65535
general
S32
1
P
-
Analog input configuration: IOL2 AI1 status
Inactive [0]
general
U8
1
P
-
Analog input configuration: IOL2 AI2 source value
- (Read only)
general
S32
1
-
r
Analog input configuration: IOL2 AI2 target address
0
general
U32
1
P
-
Analog input configuration: IOL2 AI2 scaled value
- (Read only)
general
S32
1
-
t
Analog input configuration: IOL2 AI2 data type input
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL2 AI2 bits input
16
general
U8
1
P
-
Analog input configuration: IOL2 AI2 scaling #A1min
0
general
S32
1
P
-
Analog input configuration: IOL2 AI2 scaling #A2max
65535
general
S32
1
P
-
Analog input configuration: IOL2 AI2 data type output
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL2 AI2 bits output
16
general
U8
1
P
-
Analog input configuration: IOL2 AI2 scaling #B1min
0
general
S32
1
P
-
Analog input configuration: IOL2 AI2 scaling #B2max
65535
general
S32
1
P
-
Analog input configuration: IOL2 AI2 status
Inactive [0]
general
U8
1
P
-
Analog input configuration: IOL3 AI1 source value
- (Read only)
general
S32
1
-
r
Analog input configuration: IOL3 AI1 target address
0
general
U32
1
P
-
Analog input configuration: IOL3 AI1 scaled value
- (Read only)
general
S32
1
-
t
Analog input configuration: IOL3 AI1 data type input
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL3 AI1 bits input
16
general
U8
1
P
-
Analog input configuration: IOL3 AI1 scaling #A1min
0
general
S32
1
P
-
Analog input configuration: IOL3 AI1 scaling #A2max
65535
general
S32
1
P
-
Analog input configuration: IOL3 AI1 data type output
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL3 AI1 bits output
16
general
U8
1
P
-
Analog input configuration: IOL3 AI1 scaling #B1min
0
general
S32
1
P
-
Analog input configuration: IOL3 AI1 scaling #B2max
65535
general
S32
1
P
-
Analog input configuration: IOL3 AI1 status
Inactive [0]
general
U8
1
P
-
Analog input configuration: IOL3 AI2 source value
- (Read only)
general
S32
1
-
r
Analog input configuration: IOL3 AI2 target address
0
general
U32
1
P
-
Analog input configuration: IOL3 AI2 scaled value
- (Read only)
general
S32
1
-
t
Analog input configuration: IOL3 AI2 data type input
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL3 AI2 bits input
16
general
U8
1
P
-
Analog input configuration: IOL3 AI2 scaling #A1min
0
general
S32
1
P
-
Analog input configuration: IOL3 AI2 scaling #A2max
65535
general
S32
1
P
-
Analog input configuration: IOL3 AI2 data type output
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL3 AI2 bits output
16
general
U8
1
P
-
Analog input configuration: IOL3 AI2 scaling #B1min
0
general
S32
1
P
-
Analog input configuration: IOL3 AI2 scaling #B2max
65535
general
S32
1
P
-
Analog input configuration: IOL3 AI2 status
Inactive [0]
general
U8
1
P
-
Analog input configuration: IOL4 AI1 source value
- (Read only)
general
S32
1
-
r
Analog input configuration: IOL4 AI1 target address
0
general
U32
1
P
-
Analog input configuration: IOL4 AI1 scaled value
- (Read only)
general
S32
1
-
t
Analog input configuration: IOL4 AI1 data type input
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL4 AI2 bits input
16
general
U8
1
P
-
Analog input configuration: IOL4 AI1 scaling #A1min
0
general
S32
1
P
-
Analog input configuration: IOL4 AI1 scaling #A2max
65535
general
S32
1
P
-
Analog input configuration: IOL4 AI1 data type output
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL4 AI1 bits output
16
general
U8
1
P
-
Analog input configuration: IOL4 AI1 scaling #B1min
0
general
S32
1
P
-
Analog input configuration: IOL4 AI1 scaling #B2max
65535
general
S32
1
P
-
Analog input configuration: IOL4 AI1 status
Inactive [0]
general
U8
1
P
-
Analog input configuration: IOL4 AI2 source value
- (Read only)
general
S32
1
-
r
Analog input configuration: IOL4 AI2 target address
0
general
U32
1
P
-
Analog input configuration: IOL4 AI2 scaled value
- (Read only)
general
S32
1
-
t
Analog input configuration: IOL4 AI2 data type input
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL4 AI2 bits input
16
general
U8
1
P
-
Analog input configuration: IOL4 AI2 scaling #A1min
0
general
S32
1
P
-
Analog input configuration: IOL4 AI2 scaling #A2max
65535
general
S32
1
P
-
Analog input configuration: IOL4 AI2 data type output
Unsigned [1]
general
U8
1
P
-
Analog input configuration: IOL4 AI2 bits output
16
general
U8
1
P
-
Analog input configuration: IOL4 AI2 scaling #B1min
0
general
S32
1
P
-
Analog input configuration: IOL4 AI2 scaling #B2max
65535
general
S32
1
P
-
Analog input configuration: IOL4 AI2 status
Inactive [0]
general
U8
1
P
-
Analog output configuration: IOL1 AO1 source address
0
general
U32
1
P
-
Analog output configuration: IOL1 AO1 source value
- (Read only)
general
S32
1
-
r
Analog output configuration: IOL1 AO1 scaled value
- (Read only)
general
S32
1
-
t
Analog output configuration: IOL1 AO1 data type input
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL1 AO1 bits input
16
general
U8
1
P
-
Analog output configuration: IOL1 AO1 scaling #A1min
0
general
S32
1
P
-
Analog output configuration: IOL1 AO1 scaling #A2max
65535
general
S32
1
P
-
Analog output configuration: IOL1 AO1 data type output
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL1 AO1 bits output
16
general
U8
1
P
-
Analog output configuration: IOL1 AO1 scaling #B1min
0
general
S32
1
P
-
Analog output configuration: IOL1 AO1 scaling #B2max
65535
general
S32
1
P
-
Analog output configuration: IOL1 AO1 status
Inactive [0]
general
U8
1
P
-
Analog output configuration: IOL1 AO2 source address
0
general
U32
1
P
-
Analog output configuration: IOL1 AO2 source value
- (Read only)
general
S32
1
-
r
Analog output configuration: IOL1 AO2 scaled value
- (Read only)
general
S32
1
-
t
Analog output configuration: IOL1 AO2 data type input
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL1 AO2 bits input
16
general
U8
1
P
-
Analog output configuration: IOL1 AO2 scaling #A1min
0
general
S32
1
P
-
Analog output configuration: IOL1 AO2 scaling #A2max
65535
general
S32
1
P
-
Analog output configuration: IOL1 AO2 data type output
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL1 AO2 bits output
16
general
U8
1
P
-
Analog output configuration: IOL1 AO2 scaling #B1min
0
general
S32
1
P
-
Analog output configuration: IOL1 AO2 scaling #B2max
65535
general
S32
1
P
-
Analog output configuration: IOL1 AO2 status
Inactive [0]
general
U8
1
P
-
Analog output configuration: IOL2 AO1 source address
0
general
U32
1
P
-
Analog output configuration: IOL2 AO1 source value
- (Read only)
general
S32
1
-
r
Analog output configuration: IOL2 AO1 scaled value
- (Read only)
general
S32
1
-
t
Analog output configuration: IOL2 AO1 data type input
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL2 AO1 bits input
16
general
U8
1
P
-
Analog output configuration: IOL2 AO1 scaling #A1min
0
general
S32
1
P
-
Analog output configuration: IOL2 AO1 scaling #A2max
65535
general
S32
1
P
-
Analog output configuration: IOL2 AO1 data type output
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL2 AO1 bits output
16
general
U8
1
P
-
Analog output configuration: IOL2 AO1 scaling #B1min
0
general
S32
1
P
-
Analog output configuration: IOL2 AO1 scaling #B2max
65535
general
S32
1
P
-
Analog output configuration: IOL2 AO1 status
Inactive [0]
general
U8
1
P
-
Analog output configuration: IOL2 AO2 source address
0
general
U32
1
P
-
Analog output configuration: IOL2 AO2 source value
- (Read only)
general
S32
1
-
r
Analog output configuration: IOL2 AO2 scaled value
- (Read only)
general
S32
1
-
t
Analog output configuration: IOL2 AO2 data type input
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL2 AO2 bits input
16
general
U8
1
P
-
Analog output configuration: IOL2 AO2 scaling #A1min
0
general
S32
1
P
-
Analog output configuration: IOL2 AO2 scaling #A2max
65535
general
S32
1
P
-
Analog output configuration: IOL2 AO2 data type output
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL2 AO2 bits output
16
general
U8
1
P
-
Analog output configuration: IOL2 AO2 scaling #B1min
0
general
S32
1
P
-
Analog output configuration: IOL2 AO2 scaling #B2max
65535
general
S32
1
P
-
Analog output configuration: IOL2 AO2 status
Inactive [0]
general
U8
1
P
-
Analog output configuration: IOL3 AO1 source address
0
general
U32
1
P
-
Analog output configuration: IOL3 AO1 source value
- (Read only)
general
S32
1
-
r
Analog output configuration: IOL3 AO1 scaled value
- (Read only)
general
S32
1
-
t
Analog output configuration: IOL3 AO1 data type input
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL3 AO1 bits input
16
general
U8
1
P
-
Analog output configuration: IOL3 AO1 scaling #A1min
0
general
S32
1
P
-
Analog output configuration: IOL3 AO1 scaling #A2max
65535
general
S32
1
P
-
Analog output configuration: IOL3 AO1 data type output
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL3 AO1 bits output
16
general
U8
1
P
-
Analog output configuration: IOL3 AO1 scaling #B1min
0
general
S32
1
P
-
Analog output configuration: IOL3 AO1 scaling #B2max
65535
general
S32
1
P
-
Analog output configuration: IOL3 AO1 status
Inactive [0]
general
U8
1
P
-
Analog output configuration: IOL3 AO2 source address
0
general
U32
1
P
-
Analog output configuration: IOL3 AO2 source value
- (Read only)
general
S32
1
-
r
Analog output configuration: IOL3 AO2 scaled value
- (Read only)
general
S32
1
-
t
Analog output configuration: IOL3 AO2 data type input
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL3 AO2 bits input
16
general
U8
1
P
-
Analog output configuration: IOL3 AO2 scaling #A1min
0
general
S32
1
P
-
Analog output configuration: IOL3 AO2 scaling #A2max
65535
general
S32
1
P
-
Analog output configuration: IOL3 AO2 data type output
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL3 AO2 bits output
16
general
U8
1
P
-
Analog output configuration: IOL3 AO2 scaling #B1min
0
general
S32
1
P
-
Analog output configuration: IOL3 AO2 scaling #B2max
65535
general
S32
1
P
-
Analog output configuration: IOL3 AO2 status
Inactive [0]
general
U8
1
P
-
Analog output configuration: IOL4 AO1 source address
0
general
U32
1
P
-
Analog output configuration: IOL4 AO1 source value
- (Read only)
general
S32
1
-
r
Analog output configuration: IOL4 AO1 scaled value
- (Read only)
general
S32
1
-
t
Analog output configuration: IOL4 AO1 data type input
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL4 AO1 bits input
16
general
U8
1
P
-
Analog output configuration: IOL4 AO1 scaling #A1min
0
general
S32
1
P
-
Analog output configuration: IOL4 AO1 scaling #A2max
65535
general
S32
1
P
-
Analog output configuration: IOL4 AO1 data type output
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL4 AO1 bits output
16
general
U8
1
P
-
Analog output configuration: IOL4 AO1 scaling #B1min
0
general
S32
1
P
-
Analog output configuration: IOL4 AO1 scaling #B2max
65535
general
S32
1
P
-
Analog output configuration: IOL4 AO1 status
Inactive [0]
general
U8
1
P
-
Analog output configuration: IOL4 AO2 source address
0
general
U32
1
P
-
Analog output configuration: IOL4 AO2 source value
- (Read only)
general
S32
1
-
r
Analog output configuration: IOL4 AO2 scaled value
- (Read only)
general
S32
1
-
t
Analog output configuration: IOL4 AO2 data type input
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL4 AO2 bits input
16
general
U8
1
P
-
Analog output configuration: IOL4 AO2 scaling #A1min
0
general
S32
1
P
-
Analog output configuration: IOL4 AO2 scaling #A2max
65535
general
S32
1
P
-
Analog output configuration: IOL4 AO2 data type output
Unsigned [1]
general
U8
1
P
-
Analog output configuration: IOL4 AO2 bits output
16
general
U8
1
P
-
Analog output configuration: IOL4 AO2 scaling #B1min
0
general
S32
1
P
-
Analog output configuration: IOL4 AO2 scaling #B2max
65535
general
S32
1
P
-
Analog output configuration: IOL4 AO2 status
Inactive [0]
general
U8
1
P
-
Analog signal scaling: Scaling1 source address
641859872
general
U32
1
P
-
Analog signal scaling: Scaling1 source value
- (Read only)
general
S32
1
-
r
Analog signal scaling: Scaling1 target address
0
general
U32
1
P
-
Analog signal scaling: Scaling1 scaled value
- (Read only)
general
S32
1
-
t
Analog signal scaling: Scaling1 data type input
Signed [0]
general
U8
1
P
-
Analog signal scaling: Scaling1 bits input
32
general
U8
1
P
-
Analog signal scaling: Scaling1 #A1min
0
general
S32
1
P
-
Analog signal scaling: Scaling1 #A2max
65535
general
S32
1
P
-
Analog signal scaling: Scaling1 data type output
Signed [0]
general
U8
1
P
-
Analog signal scaling: Scaling1 bits output
32
general
U8
1
P
-
Analog signal scaling: Scaling1 #B1min
0
general
S32
1
P
-
Analog signal scaling: Scaling1 #B2max
65535
general
S32
1
P
-
Analog signal scaling: Scaling1 status
Inactive [0]
general
U8
1
P
-
Analog signal scaling: Scaling2 source address
0
general
U32
1
P
-
Analog signal scaling: Scaling2 source value
- (Read only)
general
S32
1
-
r
Analog signal scaling: Scaling2 target address
0
general
U32
1
P
-
Analog signal scaling: Scaling2 scaled value
- (Read only)
general
S32
1
-
t
Analog signal scaling: Scaling2 data type input
Unsigned [1]
general
U8
1
P
-
Analog signal scaling: Scaling2 bits input
16
general
U8
1
P
-
Analog signal scaling: Scaling2 #A1min
0
general
S32
1
P
-
Analog signal scaling: Scaling2 #A2max
65535
general
S32
1
P
-
Analog signal scaling: Scaling2 data type output
Unsigned [1]
general
U8
1
P
-
Analog signal scaling: Scaling2 bits output
16
general
U8
1
P
-
Analog signal scaling: Scaling2 #B1min
0
general
S32
1
P
-
Analog signal scaling: Scaling2 #B2max
65535
general
S32
1
P
-
Analog signal scaling: Scaling2 status
Inactive [0]
general
U8
1
P
-
Logic PLC inputs: Input word
- (Read only)
general
U16
1
-
-
Logic PLC inputs: Value 1
- (Read only)
general
U16
1
-
-
Logic PLC inputs: Value 2
- (Read only)
general
U16
1
-
-
Logic PLC inputs: Value 1 selection
Not active [0]
general
U8
1
P
-
Logic PLC inputs: Value 2 selection
Not active [0]
general
U8
1
P
-
Logic PLC outputs: Output word
0
general
U16
1
-
-
Logic PLC outputs: Value 1
0
general
U16
1
-
-
Logic PLC outputs: Value 2
0
general
U16
1
-
-
User parameter 8 bit: Entry 1
0
general
U8
1
O
rt
User parameter 8 bit: Entry 2
0
general
U8
1
O
rt
User parameter 8 bit: Entry 3
0
general
U8
1
O
rt
User parameter 8 bit: Entry 4
0
general
U8
1
O
rt
User parameter 16 bit: Entry 1 ... Entry 16
0
general
U16
1
O
rt
User parameter 32 bit: Entry 1
0
general
U32
1
O
rt
User parameter 32 bit: Entry 2
0
general
U32
1
O
rt
User parameter 32 bit: Entry 3
0
general
U32
1
O
rt
User parameter 32 bit: Entry 4
0
general
U32
1
O
rt
User parameter 32 bit: Entry 5
0
general
U32
1
O
rt
User parameter 32 bit: Entry 6
0
general
U32
1
O
rt
User parameter 32 bit: Entry 7
0
general
U32
1
O
rt
User parameter 32 bit: Entry 8
0
general
U32
1
O
rt
User parameter 16 bit: Entry 1
0
general
U16
1
OP
t
User parameter 16 bit: Entry 2
0
general
U16
1
OP
t
User parameter 16 bit: Entry 3
0
general
U16
1
OP
t
User parameter 16 bit: Entry 4
0
general
U16
1
OP
t
User parameter 16 bit: Entry 5
0
general
U16
1
OP
t
Machine parameter: Motor mounting direction
Not inverted [0]
general
U16
1
PC
-
Holding brake control: Brake mode
Off [2]
general
U8
1
PC
r
Holding brake control: Brake closing time
100 ms
general
U16
1
P
-
Holding brake control: Brake opening time
100 ms
general
U16
1
P
-
Holding brake control: Brake closing threshold
0.2 Hz
general
U16
10
P
-
Holding brake control: Brake holding load
0.0 %
general
S16
10
PC
-
Holding brake control: Closing threshold delay
0 ms
general
U16
1
P
-
Holding brake control: Holding load ramptime
0 ms
general
U16
1
PC
-
Holding brake control: Brake status
- (Read only)
general
U8
1
O
-
Holding brake control: Control configuration
Via internal brake module [0]
general
U8
1
P
-
Holding brake control: Rated voltage
180 VDC [4]
general
U8
1
PC
-
Holding brake control: Brake boost mode
133% / 66% [0]
general
U8
1
P
-
Axis commands: Enable inverter
Inverter inhibited [0]
general
U8
1
X
-
0x2822:002
Axis commands: Activate quick stop
Off / ready [0]
general
U8
1
X
-
0x2822:003
Axis commands: Reset error
Off / ready [0]
general
U8
1
X
-
Axis commands: Identify motor data (energized)
0
MCTRL
U8
1
-
-
Axis commands: Calibrate motor data (non-energized)
0
MCTRL
U8
1
-
-
0x2822:019
Axis commands: Calculate Imax controller parameter
0
MCTRL
U8
1
-
-
Timeout for error response -> quickstop
6.0 s
general
U32
10
P
-
Status words: Cause of disable
- (Read only)
general
U32
1
O
-
Status words: Cause of quick stop
- (Read only)
general
U16
1
O
-
Status words: Cause of stop
- (Read only)
general
U16
1
O
-
Status words: Extended status word
- (Read only)
general
U16
1
O
t
Status words: Device status
- (Read only)
general
U8
1
O
t
Inverter diagnostics: Active control source
- (Read only)
general
U8
1
-
t
Inverter diagnostics: Active setpoint source
- (Read only)
general
U8
1
-
t
Inverter diagnostics: Active drive mode
- (Read only)
general
U8
1
-
t
Inverter diagnostics: Most recently used control register
- (Read only)
general
U32
1
OH
-
Inverter diagnostics: Most recently used setpoint register
- (Read only)
general
U32
1
H
-
Inverter diagnostics: Default frequency setpoint
x.x Hz (Read only)
general
S16
10
-
-
Inverter diagnostics: Preset frequency setpoint
x.x Hz (Read only)
general
S16
10
-
-
Inverter diagnostics: Actual frequency setpoint
x.x Hz (Read only)
general
S16
10
-
-
Inverter diagnostics: Default PID setpoint
x.xx PID unit (Read only)
general
S16
100
-
-
Inverter diagnostics: Preset PID setpoint
x.xx PID unit (Read only)
general
S16
100
-
-
Inverter diagnostics: Default torque setpoint
x.x % (Read only)
general
S16
10
-
-
Inverter diagnostics: Preset torque setpoint
x.x % (Read only)
general
S16
10
-
-
Inverter status word
- (Read only)
MCTRL
U16
1
-
t
Inverter status word 2
- (Read only)
MCTRL
U16
1
-
t
Start/stop configuration: Start method
Normal [0]
general
U8
1
P
-
Start/stop configuration: Start at power-up
Off [0]
general
U8
1
P
-
Start/stop configuration: Stop method
Standard ramp [1]
general
U8
1
P
-
Fault configuration: Restart delay
3.0 s
general
U16
10
P
-
Fault configuration: Number of restart attempts
5
general
U8
1
P
-
Fault configuration: Trouble counter reset time
40.0 s
general
U16
10
P
-
Fault configuration: Trouble counter
- (Read only)
general
U8
1
-
-
Fault configuration: Fault handling in case of state change
Reset fault [0]
general
U8
1
P
-
Limitation of rotation
Both rotational directions [1]
general
U8
1
P
-
Configuration user-defined errors: Error response fault 1
Fault > inverter disabled [23]
general
U8
1
P
-
Configuration user-defined errors: Error text fault 1
"0"
general
STRING[64]
P
-
Configuration user-defined errors: Error response fault 2
Fault > inverter disabled [23]
general
U8
1
P
-
Configuration user-defined errors: Error text fault 2
"0"
general
STRING[64]
P
-
Network monitoring: Watchdog elapsed
Trouble [16]
general
U8
1
P
-
Network monitoring: Invalid configuration
Trouble [16]
general
U8
1
P
-
Network monitoring: Initialisation error
Trouble [16]
general
U8
1
P
-
Network monitoring: Invalid process data
Trouble [16]
general
U8
1
P
-
Network monitoring: Time-out explicit message
Warning [12]
general
U8
1
P
-
Network monitoring: Timeout communication
Warning [12]
general
U8
1
P
-
Network monitoring: Fault response to master timeout
Fault > inverter disabled [23]
general
U8
1
P
-
Network monitoring: Fault response to keep alive timeout
Fault > inverter disabled [23]
general
U8
1
P
-
Network monitoring: Response to time-out
Fault > inverter disabled [23]
general
U8
1
P
-
Diagnostic configuration: Alarm suppression
0
general
U16
1
P
-
Alarm supression: Entry 1
0x00000000
general
U32
1
PH
-
Alarm supression: Entry 2
0x00000000
general
U32
1
PH
-
Alarm supression: Entry 3
0x00000000
general
U32
1
PH
-
Alarm supression: Entry 4
0x00000000
general
U32
1
PH
-
Alarm supression: Entry 5
0x00000000
general
U32
1
PH
-
Alarm supression: Entry 6
0x00000000
general
U32
1
PH
-
Alarm supression: Entry 7
0x00000000
general
U32
1
PH
-
Alarm supression: Entry 8
0x00000000
general
U32
1
PH
-
Alarm supression: Entry 9
0x00000000
general
U32
1
PH
-
Alarm supression: Entry 10
0x00000000
general
U32
1
PH
-
Frequency control: Default setpoint source
Frequency preset 1 [11]
general
U8
1
P
-
PID control: Default setpoint source
PID preset 1 [11]
general
U8
1
P
-
Torque control: Default setpoint source
Torque preset 1 [11]
general
U8
1
P
-
Safety interface: Control data
- (Read only)
U32
1
-
t
Safety interface: Status data
- (Read only)
U32
1
-
t
Safety interface: I/O status
- (Read only)
U32
1
-
t
Safety interface bits: STO active
- (Read only)
BOOL
1
X
-
Safety interface bits: SS1 active
- (Read only)
BOOL
1
X
-
Safety interface bits: SSE active
- (Read only)
BOOL
1
X
-
Safety interface bits: ES active
- (Read only)
BOOL
1
X
-
Safety interface bits: OMS active
- (Read only)
BOOL
1
X
-
Safety interface bits: MUT active
- (Read only)
BOOL
1
X
-
Safety interface bits: Error active
- (Read only)
BOOL
1
X
-
Safety interface bits: AIS S-Bus
- (Read only)
BOOL
1
X
-
Safety interface bits: AIE S-Bus
- (Read only)
BOOL
1
X
-
S-Bus control data
- (Read only)
U32
1
-
-
S-Bus control bits: STO
- (Read only)
BOOL
1
X
-
S-Bus control bits: SS1
- (Read only)
BOOL
1
X
-
S-Bus control bits: ES
- (Read only)
BOOL
1
X
-
S-Bus control bits: OMS
- (Read only)
BOOL
1
X
-
S-Bus control bits: AIS
- (Read only)
BOOL
1
X
-
S-Bus control bits: AIE
- (Read only)
BOOL
1
X
-
S-Bus control bits: SSE
- (Read only)
BOOL
1
X
-
STO Source SD-In
Disabled [0]
Safety
U8
1
P
-
STO Source S-Bus
Disabled [0]
Safety
U8
1
P
-
STO: Restart
Acknowledged restart [0]
Safety
U8
1
P
-
STO "STO active" - Output
Disabled [0]
Safety
U8
1
P
-
SS1, SS2: Stopping time
0 ms
Safety
U16
1
P
-
SS1 Source SD-In
Disabled [0]
Safety
U8
1
P
-
SS1 Source S-Bus
Disabled [0]
Safety
U8
1
P
-
SS1: Mode
STO after stopping time [0]
Safety
U8
1
P
-
SS1 "SS1 active" - Output
Disabled [0]
Safety
U8
1
P
-
SSE Source SD-In
Disabled [0]
Safety
U8
1
P
-
SSE Source S-Bus
Disabled [0]
Safety
U8
1
P
-
SSE: Emergency stop function
STO [0]
Safety
U8
1
P
-
SSE "SSE active" - Output
Disabled [0]
Safety
U8
1
P
-
OMS Source
Disabled [0]
Safety
U8
1
P
-
OMS: Stop function
STO [0]
Safety
U8
1
P
-
OMS: Motion function
Free mode [11]
Safety
U8
1
P
-
OMS: Function at low level
Normal operation [0]
Safety
U8
1
P
-
OMS "OMS active" - Output
Disabled [0]
Safety
U8
1
P
-
ES Source
Disabled [0]
Safety
U8
1
P
-
ES "ES active" - Output
Disabled [0]
Safety
U8
1
P
-
Diagnostic: Configuration diagnostic value 1
Not used [0]
U16
1
P
-
Diagnostic: Configuration diagnostic value 2
Not used [0]
U16
1
P
-
Diagnostic: Diagnostic value 1
- (Read only)
S16
1
-
t
Diagnostic: Diagnostic value 2
- (Read only)
S16
1
-
t
Speed controller settings: Gain
0.00000 Nm/rpm
MCTRL
U32
100000
P
-
Speed controller settings: Reset time
0.0 ms
MCTRL
U16
10
P
-
Actual speed filter time
2.0 ms
MCTRL
U16
10
P
-
Inertia settings: Motor moment of inertia
0.00 kg cm²
MCTRL
U32
100
P
-
Inertia settings: Scaled load inertia
0.00 kg cm²
MCTRL
U32
100
P
-
Inertia settings: Coupling
With backlash [2]
MCTRL
U8
1
P
-
Frequency setpoint presets: Preset 1
20.0 Hz
general
U16
10
P
-
Frequency setpoint presets: Preset 2
40.0 Hz
general
U16
10
P
-
Frequency setpoint presets: Preset 3
50.0 Hz
general
U16
10
P
-
Frequency setpoint presets: Preset 4
0.0 Hz
general
U16
10
P
-
Frequency setpoint presets: Preset 5
0.0 Hz
general
U16
10
P
-
Frequency setpoint presets: Preset 6
0.0 Hz
general
U16
10
P
-
Frequency setpoint presets: Preset 7
0.0 Hz
general
U16
10
P
-
Frequency setpoint presets: Preset 8
0.0 Hz
general
U16
10
P
-
Frequency setpoint presets: Preset 9
0.0 Hz
general
U16
10
P
-
Frequency setpoint presets: Preset 10
0.0 Hz
general
U16
10
P
-
Frequency setpoint presets: Preset 11
0.0 Hz
general
U16
10
P
-
Frequency setpoint presets: Preset 12
0.0 Hz
general
U16
10
P
-
Frequency setpoint presets: Preset 13
0.0 Hz
general
U16
10
P
-
Frequency setpoint presets: Preset 14
0.0 Hz
general
U16
10
P
-
Frequency setpoint presets: Preset 15
0.0 Hz
general
U16
10
P
-
Torque setpoint presets: Preset 1
100.0 %
general
S16
10
P
-
Torque setpoint presets: Preset 2
100.0 %
general
S16
10
P
-
Torque setpoint presets: Preset 3
100.0 %
general
S16
10
P
-
Torque setpoint presets: Preset 4
100.0 %
general
S16
10
P
-
Torque setpoint presets: Preset 5
100.0 %
general
S16
10
P
-
Torque setpoint presets: Preset 6
100.0 %
general
S16
10
P
-
Torque setpoint presets: Preset 7
100.0 %
general
S16
10
P
-
Torque setpoint presets: Preset 8
100.0 %
general
S16
10
P
-
Minimum frequency
0.0 Hz
general
U16
10
P
-
Maximum frequency
50.0 Hz
general
U16
10
P
-
Auto-changeover threshold of ramp 2
0.0 Hz
general
U16
10
P
-
Quick stop deceleration time
1.0 s
general
U16
10
P
-
Ramp times: Acceleration time 1
5.00 s
general
U16
100
P
rt
Ramp times: Deceleration time 1
5.00 s
general
U16
100
P
rt
Ramp times: Acceleration time 2
5.00 s
general
U16
100
P
rt
Ramp times: Deceleration time 2
5.00 s
general
U16
100
P
rt
S-Ramp characteristic: Smoothing factor
0.0 %
general
U16
10
P
r
S-Ramp characteristic: Target window
1.0 Hz
general
U16
10
P
-
S-Ramp characteristic: Stop threshold
10.0 %
general
U16
10
P
-
Skip frequencies: Skip frequency 1
0.0 Hz
general
U16
10
P
-
Skip frequencies: Skip bandwidth 1
0.0 Hz
general
U8
10
P
-
Skip frequencies: Skip frequency 2
0.0 Hz
general
U16
10
P
-
Skip frequencies: Skip bandwidth 2
0.0 Hz
general
U8
10
P
-
Skip frequencies: Skip frequency 3
0.0 Hz
general
U16
10
P
-
Skip frequencies: Skip bandwidth 3
0.0 Hz
general
U8
10
P
-
Skip frequencies: Status
- (Read only)
general
U16
1
X
-
Skip frequencies: Input frequency
x.xx Hz (Read only)
general
S32
100
X
-
Skip frequencies: Output frequency
x.xx Hz (Read only)
general
S32
100
X
-
Switching frequency
0
general
U8
1
P
-
Actual switching frequency
- (Read only)
general
U8
1
-
t
Current controller parameters: Gain
0.00 V/A
MCTRL
U32
100
P
-
Current controller parameters: Reset time
0.00 ms
MCTRL
U32
100
P
-
Current controller parameters: d-axis gain
0.00 V/A
MCTRL
U32
100
P
-
Current controller parameters: d-axis reset time
0.00 ms
MCTRL
U32
100
P
-
Current controller parameters: q-axis gain
0.00 V/A
MCTRL
U32
100
P
-
Current controller parameters: q-axis reset time
0.00 ms
MCTRL
U32
100
P
-
Speed limitation: Upper speed limit
0 rpm
general
S32
480000/2^31-1
P
r
Speed limitation: Lower speed limit
0 rpm
general
S32
480000/2^31-1
P
r
Speed limitation: Upper speed limit source
Maximum frequency [0]
general
U8
1
P
-
Speed limitation: Lower speed limit source
(-) Maximum frequency [0]
general
U8
1
P
-
Speed limitation: Upper frequency limit
50.0 Hz
general
S16
10
P
-
Speed limitation: Lower frequency limit
-50.0 Hz
general
S16
10
P
-
Speed limitation: Actual upper speed limit
x.x Hz (Read only)
general
S16
10
-
-
Speed limitation: Actual lower speed limit
x.x Hz (Read only)
general
S16
10
-
-
Inverter characteristic: Value y1 ... Value y17
0.00 V
MCTRL
U16
100
P
-
Torque setpoint: Actual torque setpoint
x.x % (Read only)
general
S16
10
O
-
Torque setpoint: ramp time
1.0 s
general
U16
10
P
-
Torque limit source selection: Positive torque limit source
Max torque [0]
general
U8
1
P
-
Torque limit source selection: Negative torque limit source
(-) Max torque [0]
general
U8
1
P
-
Torque limit source selection: Actual positive torque limit
x.x % (Read only)
general
S16
10
-
-
Torque limit source selection: Actual negative torque limit
x.x % (Read only)
general
S16
10
-
-
Position controller gain
28.40 1/s
MCTRL
U32
100
P
-
Position controller output signal limitation
480000 rpm
MCTRL
U32
240000/2^30
OP
r
Field controller settings: Gain
0.00 A/Vs
MCTRL
U32
100
P
-
Field controller settings: Reset time
0.0 ms
MCTRL
U16
10
P
-
Field weakening controller settings: Gain (ASM)
0.000 Vs/V
MCTRL
U32
1000
P
-
Field weakening controller settings: Reset time (ASM)
0.0 ms
MCTRL
U32
10
P
-
Field weakening controller settings: Reset time (PSM)
0.0 ms
MCTRL
U32
10
P
-
Field weakening controller Field limitation
100.00 %
MCTRL
U16
100
P
-
DC-bus filter time
25.0 ms
MCTRL
U16
10
P
-
Motor voltage filter time
25.0 ms
MCTRL
U16
10
P
-
Voltage reserve range
5 %
MCTRL
U8
1
P
-
V/f characteristic shape
Linear [0]
MCTRL
U8
1
PC
-
V/f shape data: Base voltage
0 V
MCTRL
U16
1
P
-
V/f shape data: Base frequency
0 Hz
MCTRL
U16
1
P
-
V/f shape data: Midpoint voltage
0 V
MCTRL
U16
1
P
-
V/f shape data: Midpoint frequency
0 Hz
MCTRL
U16
1
P
-
Frequency grid points (x) user V/f characteristic: x1 = f01
-50 Hz
MCTRL
S16
1
P
-
Frequency grid points (x) user V/f characteristic: x2 = f02
-40 Hz
MCTRL
S16
1
P
-
Frequency grid points (x) user V/f characteristic: x3 = f03
-30 Hz
MCTRL
S16
1
P
-
Frequency grid points (x) user V/f characteristic: x4 = f04
-20 Hz
MCTRL
S16
1
P
-
Frequency grid points (x) user V/f characteristic: x5 = f05
-10 Hz
MCTRL
S16
1
P
-
Frequency grid points (x) user V/f characteristic: x6 = f06
0 Hz
MCTRL
S16
1
P
-
Frequency grid points (x) user V/f characteristic: x7 = f07
10 Hz
MCTRL
S16
1
P
-
Frequency grid points (x) user V/f characteristic: x8 = f08
20 Hz
MCTRL
S16
1
P
-
Frequency grid points (x) user V/f characteristic: x9 = f09
30 Hz
MCTRL
S16
1
P
-
Frequency grid points (x) user V/f characteristic: x10 = f10
40 Hz
MCTRL
S16
1
P
-
Frequency grid points (x) user V/f characteristic: x11 = f11
50 Hz
MCTRL
S16
1
P
-
Voltage grid points (y) user V/f characteristic: y1 = U01 (x = f01)
400.00 V
MCTRL
S32
100
P
-
Voltage grid points (y) user V/f characteristic: y2 = U02 (x = f02)
320.00 V
MCTRL
S32
100
P
-
Voltage grid points (y) user V/f characteristic: y3 = U03 (x = f03)
240.00 V
MCTRL
S32
100
P
-
Voltage grid points (y) user V/f characteristic: y4 = U04 (x = f04)
160.00 V
MCTRL
S32
100
P
-
Voltage grid points (y) user V/f characteristic: y5 = U05 (x = f05)
80.00 V
MCTRL
S32
100
P
-
Voltage grid points (y) user V/f characteristic: y6 = U06 (x = f06)
0.00 V
MCTRL
S32
100
P
-
Voltage grid points (y) user V/f characteristic: y7 = U07 (x = f07)
80.00 V
MCTRL
S32
100
P
-
Voltage grid points (y) user V/f characteristic: y8 = U08 (x = f08)
160.00 V
MCTRL
S32
100
P
-
Voltage grid points (y) user V/f characteristic: y9 = U09 (x = f09)
240.00 V
MCTRL
S32
100
P
-
Voltage grid points (y) user V/f characteristic: y10 = U10 (x = f10)
320.00 V
MCTRL
S32
100
P
-
Voltage grid points (y) user V/f characteristic: y11 = U11 (x = f11)
400.00 V
MCTRL
S32
100
P
-
Load adaption: Direction of rotation
Passive load [0]
MCTRL
U8
1
PC
-
Load adaption: Load adaption value
0.00 %
MCTRL
U32
100
P
-
V/f Imax controller: Gain
0.000 Hz/A
MCTRL
U32
1000
P
-
V/f Imax controller: Reset time
0.0 ms
MCTRL
U32
10
P
-
Slip compensation: Gain
100.00 %
MCTRL
S16
100
P
-
Slip compensation: Filter time
100 ms
MCTRL
U16
1
P
-
Oscillation damping: Gain
150 %
MCTRL
S16
1
P
-
Oscillation damping: Filter time
30 ms
MCTRL
U16
1
P
-
Ramp generator frequency
x.x Hz (Read only)
MCTRL
S16
10
O
t
Override field weakening
-40.0 Hz
MCTRL
S16
10
P
-
VFC-ECO: Minimum voltage
20 %
MCTRL
S16
1
P
-
VFC-ECO: Cos phi actual value
- (Read only)
MCTRL
S16
100
-
t
Frequency setpoint
x.x Hz (Read only)
MCTRL
S16
10
-
t
Output frequency motor
x.x Hz (Read only)
MCTRL
S16
10
O
t
V/f torque limitation: Gain
0.00 %
MCTRL
U16
100
P
-
V/f voltage boost: Fixed boost
0.0 %
MCTRL
U8
10
P
-
V/f voltage boost: Boost at acceleration
0.0 %
MCTRL
U8
10
P
-
Additive voltage impression: Enable Function
Disable [0]
general
U8
1
P
-
Additive voltage impression: Setpoint source
Network [3]
general
U8
1
P
-
Additive voltage impression: Actual voltage
x V (Read only)
general
S16
1
-
-
Additive voltage impression: Ramp time
0.0 s
general
U16
10
P
-
Slip controller: Gain
0.100
MCTRL
U16
1000
P
-
Slip controller: Reset time
100.0 ms
MCTRL
U16
10
P
-
Slip controller: Frequency limitation
10.00 Hz
MCTRL
U16
100
P
-
SLVC: Gain
0.0000 Hz/A
MCTRL
U32
10000
P
-
SLVC: Reset time
0.0 ms
MCTRL
U32
10
P
-
SLVC: Q-Feedforward
0.00
MCTRL
U32
100
P
-
SLVC: D-Feedforward
0.00
MCTRL
U32
100
P
-
DC braking: Current
0.0 %
general
U16
10
P
-
DC braking: Automatic hold time
0.0 s
general
U16
10
P
-
DC braking: Automatic operating threshold
0.0 Hz
general
U16
10
P
-
DC braking: Demagnetization time
100 %
general
U8
1
P
-
DC braking: Default demagnetization time
x ms (Read only)
general
U16
1
-
-
DC braking: Inverter disable
Disabled [0]
general
U8
1
P
-
Flying restart circuit: Current
30 %
MCTRL
U16
1
P
-
Flying restart circuit: Start frequency
20.0 Hz
MCTRL
S16
10
P
-
Flying restart circuit: Restart time
0 ms
MCTRL
U16
1
P
-
Flying restart circuit: Flying restart frequency
x.x Hz (Read only)
MCTRL
S16
10
O
t
Motor control mode
V/f characteristic control (VFC open loop) [6]
MCTRL
U8
1
PC
-
Motor parameters: Number of pole pairs
- (Read only)
MCTRL
U8
1
-
-
Motor parameters: Stator resistance
0.0000 Ω
MCTRL
U32
10000
P
-
Motor parameters: Stator leakage inductance
0.000 mH
MCTRL
U32
1000
P
-
Motor parameters: Rated speed
1450 rpm
MCTRL
U16
1
P
-
Motor parameters: Rated frequency
50.0 Hz
MCTRL
U16
10
P
-
Motor parameters: Rated power
0.00 kW
MCTRL
U16
100
P
-
Motor parameters: Rated voltage
0 V
MCTRL
U16
1
P
-
Motor parameters: Cosine phi
0.80
MCTRL
U16
100
P
-
Motor parameters: Motor name
"Default Motor"
MCTRL
STRING[25]
P
-
Motor parameter (ASM): Rotor resistance
0.0000 Ω
MCTRL
U32
10000
P
-
Motor parameter (ASM): Mutual inductance
0.0 mH
MCTRL
U32
10
P
-
Motor parameter (ASM): Magnetising current
0.00 A
MCTRL
U16
100
P
-
Motor parameter (ASM): Slip frequency
x.x Hz (Read only)
MCTRL
U16
10
-
-
Motor parameter (PSM): Back EMF constant
41.8 V/1000rpm
MCTRL
U32
10
P
-
Motor parameter (PSM): D-axis inductance Ld
23.566 mH
MCTRL
U32
1000
P
-
Motor parameter (PSM): Q-axis inductance Lq
23.566 mH
MCTRL
U32
1000
P
-
Reference for current grid points (x) Lss saturation characteristic
5.4 A
MCTRL
U16
10
P
-
q-axis Lss saturation characteristic: y1 = L01 (x = 0.00 %)
100 %
MCTRL
U16
1
P
-
q-axis Lss saturation characteristic: y3 = L03 (x = 12.50 %)
100 %
MCTRL
U16
1
P
-
q-axis Lss saturation characteristic: y5 = L05 (x = 25.00 %)
100 %
MCTRL
U16
1
P
-
q-axis Lss saturation characteristic: y7 = L07 (x = 37.50 %)
100 %
MCTRL
U16
1
P
-
q-axis Lss saturation characteristic: y9 = L09 (x = 50.00 %)
100 %
MCTRL
U16
1
P
-
q-axis Lss saturation characteristic: y11 = L11 (x = 62.50 %)
100 %
MCTRL
U16
1
P
-
q-axis Lss saturation characteristic: y13 = L13 (x = 75.00 %)
100 %
MCTRL
U16
1
P
-
q-axis Lss saturation characteristic: y15 = L15 (x = 87.50 %)
100 %
MCTRL
U16
1
P
-
q-axis Lss saturation characteristic: y17 = L17 (x = 100.00 %)
100 %
MCTRL
U16
1
P
-
Low speed range: HF amplitude
50.0 V
MCTRL
U16
10
P
-
Low speed range: HF injection range
6.0 %
MCTRL
U16
10
P
-
High speed range: Lower limit
10 %
MCTRL
U16
1
P
-
High speed range: Stall monitoring limit
50 %
MCTRL
U16
1
P
-
SM low speed range: Acceleration current
70 %
MCTRL
U16
1
P
-
SM low speed range: Standstill current
30 %
MCTRL
U16
1
P
-
SLSM-PSM low speed method
0
MCTRL
U8
1
PC
-
Anisotropy shift: Y1 = A01 (x = 0.00 %)
0.0 °
MCTRL
S16
10
P
-
Anisotropy shift: Y2 = A02 (x = 12.50 %)
0.0 °
MCTRL
S16
10
P
-
Anisotropy shift: Y3 = A03 (x = 25.00 %)
0.0 °
MCTRL
S16
10
P
-
Anisotropy shift: Y4 = A04 (x = 37.50 %)
0.0 °
MCTRL
S16
10
P
-
Anisotropy shift: Y5 = A05 (x = 50.00 %)
0.0 °
MCTRL
S16
10
P
-
Anisotropy shift: Y6 = A06 (x = 62.50 %)
0.0 °
MCTRL
S16
10
P
-
Anisotropy shift: Y7 = A06 (x = 75.00 %)
0.0 °
MCTRL
S16
10
P
-
Anisotropy shift: Y8 = A08 (x = 87.50 %)
0.0 °
MCTRL
S16
10
P
-
Anisotropy shift: Y9 = A09 (x = 100.00 %)
0.0 °
MCTRL
S16
10
P
-
Encoder settings: Increments/revolution
128
general
U32
1
PC
-
Encoder settings: Actual velocity
x rpm (Read only)
general
S32
1
O
-
Encoder settings: Status
- (Read only)
general
U32
1
O
-
Motor feedback error response
Warning [12]
general
U8
1
P
-
Position counter: Signal source
Disabled [0]
general
U8
1
P
-
Position counter: Set position
By rising edge [0]
general
U8
1
P
-
Position counter: Actual position
- (Read only)
general
U32
1
H
t
Position counter: External position
- (Read only)
general
U32
1
H
r
Position counter: Initial position
0x00000000
general
U32
1
PH
r
Load encoder/master encoder type
HTL encoder DI3 + DI4 [13]
general
U8
1
PC
-
Load encoder/master encoder settings (encoder): Increments/revolution
128
general
U32
1
PC
-
Load encoder/master encoder settings (encoder): Actual velocity
x rpm (Read only)
general
S32
1
O
-
Load encoder/master encoder settings (encoder): Status
0
general
U32
1
-
-
PPI without movement: Execution
After each enable [2]
MCTRL
U8
1
PC
-
PPI without movement: Current adjust factor
100 %
MCTRL
U16
1
PC
-
PPI without movement: Status pole position identification
- (Read only)
general
U16
1
-
-
Device utilisation ixt: Power unit warning threshold
95 %
general
U16
1
P
-
Device utilisation ixt: Device actual utilisation
x % (Read only)
general
U16
1
O
t
Device utilisation ixt: Error response
Fault > inverter disabled [23]
general
U8
1
P
-
Overspeed monitoring: Threshold
8000 rpm
MCTRL
U16
1
P
-
Overspeed monitoring: Response
Fault > inverter disabled [23]
general
U8
1
P
-
Motor phase failure detection: Response - Motor phase 1
No response [0]
general
U8
1
P
-
Motor phase failure detection: Current threshold
5.0 %
MCTRL
U8
10
P
-
Motor phase failure detection: Voltage threshold
10.0 V
MCTRL
U16
10
P
-
Overcurrent monitoring: Threshold
0.0 A
MCTRL
U16
10
P
-
Overcurrent monitoring: Response
Fault > inverter disabled [23]
general
U8
1
P
-
Motor temperature monitoring: Response
Fault > inverter disabled [23]
general
U8
1
P
-
Motor overload monitoring (i²xt): Maximum utilisation [60 s]
150 %
MCTRL
U16
1
P
-
Motor overload monitoring (i²xt): Speed compensation
On [0]
MCTRL
U8
1
P
-
Motor overload monitoring (i²xt): Response
Fault > inverter disabled [23]
general
U8
1
P
-
Motor overload monitoring (i²xt): Thermal load
- (Read only)
MCTRL
U16
1
-
-
Motor utilisation (i²xt)
x % (Read only)
MCTRL
U16
1
O
t
Maximum torque monitoring: Response
No response [0]
general
U8
1
P
-
Maximum torque monitoring: Triggering delay
0.000 s
MCTRL
U16
1000
P
-
Life-diagnosis: Operating time
x s (Read only)
general
U32
1
-
-
Life-diagnosis: Power-on time
x s (Read only)
general
U32
1
-
-
Life-diagnosis: Control unit operating time
x ns (Read only)
general
U64
1
-
-
Life-diagnosis: Main switching cycles
- (Read only)
general
U32
1
-
-
Life-diagnosis: Short-circuit counter
- (Read only)
general
U32
1
-
-
Life-diagnosis: Earth fault counter
- (Read only)
general
U32
1
-
-
Life-diagnosis: Clamp active
- (Read only)
general
U32
1
-
-
Life-diagnosis: Fan operating time
x s (Read only)
general
U32
1
-
-
Motor actual voltage (Veff)
x.x V (Read only)
MCTRL
U32
10
O
t
Motor-Phasenströme: Phase U current
x.xx A (Read only)
MCTRL
S32
100
O
t
Motor-Phasenströme: Phase V current
x.xx A (Read only)
MCTRL
S32
100
O
t
Motor-Phasenströme: Phase W current
x.xx A (Read only)
MCTRL
S32
100
O
t
Heatsink temperature: Heatsink temperature
x.x °C (Read only)
general
S16
10
O
t
Heatsink temperature: Warning threshold
0.0 °C
general
S16
10
P
-
Heatsink temperature: Fan on threshold
0.0 °C
general
S16
10
P
-
Heatsink temperature: Fan off threshold
0.0 °C
general
S16
10
P
-
DC-bus voltage
x V (Read only)
MCTRL
U16
1
O
t
Motor current
x.x A (Read only)
MCTRL
S16
10
O
t
Motor voltage
x VAC (Read only)
MCTRL
U16
1
-
t
Output power: Effective power
x.xxx kW (Read only)
MCTRL
S32
1000
O
t
Output power: Apparent power
x.xxx kVA (Read only)
MCTRL
S32
1000
O
t
Output energy: Motor
x.xx kWh (Read only)
MCTRL
S32
100
O
t
Output energy: Generator
x.xx kWh (Read only)
MCTRL
S32
100
O
t
Diagnostics of analog input 1: Value in percent
x.x % (Read only)
general
S16
10
O
t
Diagnostics of analog input 1: Frequency value
x.x Hz (Read only)
general
S16
10
O
t
Diagnostics of analog input 1: Process controller value
x.xx PID unit (Read only)
general
S16
100
O
t
Diagnostics of analog input 1: Torque value
x.x % (Read only)
general
S16
10
O
t
Diagnostics of analog input 1: Status
- (Read only)
general
U16
1
O
-
Diagnostics of analog input 2: Value in percent
x.x % (Read only)
general
S16
10
O
t
Diagnostics of analog input 2: Frequency value
x.x Hz (Read only)
general
S16
10
O
t
Diagnostics of analog input 2: Process controller value
x.xx PID unit (Read only)
general
S16
100
O
t
Diagnostics of analog input 2: Torque value
x.x % (Read only)
general
S16
10
O
t
Diagnostics of analog input 2: Status
- (Read only)
general
U16
1
O
-
Diagnostics of analog output 1: Voltage
x.xx V (Read only)
general
U16
100
O
t
Diagnostics of analog output 1: Current
x.xx mA (Read only)
general
U16
100
O
t
Motor currents: Actual D-current (id)
x.xx A (Read only)
MCTRL
S32
100
O
t
Motor currents: Actual Q-current (iq)
x.xx A (Read only)
MCTRL
S32
100
O
t
Motor currents: Setpoint D-current (id)
x.xx A (Read only)
MCTRL
S32
100
O
t
Motor currents: Setpoint Q-current (iq)
x.xx A (Read only)
MCTRL
S32
100
O
t
Motor currents: Motor current (Ieff)
x.xx A (Read only)
MCTRL
S32
100
O
t
Speed setpoints: Speed setpoint
x rpm (Read only)
MCTRL
S32
1
-
t
Speed setpoints: Speed setpoint limited
x rpm (Read only)
MCTRL
S32
1
-
t
Speed controller output signals: Output signal 1
x.x % (Read only)
MCTRL
S16
10
-
-
Speed controller output signals: Output signal 2
x.x % (Read only)
MCTRL
S16
10
-
t
Torque setpoint
x.xx Nm (Read only)
MCTRL
S32
100
-
t
Actual slip value
x.x Hz (Read only)
MCTRL
S16
10
-
t
Output frequency
x.x Hz (Read only)
MCTRL
S16
10
O
t
Axis information: Rated current
x.xx A (Read only)
MCTRL
U16
100
O
t
Axis information: Maximum current
x.xx A (Read only)
MCTRL
U16
100
O
t
Service settings: Motor control behavior
8
MCTRL
U16
1
PC
-
Service settings: Limitation of output voltage
Default setting [0]
MCTRL
U8
1
P
-
MOP starting mode
Last value [0]
general
U8
1
P
-
MOP starting values: Frequency
0.0 Hz
general
U16
10
P
-
MOP starting values: PID value
0.00 PID unit
general
S16
100
P
-
MOP starting values: Torque
0.0 %
general
U16
10
P
-
Frequency threshold
0.0 Hz
MCTRL
U16
10
P
-
Load loss detection: Threshold
0.0 %
MCTRL
U16
10
P
-
Load loss detection: Delay time
0.0 s
MCTRL
U16
10
P
-
Load loss detection: Error response
No response [0]
general
U8
1
P
-
Heavy load monitoring: Error threshold
200.0 %
MCTRL
U16
10
P
-
Heavy load monitoring: Delay time
3.0 s
MCTRL
U16
10
P
-
Heavy load monitoring: Error response
No response [0]
general
U8
1
P
-
Process input words: NetWordIN1
0x0000
general
U16
1
HK
r
Process input words: NetWordIN2
0x0000
general
U16
1
HK
r
Process input words: NetWordIN3
0.0 %
general
U16
10
K
r
Process input words: NetWordIN4
0.0 %
general
U16
10
K
r
Process input words: NetWordIN5
0.0 %
general
S16
10
OK
r
MOP values saved: Frequency
x.x Hz (Read only)
general
U16
10
-
t
MOP values saved: PID value
x.xx PID unit (Read only)
general
S16
100
-
t
MOP values saved: Torque
x.x % (Read only)
general
U16
10
-
t
Process output words: NetWordOUT1
- (Read only)
general
U16
1
OH
t
Process input data: AC Drive control word
0
general
U16
1
-
r
Process input data: Network setpoint frequency (0.1)
0.0 Hz
general
U16
10
OK
r
Process input data: Network setpoint speed
0 rpm
general
U16
1
OK
r
Process input data: Network setpoint frequency (0.01)
0.00 Hz
general
U16
100
O
r
Process input data: Velocity mode setpoint
0.0 Hz
general
S16
10
OK
r
Process input data: PID setpoint
0.00 PID unit
general
S16
100
OK
r
Process input data: Torque mode setpoint
0 Nm
general
S16
1
OK
r
Process input data: Torque scaling
0
general
S8
1
OK
-
Process input data: AC Drive mode
- (Read only)
EtherNet/IP
U8
1
OK
-
Process input data: PID feedback
0.00 PID unit
general
S16
100
OK
r
Process input data: Network frequency setpoint [+/-16384]
0
general
S16
1
O
r
Process output data: AC Drive status word
- (Read only)
general
U16
1
-
t
Process output data: Frequency (0.1)
x.x Hz (Read only)
MCTRL
U16
10
-
t
Process output data: Motor speed
x rpm (Read only)
MCTRL
U16
1
-
t
Process output data: Drive status
- (Read only)
general
U16
1
-
t
Process output data: Frequency (0.01)
x.xx Hz (Read only)
MCTRL
U16
100
-
t
Process output data: Torque scaled
- (Read only)
general
S16
1
-
t
Process output data: Frequency [+/-16384]
- (Read only)
general
S16
1
-
t
NetWordIN1 function: Bit 0
Not active [0]
general
U8
1
PC
-
NetWordIN1 function: Bit 1
Not active [0]
general
U8
1
PC
-
NetWordIN1 function: Bit 2
Activate quick stop [3]
general
U8
1
PC
-
NetWordIN1 function: Bit 3
Not active [0]
general
U8
1
PC
-
NetWordIN1 function: Bit 4
Run forward (CW) [8]
general
U8
1
PC
-
NetWordIN1 function: Bit 5
Activate preset (bit 0) [18]
general
U8
1
PC
-
NetWordIN1 function: Bit 6
Activate preset (bit 1) [19]
general
U8
1
PC
-
NetWordIN1 function: Bit 7
Reset error [4]
general
U8
1
PC
-
NetWordIN1 function: Bit 8
Not active [0]
general
U8
1
PC
-
NetWordIN1 function: Bit 9
Activate DC braking [5]
general
U8
1
PC
-
NetWordIN1 function: Bit 10
Not active [0]
general
U8
1
PC
-
NetWordIN1 function: Bit 11
Not active [0]
general
U8
1
PC
-
NetWordIN1 function: Bit 12
Reverse rotational direction [13]
general
U8
1
PC
-
NetWordIN1 function: Bit 13
Not active [0]
general
U8
1
PC
-
NetWordIN1 function: Bit 14
Not active [0]
general
U8
1
PC
-
NetWordIN1 function: Bit 15
Not active [0]
general
U8
1
PC
-
Digital input status: Level of digital input 1
- (Read only)
general
U8
1
X
-
Digital input status: Level of digital input 2
- (Read only)
general
U8
1
X
-
Digital input status: Level of digital input 3
- (Read only)
general
U8
1
X
-
Digital input status: Level of digital input 4
- (Read only)
general
U8
1
X
-
Digital input status: Level of digital input 5
- (Read only)
general
U8
1
X
-
Digital input status: Level of digital input 6
- (Read only)
general
U8
1
X
-
Digital input status: Level of digital input 7
- (Read only)
general
U8
1
X
-
Digital input status: Level of digital input 8
- (Read only)
general
U8
1
X
-
Digital input status: Level from digital input 1
- (Read only)
general
U8
1
X
-
Digital input status: Level from digital input 2
- (Read only)
general
U8
1
X
-
Digital input status: Level from digital input 3
- (Read only)
general
U8
1
X
-
Digital input status: Level from digital input 4
- (Read only)
general
U8
1
X
-
Digital input status: Level from digital input 5
- (Read only)
general
U8
1
X
-
Digital input status: Level from digital input 6
- (Read only)
general
U8
1
X
-
Digital input status: Level from digital input 7
- (Read only)
general
U8
1
X
-
Digital input status: Level from digital input 8
- (Read only)
general
U8
1
X
-
Digital output configuration: DO1 switch-off delay
0.000 s
general
U16
1000
P
-
Digital output configuration: DO1 switch-on delay
0.000 s
general
U16
1000
P
-
Digital output configuration: DO1 terminal state
- (Read only)
general
U8
1
X
-
Digital output configuration: DO1 trigger signal state
- (Read only)
general
U8
1
X
-
Digital output configuration: DO2 switch-off delay
0.000 s
general
U16
1000
P
-
Digital output configuration: DO2 switch-on delay
0.000 s
general
U16
1000
P
-
Digital output configuration: DO2 terminal state
- (Read only)
general
U8
1
X
-
Digital output configuration: DO2 trigger signal state
- (Read only)
general
U8
1
X
-
Digital output configuration: DO3 switch-off delay
0.000 s
general
U16
1000
P
-
Digital output configuration: DO3 switch-on delay
0.000 s
general
U16
1000
P
-
Digital output configuration: DO3 terminal state
- (Read only)
general
U8
1
X
-
Digital output configuration: DO3 trigger signal state
- (Read only)
general
U8
1
X
-
Digital output configuration: DO4 switch-off delay
0.000 s
general
U16
1000
P
-
Digital output configuration: DO4 switch-on delay
0.000 s
general
U16
1000
P
-
Digital output configuration: DO4 terminal state
- (Read only)
general
U8
1
X
-
Digital output configuration: DO4 trigger signal state
- (Read only)
general
U8
1
X
-
IO-Link: Encoder position value
0
general
S32
1
-
r
Process controller diagnostics: Current setpoint
x.xx PID unit (Read only)
general
S16
100
O
t
Process controller diagnostics: Current process variable
x.xx PID unit (Read only)
general
S16
100
O
t
Process controller diagnostics: Status
- (Read only)
general
U8
1
O
t
Process controller diagnostics: PID control value
x.x Hz (Read only)
general
S16
10
-
-
Process controller diagnostics: PID Feedforward value
x.x Hz (Read only)
general
S16
10
-
-
Process controller diagnostics: PID output value
x.x Hz (Read only)
general
S16
10
-
-
Process controller diagnostics: PID error value
x.xx PID unit (Read only)
general
S32
100
-
-
Process controller setup (PID): Operating mode
Inhibited [0]
general
U8
1
P
-
Process controller setup (PID): PID process variable
Network [5]
general
U8
1
P
-
Process controller setup (PID): Closed-loop controlled speed range
100 %
general
U16
1
P
rt
Process controller setup (PID): Speed feedforward control source
Without speed addition [0]
general
U8
1
P
-
Process controller setup (PID): Min speed limit
-100.0 %
general
S16
10
P
-
Process controller setup (PID): Max speed limit
100.0 %
general
S16
10
P
-
PID speed operation: Acceleration time
1.0 s
general
U16
10
P
-
PID speed operation: Deceleration time
1.0 s
general
U16
10
P
-
PID setpoint presets: Preset 1
0.00 PID unit
general
S16
100
P
-
PID setpoint presets: Preset 2
0.00 PID unit
general
S16
100
P
-
PID setpoint presets: Preset 3
0.00 PID unit
general
S16
100
P
-
PID setpoint presets: Preset 4
0.00 PID unit
general
S16
100
P
-
PID setpoint presets: Preset 5
0.00 PID unit
general
S16
100
P
-
PID setpoint presets: Preset 6
0.00 PID unit
general
S16
100
P
-
PID setpoint presets: Preset 7
0.00 PID unit
general
S16
100
P
-
PID setpoint presets: Preset 8
0.00 PID unit
general
S16
100
P
-
PID sleep mode: Activation
Disabled [0]
general
U8
1
P
-
PID sleep mode: Stop method
Coasting [0]
general
U8
1
P
-
PID sleep mode: Frequency threshold
0.0 Hz
general
U16
10
P
-
PID sleep mode: Feedback threshold
0.00 PID unit
general
S16
100
P
-
PID sleep mode: Delay time
0.0 s
general
U16
10
P
-
PID sleep mode: Recovery
Setpoint > threshold OR system deviation > bandwidth [0]
general
U8
1
P
-
PID sleep mode: Bandwidth
0.00 PID unit
general
U16
100
P
-
PID sleep mode: Recovery threshold
0.00 PID unit
general
S16
100
P
-
Automatic rinsing: Rinsing in sleep mode
Inhibited [0]
general
U8
1
P
-
Automatic rinsing: Rinse interval
30.0 min
general
U16
10
P
-
Automatic rinsing: Rinse speed
0.0 Hz
general
S16
10
P
-
Automatic rinsing: Rinse period
0.0 s
general
U16
10
P
-
Parameter change-over: Parameter 1 ... Parameter 32
0
general
IDX
PH
-
Parameter value set 1: Value of parameter 1 ... Value of parameter 32
0
general
S32
1
P
-
Parameter value set 2: Value of parameter 1 ... Value of parameter 32
0
general
S32
1
P
-
Parameter value set 3: Value of parameter 1 ... Value of parameter 32
0
general
S32
1
P
-
Parameter value set 4: Value of parameter 1 ... Value of parameter 32
0
general
S32
1
P
-
Activation of parameter set
Via command (disable required) [0]
general
U8
1
P
-
Parameter change-over error message: Status
- (Read only)
general
U16
1
-
-
Parameter change-over error message: List entry
- (Read only)
general
U8
1
X
-
PID P-component
5.0 %
general
U16
10
P
rt
PID I- component
400 ms
general
U16
1
P
rt
PID D-component
0.0 s
general
U8
10
P
rt
PID setpoint ramp
20.0 s
general
U16
10
P
-
PID influence: Acceleration time for activation
5.0 s
general
U16
10
P
-
PID influence: Deceleration time for masking out
5.0 s
general
U16
10
P
-
PID influence: PID influence factor
100.0 %
general
S16
10
P
r
PID alarms: MIN alarm threshold
0.00 PID unit
general
S16
100
P
-
PID alarms: MAX alarm threshold
100.00 PID unit
general
S16
100
P
-
PID alarms: Monitoring bandwidth PID feedback signal
2.00 PID unit
general
U16
100
P
-
PID setpoint limits: Minimum setpoint
-300.00 PID unit
general
S16
100
P
-
PID setpoint limits: Maximum setpoint
300.00 PID unit
general
S16
100
P
-
TA axis parameter: Status word
- (Read only)
general
U32
1
O
-
TA axis parameter: Actual position
x.xxxx Unit (Read only)
general
S32
10000
O
t
TA axis parameter: Actual velocity
x.xxxx unit/s (Read only)
general
S32
10000
O
t
TA axis parameter: Actual acceleration
x.xx unit/s² (Read only)
general
S32
100
O
t
TA axis parameter: Position setpoint
x.xxxx Unit (Read only)
general
S32
10000
-
-
TA axis parameter: Velocity setpoint
x.xxxx unit/s (Read only)
general
S32
10000
-
-
TA axis parameter: Acceleration setpoint
x.xx unit/s² (Read only)
general
S32
100
-
-
TA axis parameter: Motion kind
not defined [0]
general
U16
1
PC
-
TA axis parameter: Virtual mode
Inactive [0]
general
U8
1
PC
-
TA axis parameter: Travel range
Limited [1]
general
U16
1
PC
-
TA axis parameter: Cycle length
360.0000 Unit
general
S32
10000
PC
-
TA axis parameter: Feed constant
360.0000
general
S32
10000
PC
-
TA axis parameter: Gearbox factor - nominator
1
general
U32
1
PC
-
TA axis parameter: Gearbox factor - denominator
1
general
U32
1
PC
-
TA axis parameter: Max. velocity
0.0000 unit/s
general
S32
10000
P
-
TA axis parameter: Max. acceleration
0.00 unit/s²
general
S32
100
P
-
TA axis parameter: Max. jerk
0.00 unit/s³
general
S32
100
P
-
TA axis parameter: Enable software position limits
Inactive [0]
general
U8
1
P
-
TA axis parameter: Software position limit positive
0.0000 Unit
general
S32
10000
P
-
TA axis parameter: Software position limit negative
0.0000 Unit
general
S32
10000
P
-
TA axis parameter: Following error monitoring
Active [1]
general
U8
1
P
-
TA axis parameter: Following error: Warning threshold
180.0000 Unit
general
S32
10000
P
-
TA axis parameter: Following error: Error threshold
360.0000 Unit
general
S32
10000
P
-
TA axis parameter: Actual following error
x.xxxx Unit (Read only)
general
S32
10000
O
t
TA axis parameter: Maximum following error
x.xxxx Unit (Read only)
general
S32
10000
O
-
TA axis parameter: Response to following error
Warning [12]
general
U8
1
P
-
TA axis parameter: Homing mode
SetPositionDirect [0]
general
S16
1
P
-
TA axis parameter: Action after "Home position detected"
Stop positioning [0]
general
S16
1
P
-
TA axis parameter: Homing: Target position
0.0000 Unit
general
S32
10000
P
-
TA axis parameter: Homing: Velocity 1
360.0000 unit/s
general
S32
10000
P
-
TA axis parameter: Homing: Velocity 2
0.0000 unit/s
general
S32
10000
P
-
TA axis parameter: Homing: Acceleration 1
720.00 unit/s²
general
S32
100
P
-
TA axis parameter: Homing: Acceleration 2
360.00 unit/s²
general
S32
100
P
-
TA axis parameter: Homing: Jerk
7200.00 unit/s³
general
S32
100
P
-
TA axis parameter: Homing: Torque limit
0.10 Nm
general
S32
100
P
-
TA axis parameter: Homing: Blocking time
1.000 s
general
S32
1000
P
-
TA axis parameter: Homing: Touch probe configuration
TP1 - positive edge [1]
general
U16
1
P
-
TA axis parameter: Home position
0.0000 Unit
general
S32
10000
P
-
TA axis parameter: Default control mode
Position control via motor encoder [0]
general
U16
1
PC
-
TA axis parameter: Response to hardware limit switch error
Warning [12]
general
U8
1
P
-
TA axis parameter: Response to software position limit error
Warning [12]
general
U8
1
P
-
TA axis parameter: Response to error "max. values exceeded"
Warning [12]
general
U8
1
P
-
TA axis parameter: Position window size
0.0000 Unit
general
S32
10000
P
-
TA axis parameter: Position window dwell time
0.000 s
general
S32
1000
P
-
TA axis parameter: Modulo positioning tolerance window
0.0000 Unit
general
S32
10000
P
-
TA axis parameter: Tolerance window actual position=set position upper limit
0.0000 Unit
general
S32
10000
P
-
TA axis parameter: Tolerance window actual position=set position lower limit
0.0000 Unit
general
S32
10000
P
-
TA axis parameter: Manual jog velocity
360.0000 unit/s
general
S32
10000
P
-
TA axis parameter: Manual jog acceleration
720.00 unit/s²
general
S32
100
P
-
TA axis parameter: Manual jog deceleration
720.00 unit/s²
general
S32
100
P
-
TA axis parameter: Manual jog jerk
7200.00 unit/s³
general
S32
100
P
-
TA axis parameter: Deceleration of Halt
720.00 unit/s²
general
S32
100
P
-
TA axis parameter: Jerk of Halt
7200.00 unit/s³
general
S32
100
P
-
Load encoder: Gearbox factor - nominator
1
general
U32
1
PC
-
Load encoder: Gearbox factor - denominator
1
general
U32
1
PC
-
Load encoder: Load encoder mounting direction
CW [0]
general
U16
1
PC
-
Load encoder: Homepos available for absolute encoder
Default behaviour [0]
general
U8
1
P
-
Load encoder: Homing: Offset Position (for Mode 98 or Sub 85)
0.0000 Unit
general
S32
10000
P
-
Interface selection: TP1 source
Digital input 2, positive edge [11]
general
U16
1
-
-
Table Positioning: Simulation of control signals
0
general
U8
1
O
-
Table Positioning: Activate flying homing
FALSE [0]
general
U16
1
OP
-
Table Positioning: Activate "Stop positioning"
FALSE [0]
general
U16
1
OP
-
Table Positioning: Control signals
0
general
U32
1
O
r
Table Positioning: External velocity override
0.00 %
general
S32
100
-
r
Table Positioning: External velocity
0.0000 unit/s
general
S32
10000
-
r
Table Positioning: External acceleration
0.00 unit/s²
general
S32
100
-
r
Table Positioning: External deceleration
0.00 unit/s²
general
S32
100
-
r
Table Positioning: External jerk
0.00 unit/s³
general
U32
100
-
r
Table Positioning: External set position
0.0000 Unit
general
S32
10000
-
r
Table Positioning: Simulation of status signals
0x00
general
U8
1
OH
-
Table Positioning: Status signals
0
general
U32
1
O
t
Table Positioning: Interface dialog
- (Read only)
general
U8
1
-
-
Table Positioning: Signal flow dialog
- (Read only)
general
U8
1
-
-
Settings profile parameters: Positioning mode [1]
absolute [0]
general
S16
1
OP
-
Settings profile parameters: Target position [1]
0.0000 Unit
general
S32
10000
P
-
Settings profile parameters: Profile velocity [1]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Profile acceleration [1]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile deceleration [1]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile jerk [1]
1000.00 unit/s³
general
S32
100
P
-
Settings profile parameters: Final velocity [1]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Sequence profile after touch probe [1]
0
general
U16
1
OP
-
Settings profile parameters: Sequence profile [1]
0
general
U16
1
OP
-
Settings profile parameters: Positioning mode [2]
absolute [0]
general
S16
1
OP
-
Settings profile parameters: Target position [2]
0.0000 Unit
general
S32
10000
P
-
Settings profile parameters: Profile velocity [2]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Profile acceleration [2]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile deceleration [2]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile jerk [2]
1000.00 unit/s³
general
S32
100
P
-
Settings profile parameters: Final velocity [2]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Sequence profile after touch probe [2]
0
general
U16
1
OP
-
Settings profile parameters: Sequence profile [2]
0
general
U16
1
OP
-
Settings profile parameters: Positioning mode [3]
absolute [0]
general
S16
1
OP
-
Settings profile parameters: Target position [3]
0.0000 Unit
general
S32
10000
P
-
Settings profile parameters: Profile velocity [3]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Profile acceleration [3]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile deceleration [3]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile jerk [3]
1000.00 unit/s³
general
S32
100
P
-
Settings profile parameters: Final velocity [3]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Sequence profile after touch probe [3]
0
general
U16
1
OP
-
Settings profile parameters: Sequence profile [3]
0
general
U16
1
OP
-
Settings profile parameters: Positioning mode [4]
absolute [0]
general
S16
1
OP
-
Settings profile parameters: Target position [4]
0.0000 Unit
general
S32
10000
P
-
Settings profile parameters: Profile velocity [4]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Profile acceleration [4]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile deceleration [4]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile jerk [4]
1000.00 unit/s³
general
S32
100
P
-
Settings profile parameters: Final velocity [4]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Sequence profile after touch probe [4]
0
general
U16
1
OP
-
Settings profile parameters: Sequence profile [4]
0
general
U16
1
OP
-
Settings profile parameters: Positioning mode [5]
absolute [0]
general
S16
1
OP
-
Settings profile parameters: Target position [5]
0.0000 Unit
general
S32
10000
P
-
Settings profile parameters: Profile velocity [5]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Profile acceleration [5]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile deceleration [5]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile jerk [5]
1000.00 unit/s³
general
S32
100
P
-
Settings profile parameters: Final velocity [5]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Sequence profile after touch probe [5]
0
general
U16
1
OP
-
Settings profile parameters: Sequence profile [5]
0
general
U16
1
OP
-
Settings profile parameters: Positioning mode [6]
absolute [0]
general
S16
1
OP
-
Settings profile parameters: Target position [6]
0.0000 Unit
general
S32
10000
P
-
Settings profile parameters: Profile velocity [6]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Profile acceleration [6]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile deceleration [6]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile jerk [6]
1000.00 unit/s³
general
S32
100
P
-
Settings profile parameters: Final velocity [6]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Sequence profile after touch probe [6]
0
general
U16
1
OP
-
Settings profile parameters: Sequence profile [6]
0
general
U16
1
OP
-
Settings profile parameters: Positioning mode [7]
absolute [0]
general
S16
1
OP
-
Settings profile parameters: Target position [7]
0.0000 Unit
general
S32
10000
P
-
Settings profile parameters: Profile velocity [7]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Profile acceleration [7]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile deceleration [7]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile jerk [7]
1000.00 unit/s³
general
S32
100
P
-
Settings profile parameters: Final velocity [7]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Sequence profile after touch probe [7]
0
general
U16
1
OP
-
Settings profile parameters: Sequence profile [7]
0
general
U16
1
OP
-
Settings profile parameters: Positioning mode [8]
absolute [0]
general
S16
1
OP
-
Settings profile parameters: Target position [8]
0.0000 Unit
general
S32
10000
P
-
Settings profile parameters: Profile velocity [8]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Profile acceleration [8]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile deceleration [8]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile jerk [8]
1000.00 unit/s³
general
S32
100
P
-
Settings profile parameters: Final velocity [8]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Sequence profile after touch probe [8]
0
general
U16
1
OP
-
Settings profile parameters: Sequence profile [8]
0
general
U16
1
OP
-
Settings profile parameters: Positioning mode [9]
absolute [0]
general
S16
1
OP
-
Settings profile parameters: Target position [9]
0.0000 Unit
general
S32
10000
P
-
Settings profile parameters: Profile velocity [9]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Profile acceleration [9]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile deceleration [9]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile jerk [9]
1000.00 unit/s³
general
S32
100
P
-
Settings profile parameters: Final velocity [9]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Sequence profile after touch probe [9]
0
general
U16
1
OP
-
Settings profile parameters: Sequence profile [9]
0
general
U16
1
OP
-
Settings profile parameters: Positioning mode [10]
absolute [0]
general
S16
1
OP
-
Settings profile parameters: Target position [10]
0.0000 Unit
general
S32
10000
P
-
Settings profile parameters: Profile velocity [10]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Profile acceleration [10]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile deceleration [10]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile jerk [10]
1000.00 unit/s³
general
S32
100
P
-
Settings profile parameters: Final velocity [10]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Sequence profile after touch probe [10]
0
general
U16
1
OP
-
Settings profile parameters: Sequence profile [10]
0
general
U16
1
OP
-
Settings profile parameters: Positioning mode [11]
absolute [0]
general
S16
1
OP
-
Settings profile parameters: Target position [11]
0.0000 Unit
general
S32
10000
P
-
Settings profile parameters: Profile velocity [11]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Profile acceleration [11]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile deceleration [11]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile jerk [11]
1000.00 unit/s³
general
S32
100
P
-
Settings profile parameters: Final velocity [11]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Sequence profile after touch probe [11]
0
general
U16
1
OP
-
Settings profile parameters: Sequence profile [11]
0
general
U16
1
OP
-
Settings profile parameters: Positioning mode [12]
absolute [0]
general
S16
1
OP
-
Settings profile parameters: Target position [12]
0.0000 Unit
general
S32
10000
P
-
Settings profile parameters: Profile velocity [12]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Profile acceleration [12]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile deceleration [12]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile jerk [12]
1000.00 unit/s³
general
S32
100
P
-
Settings profile parameters: Final velocity [12]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Sequence profile after touch probe [12]
0
general
U16
1
OP
-
Settings profile parameters: Sequence profile [12]
0
general
U16
1
OP
-
Settings profile parameters: Positioning mode [13]
absolute [0]
general
S16
1
OP
-
Settings profile parameters: Target position [13]
0.0000 Unit
general
S32
10000
P
-
Settings profile parameters: Profile velocity [13]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Profile acceleration [13]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile deceleration [13]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile jerk [13]
1000.00 unit/s³
general
S32
100
P
-
Settings profile parameters: Final velocity [13]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Sequence profile after touch probe [13]
0
general
U16
1
OP
-
Settings profile parameters: Sequence profile [13]
0
general
U16
1
OP
-
Settings profile parameters: Positioning mode [14]
absolute [0]
general
S16
1
OP
-
Settings profile parameters: Target position [14]
0.0000 Unit
general
S32
10000
P
-
Settings profile parameters: Profile velocity [14]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Profile acceleration [14]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile deceleration [14]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile jerk [14]
1000.00 unit/s³
general
S32
100
P
-
Settings profile parameters: Final velocity [14]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Sequence profile after touch probe [14]
0
general
U16
1
OP
-
Settings profile parameters: Sequence profile [14]
0
general
U16
1
OP
-
Settings profile parameters: Positioning mode [15]
absolute [0]
general
S16
1
OP
-
Settings profile parameters: Target position [15]
0.0000 Unit
general
S32
10000
P
-
Settings profile parameters: Profile velocity [15]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Profile acceleration [15]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile deceleration [15]
1.00 unit/s²
general
S32
100
P
-
Settings profile parameters: Profile jerk [15]
1000.00 unit/s³
general
S32
100
P
-
Settings profile parameters: Final velocity [15]
0.0000 unit/s
general
S32
10000
P
-
Settings profile parameters: Sequence profile after touch probe [15]
0
general
U16
1
OP
-
Settings profile parameters: Sequence profile [15]
0
general
U16
1
OP
-
Diagnostic profile parameters: Active Profile
- (Read only)
general
U16
1
O
-
Diagnostic profile parameters: Acceleration
x.xx unit/s² (Read only)
general
S32
100
O
-
Diagnostic profile parameters: Deceleration setpoint
x.xx unit/s² (Read only)
general
S32
100
O
-
Diagnostic profile parameters: Jerk
x.xx unit/s³ (Read only)
general
S32
100
O
-
Diagnostic profile parameters: Velocity
x.xxxx unit/s (Read only)
general
S32
10000
O
-
Diagnostic profile parameters: Position
x.xxxx Unit (Read only)
general
S32
10000
O
-
Diagnostic profile parameters: Selected profile
- (Read only)
general
U16
1
O
-
Diagnostic profile parameters: Velocity override
x.xx % (Read only)
general
S32
100
O
-
Application diagnostics: Application state
- (Read only)
general
U8
1
-
-
Application diagnostics: Processor workload
x.xx % (Read only)
general
U16
100
-
-
Configuration PLC application: Output data at stopped Logic PLC
Clear data [1]
general
U8
1
PC
-
Configuration PLC application: Error response on exception
Fault > inverter disabled [23]
general
U8
1
P
-
0x5905:001
User management - Configuration: User management - Login
"0"
general
STRING[200]
PW
-
0x5905:002
User management - Configuration: Status word
- (Read only)
general
U8
1
-
-
0x5905:003
User management - Configuration: User rights - status
- (Read only)
general
U32
1
-
-
0x5905:004
User management - Configuration: Access right
- (Read only)
general
STRING[32]
-
-
0x5905:010
User management - Configuration: Device security status
- (Read only)
general
U32
1
-
-
0x5905:011
User management - Configuration: Activate security level
Off / ready [0]
general
U8
1
-
-
0x5905:012
User management - Configuration: Selection of security level
No selection [0]
general
U8
1
-
-
0x5905:021
User management - Configuration: User management - activation
Off / Ready [0]
general
U8
1
-
-
0x5905:022
User management - Configuration: User management - selection
No selection [0]
general
U8
1
-
-
Error code
- (Read only)
general
U16
1
O
t
CiA control word
0
general
U16
1
O
r
CiA status word
- (Read only)
general
U16
1
O
t
Set speed
0 rpm
general
S16
1
O
r
Internal set speed
x rpm (Read only)
general
S16
1
-
t
Actual speed
x rpm (Read only)
MCTRL
S16
1
O
t
Speed limits: Min. speed
0 rpm
general
U32
1
OP
r
Speed limits: Max. speed
2147483647 rpm
general
U32
1
OP
r
Acceleration ramp: CiA acceleration: Delta speed
3000 rpm
general
U32
1
OP
r
Acceleration ramp: CiA acceleration: Delta time
10 s
general
U16
1
OP
r
Deceleration ramp: CiA deceleration: Delta speed
3000 rpm
general
U32
1
OP
r
Deceleration ramp: CiA deceleration: Delta time
10 s
general
U16
1
OP
r
CiA: Quick stop mode
Ramp > switch on disabled [2]
general
S16
1
P
-
Shutdown option code
Disable drive function [0]
general
S16
1
P
-
CiA: Operation mode
MS: Velocity mode [-2]
general
S8
1
OPC
r
CiA: Active operation mode
- (Read only)
general
S8
1
-
t
Set torque
0.0 %
general
S16
10
O
r
Max. torque
250.0 %
general
U16
10
OP
r
Max. current
200.0 %
MCTRL
U16
10
P
r
Internal set torque
x.x % (Read only)
MCTRL
S16
10
O
-
Rated motor current
0.000 A
MCTRL
U32
1000
PC
-
Rated motor torque
0.000 Nm
MCTRL
U32
1000
PC
-
Actual torque
x.x % (Read only)
MCTRL
S16
10
O
t
Actual current
x.x % (Read only)
MCTRL
S16
10
O
t
DC-bus voltage
x.xxx V (Read only)
MCTRL
U32
1000
O
t
Max. motor speed
6075 rpm
MCTRL
U32
1
P
r
Quick stop deceleration
546000 inc/s²
general
U32
1
P
-
Positive torque limit
250.0 %
general
U16
10
P
r
Negative torque limit
250.0 %
general
U16
10
P
r
Digital input status
- (Read only)
general
U32
1
O
t
Motor type
Asynchronous motor [7]
EtherNet/IP
U16
1
P
-
FSoE Slave Frame Elements: Command
- (Read only)
U8
1
-
-
FSoE Slave Frame Elements: Connection ID
- (Read only)
U16
1
-
-
FSoE Slave Frame Elements: CRC_0
- (Read only)
U16
1
-
-
FSoE Slave Frame Elements: CRC_1
- (Read only)
U16
1
-
-
FSoE Slave Frame Elements: CRC_2
- (Read only)
U16
1
-
-
FSoE Slave Frame Elements: CRC_3
- (Read only)
U16
1
-
-
FSoE Slave Frame Elements: CRC_4
- (Read only)
U16
1
-
-
FSoE Master Frame Elements: Command
- (Read only)
U8
1
-
-
FSoE Master Frame Elements: Connection ID
- (Read only)
U16
1
-
-
FSoE Master Frame Elements: CRC_0
- (Read only)
U16
1
-
-
FSoE Master Frame Elements: CRC_1
- (Read only)
U16
1
-
-
FSoE Master Frame Elements: CRC_2
- (Read only)
U16
1
-
-
FSoE Connection Communication Parameter: Version
- (Read only)
STRING[30]
1
-
-
FSoE Connection Communication Parameter: Safety address
- (Read only)
U16
1
-
-
FSoE Connection Communication Parameter: Connection ID
- (Read only)
U16
1
-
-
FSoE Connection Communication Parameter: Watchdog Time
- (Read only)
U16
1
-
-
FSoE Connection Communication Parameter: Connection Type
- (Read only)
U16
1
-
-
FSoE Connection Communication Parameter: Communication Parameter Length
- (Read only)
U16
1
-
-
FSoE Connection Communication Parameter: Application Parameter Length
- (Read only)
U16
1
-
-
S-Bus: FSoE status
- (Read only)
U16
1
-
-
Safety addresses: FSoE address
- (Read only)
U16
1
-
-
Safety addresses: Safety address
1
Safety
U16
1
P
-